Rosemount 5300/5400 Series

Manual Supplement

00809-0500-4530, Rev AA October 2010

Thermo Electron Autopilot

Figure 1-12. Wiring Diagram for

Connecting 5300/5400 Modbus to

Thermo Electron Autopilot

5300/5400 Modbus

MA

MB

POWER +

POWER -

AutoPILOT

CEB TB1

1 RX +

2 RX -

Table 1-22. Parameter Values (in case of Thermo Electron Autopilot)

Power Supply

+8 to + 30 Vdc (max. rating)

GND

Parameter

Value

Baud Rate

9600

Floating Point Format Code

1

RTU Data Type

IEEE Flt 2R

Input Register Base Number

0

 

 

The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1302 needs to have 1302 entered as the address etc.

Bristol ControlWave Micro

Figure 1-13. Wiring Diagram for Connecting 5300/5400 Modbus to Bristol ControlWave Micro

Table 1-23. Parameter Values (in case of Bristol ControlWave Micro)

 

ControlWave Micro

5300/5400 Modbus

Com Port 3 (C3) RS-485

MA

 

 

 

MB

 

1

 

POWER +

 

6

 

2

POWER -

 

7

TXD-

3

 

8

 

TXD+

4

Power Supply

9

GND

5

+ 8 to + 30 Vdc

 

 

 

 

(max. rating)

 

DB9 Male

GND

 

 

 

 

Parameter

 

Value

 

Baud Rate

9600

 

 

Floating Point Format Code

2 (FC 4)

 

 

RTU Data Type

32-bit registers as 2 16-bit registers

 

 

Input Register Base Number

1

The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1302 needs to have 1303 entered as the address etc.

1-32

Image 32
Contents Rosemount 5300/5400 Series with Hart to Modbus Converter Manual SupplementSafety Messages Explosions could result in death or serious injuryIntroduction WorkflowMechanical Installation Electrical Installation Field Wiring Connections Hart + Installation cases RS-485 BusStar Topology Alternative Multidrop Connection of 5300/5400 TransmittersNo. of devices Approx. update rate Slaves External Hart Devices SlavesEstablish Hart Communication Connect to the MA/MB terminalsRosemount 5300/5400 Series Connect to the Hart terminals Transmitter Configuration Modbus Communication Protocol Configuration Using RRM to change communication parametersModbus Setup Modbus RTU Parameter Configuration Example HMC A127 Levelmaster Communication SetupHMC A44 B4800 PO S2 Levelmaster Parameter Configuration Example HMC M2 A2 B9600 D7 PN S1Implemented Functions of Levelmaster Protocol Modbus Ascii Communication Setup HMC M1 A246 B9600 D7 PN S1Rosemount 5300/5400 Series Alarm Handling Modbus Ascii Modbus RTULevelmaster Rosemount 5300/5400 Series Common Modbus Host Configuration Input RegistersBit information in bitfield 14. Output Variables for Floating Point Format Code Rosemount 5300/5400 Series Volume Length Measurement UnitsSpecific Modbus Host Configuration Emerson Process Management ROC800 SeriesEmerson Process Management FloBoss ABB TotalFlowThermo Electron Autopilot Bristol ControlWave MicroScadaPack Kimray Dacc 2000/3000Troubleshooting No communication on RS-485 bus MA, MB No 5300/5400 communication in RRMNo communication with Modbus RTU protocol No communication with Modbus Ascii protocolHMC Firmware Upgrade in Rosemount Radar Master Select Enable Modbus Communication and click OKRosemount 5300/5400 Series Click Browse Checksum Rosemount 5300/5400 Series Specifications Rosemount 5300/5400 Series Emerson Process Management Rosemount Measurement