Emerson 5300, 5400 specifications Introduction, Workflow

Page 3

Manual Supplement

00809-0500-4530, Rev AA October 2010

Rosemount 5300/5400 Series

INTRODUCTION

The Rosemount 5300 Series and Rosemount 5400 Series transmitters are

 

Modbus compatible measurement devices that support communication with a

 

Remote Terminal Unit (RTU) using a subset of read, write, and diagnostic

 

commands used by most Modbus compatible host controllers. The

 

transmitters also support communication through Levelmaster and Modbus

 

ASCII protocols.

 

The HART® to Modbus Converter (HMC) module is located inside the

 

Rosemount 5300 and Rosemount 5400 transmitter enclosure and provides

 

power to and communicates with the transmitter through a HART interface.

Figure 1-1. System Overview

5300/5400 transmitter enclosure

 

 

HART

 

5300/5400

 

signals

HART to

transmitter

 

 

 

Modbus

electronics

 

 

 

Converter

 

 

 

 

 

Modbus and Levelmaster communication

HART signals

Remote

Terminal

Unit

Rosemount

Radar Master/

Field

Communicator

During normal operation, the HMC “mirrors” the contents of process variables from the 5300/5400 transmitter to the Modbus registers. To configure the 5300/5400 transmitter, it is possible to connect a configuration tool to the HMC. See “Transmitter Configuration” on page 1-13for more information.

WORKFLOW

Overview of workflow for commissioning a Rosemount 5300 or a Rosemount

 

5400 transmitter with Modbus protocol:

 

1.

Mount the transmitter on the tank.

 

2.

Connect the power and communication wires.

 

3.

Establish HART communication with the transmitter through Rosemount

 

 

Radar Master, or a Field Communicator. This is done by:

 

• Connecting to the HART terminals, or

 

• Connecting to the MA/MB terminals (tunneling mode)

 

4.

Configure the transmitter.

 

5.

Configure the Modbus communication.

 

6.

Configure Modbus host.

 

7.

Verify output values as reported by the transmitter.

1-3

Image 3
Contents Manual Supplement Rosemount 5300/5400 Series with Hart to Modbus ConverterExplosions could result in death or serious injury Safety MessagesWorkflow IntroductionMechanical Installation Electrical Installation Field Wiring Connections Hart + RS-485 Bus Installation casesAlternative Multidrop Connection of 5300/5400 Transmitters Star TopologyExternal Hart Devices Slaves No. of devices Approx. update rate SlavesConnect to the MA/MB terminals Establish Hart CommunicationRosemount 5300/5400 Series Connect to the Hart terminals Transmitter Configuration Using RRM to change communication parameters Modbus Communication Protocol ConfigurationModbus Setup Modbus RTU Parameter Configuration Example Levelmaster Communication Setup HMC A44 B4800 PO S2HMC A127 HMC M2 A2 B9600 D7 PN S1 Levelmaster Parameter Configuration ExampleImplemented Functions of Levelmaster Protocol HMC M1 A246 B9600 D7 PN S1 Modbus Ascii Communication SetupRosemount 5300/5400 Series Alarm Handling Modbus RTU LevelmasterModbus Ascii Rosemount 5300/5400 Series Input Registers Common Modbus Host ConfigurationBit information in bitfield 14. Output Variables for Floating Point Format Code Rosemount 5300/5400 Series Measurement Units Volume LengthEmerson Process Management ROC800 Series Specific Modbus Host ConfigurationABB TotalFlow Emerson Process Management FloBossBristol ControlWave Micro Thermo Electron AutopilotKimray Dacc 2000/3000 ScadaPackNo communication with Modbus Ascii protocol Troubleshooting No communication on RS-485 bus MA, MBNo 5300/5400 communication in RRM No communication with Modbus RTU protocolSelect Enable Modbus Communication and click OK HMC Firmware Upgrade in Rosemount Radar MasterRosemount 5300/5400 Series Click Browse Checksum Rosemount 5300/5400 Series Specifications Rosemount 5300/5400 Series Emerson Process Management Rosemount Measurement