Emerson specifications Rosemount 5300/5400 Series

Page 36

Rosemount 5300/5400 Series

Manual Supplement

00809-0500-4530, Rev AA October 2010

4.If the HMC is configured for Modbus ASCII or Levelmaster communication cycle the power to the transmitter (the HMC will then communicate using Modbus RTU for 20 seconds and under that time it is possible to connect with RRM).

5.Open the Search Device window and make sure Modbus is selected in the Protocol list.

6.Search for HMCs by selecting “Scan Address Range”, and choose a start and end address for Modbus. The default HMC Modbus address is 246.

7.Click the Start Scan button.

8.Click OK to connect when the device is found.

9.From the Service menu, choose the Enter Service Mode option.

10.Type password, “admin”.

1-36

Image 36
Contents Rosemount 5300/5400 Series with Hart to Modbus Converter Manual SupplementSafety Messages Explosions could result in death or serious injuryIntroduction WorkflowMechanical Installation Electrical Installation Field Wiring Connections Hart + Installation cases RS-485 BusStar Topology Alternative Multidrop Connection of 5300/5400 TransmittersNo. of devices Approx. update rate Slaves External Hart Devices SlavesEstablish Hart Communication Connect to the MA/MB terminalsRosemount 5300/5400 Series Connect to the Hart terminals Transmitter Configuration Modbus Communication Protocol Configuration Using RRM to change communication parametersModbus Setup Modbus RTU Parameter Configuration Example Levelmaster Communication Setup HMC A44 B4800 PO S2HMC A127 Levelmaster Parameter Configuration Example HMC M2 A2 B9600 D7 PN S1Implemented Functions of Levelmaster Protocol Modbus Ascii Communication Setup HMC M1 A246 B9600 D7 PN S1Rosemount 5300/5400 Series Alarm Handling Modbus RTU LevelmasterModbus Ascii Rosemount 5300/5400 Series Common Modbus Host Configuration Input RegistersBit information in bitfield 14. Output Variables for Floating Point Format Code Rosemount 5300/5400 Series Volume Length Measurement UnitsSpecific Modbus Host Configuration Emerson Process Management ROC800 SeriesEmerson Process Management FloBoss ABB TotalFlowThermo Electron Autopilot Bristol ControlWave MicroScadaPack Kimray Dacc 2000/3000Troubleshooting No communication on RS-485 bus MA, MB No 5300/5400 communication in RRMNo communication with Modbus RTU protocol No communication with Modbus Ascii protocolHMC Firmware Upgrade in Rosemount Radar Master Select Enable Modbus Communication and click OKRosemount 5300/5400 Series Click Browse Checksum Rosemount 5300/5400 Series Specifications Rosemount 5300/5400 Series Emerson Process Management Rosemount Measurement