Emerson 5300, 5400 specifications Output Variables for Floating Point Format Code

Page 27

Manual Supplement

00809-0500-4530, Rev AA October 2010

Rosemount 5300/5400 Series

Table 1-14. Output Variables for

 

 

 

Floating Point Format Code 0

 

 

 

Register Name

Register Number

Note

 

 

 

 

Bit information in bitfield:

 

 

 

Bit 0: Invalid Measurement Slave 1 PV.

 

 

 

Bit 1: Invalid Measurement Slave 1 SV.

 

 

 

Bit 2: Invalid Measurement Slave 1 TV.

 

 

 

Bit 3: Invalid Measurement Slave 1 FV.

 

Slave 1 Status

2000

Bit 14: HART bus busy (slave in burst or

 

other master present)

 

 

 

 

 

 

Bit 15: HTM Task not running (option not

 

 

 

available).

 

 

 

Note: Bit 1-3 is set when Invalid

 

 

 

Measurement of Slave 1 Non PV, i.e. all

 

 

 

three bits are set simultaneously.

 

 

 

Primary variable from slave 1

 

Slave 1 PV

2002

represented in IEEE 754 format, using

 

 

 

Floating Point Format Code 0.

 

 

 

Secondary variable from slave 1

 

Slave 1 SV

2004

represented in IEEE 754 format, using

 

 

 

Floating Point Format Code 0.

 

 

 

Tertiary variable from slave 1

 

Slave 1 TV

2006

represented in IEEE 754 format, using

 

 

 

Floating Point Format Code 0.

 

 

 

Fourth variable from slave 1 represented

 

Slave 1 FV (QV)

2008

in IEEE 754 format, using Floating Point

 

 

 

Format Code 0.

Table 1-15. Output Variables for

 

 

 

Floating Point Format Code 2

 

 

 

Register Name

Register Number

Note

 

 

 

 

Bit information in bitfield:

 

 

 

Bit 0: Invalid Measurement Slave 1 PV.

 

 

 

Bit 1: Invalid Measurement Slave 1 SV.

 

 

 

Bit 2: Invalid Measurement Slave 1 TV.

 

 

 

Bit 3: Invalid Measurement Slave 1 FV.

 

Slave 1 Status

2100

Bit 14: HART bus busy (slave in burst or

 

other master present)

 

 

 

 

 

 

Bit 15: HTM Task not running (option not

 

 

 

available).

 

 

 

Note: Bit 1-3 is set when Invalid

 

 

 

Measurement of Slave 1 Non PV, i.e. all

 

 

 

three bits are set simultaneously.

 

 

 

Primary variable from slave 1

 

Slave 1 PV

2102

represented in IEEE 754 format, using

 

 

 

Floating Point Format Code 2.

 

 

 

 

1-27

Image 27
Contents Manual Supplement Rosemount 5300/5400 Series with Hart to Modbus ConverterExplosions could result in death or serious injury Safety MessagesWorkflow IntroductionMechanical Installation Electrical Installation Field Wiring Connections Hart + RS-485 Bus Installation casesAlternative Multidrop Connection of 5300/5400 Transmitters Star TopologyExternal Hart Devices Slaves No. of devices Approx. update rate SlavesConnect to the MA/MB terminals Establish Hart CommunicationRosemount 5300/5400 Series Connect to the Hart terminals Transmitter Configuration Using RRM to change communication parameters Modbus Communication Protocol ConfigurationModbus Setup Modbus RTU Parameter Configuration Example Levelmaster Communication Setup HMC A44 B4800 PO S2HMC A127 HMC M2 A2 B9600 D7 PN S1 Levelmaster Parameter Configuration ExampleImplemented Functions of Levelmaster Protocol HMC M1 A246 B9600 D7 PN S1 Modbus Ascii Communication SetupRosemount 5300/5400 Series Alarm Handling Modbus RTU LevelmasterModbus Ascii Rosemount 5300/5400 Series Input Registers Common Modbus Host ConfigurationBit information in bitfield 14. Output Variables for Floating Point Format Code Rosemount 5300/5400 Series Measurement Units Volume LengthEmerson Process Management ROC800 Series Specific Modbus Host ConfigurationABB TotalFlow Emerson Process Management FloBossBristol ControlWave Micro Thermo Electron AutopilotKimray Dacc 2000/3000 ScadaPackNo communication with Modbus Ascii protocol Troubleshooting No communication on RS-485 bus MA, MBNo 5300/5400 communication in RRM No communication with Modbus RTU protocolSelect Enable Modbus Communication and click OK HMC Firmware Upgrade in Rosemount Radar MasterRosemount 5300/5400 Series Click Browse Checksum Rosemount 5300/5400 Series Specifications Rosemount 5300/5400 Series Emerson Process Management Rosemount Measurement