Emerson 5300, 5400 specifications ScadaPack, Kimray Dacc 2000/3000

Page 33

Manual Supplement

00809-0500-4530, Rev AA October 2010

Rosemount 5300/5400 Series

ScadaPack

Figure 1-14. Wiring Diagram for

Connecting 5300/5400 Modbus to

SCADAPack 32

5300/5400 Modbus

MA

MB

POWER +

POWER -

Power Supply

+ 8 to + 30 Vdc

(max. rating)

REF

SCADAPack32

RS-485 on COM1

1 +5 V

2RX-

3TX-

4 GND

5RX+

6TX+

7Not Used

8Not Used

Table 1-24. Parameter Values (in case of SCADAPack 32)

Kimray DACC 2000/3000

Parameter

Value

Baud Rate

9600

Floating Point Format Code

0

RTU Data Type

Floating Point

Input Register Base Number

30001

 

 

The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1302 needs to have 31303 entered as the address etc.

This table shows input types in Kimray IMI software and the corresponding value. The communication port must be configured to use “Tank Levels” protocol.

Table 1-25. Kimray Input Types and

 

 

 

Corresponding Values

 

 

 

Kimray Inp type

5300/5400 variable

Format

 

 

Tank Level1

PV

ddd.dd.alt. -dd.dd

 

Tank Level2

SV

ddd.dd.alt -dd.dd

 

 

 

 

1-33

Image 33
Contents Manual Supplement Rosemount 5300/5400 Series with Hart to Modbus ConverterExplosions could result in death or serious injury Safety MessagesWorkflow IntroductionMechanical Installation Electrical Installation Field Wiring Connections Hart + RS-485 Bus Installation casesAlternative Multidrop Connection of 5300/5400 Transmitters Star TopologyExternal Hart Devices Slaves No. of devices Approx. update rate SlavesConnect to the MA/MB terminals Establish Hart CommunicationRosemount 5300/5400 Series Connect to the Hart terminals Transmitter Configuration Using RRM to change communication parameters Modbus Communication Protocol ConfigurationModbus Setup Modbus RTU Parameter Configuration Example Levelmaster Communication Setup HMC A44 B4800 PO S2HMC A127 HMC M2 A2 B9600 D7 PN S1 Levelmaster Parameter Configuration ExampleImplemented Functions of Levelmaster Protocol HMC M1 A246 B9600 D7 PN S1 Modbus Ascii Communication SetupRosemount 5300/5400 Series Alarm Handling Modbus RTU LevelmasterModbus Ascii Rosemount 5300/5400 Series Input Registers Common Modbus Host ConfigurationBit information in bitfield 14. Output Variables for Floating Point Format Code Rosemount 5300/5400 Series Measurement Units Volume LengthEmerson Process Management ROC800 Series Specific Modbus Host ConfigurationABB TotalFlow Emerson Process Management FloBossBristol ControlWave Micro Thermo Electron AutopilotKimray Dacc 2000/3000 ScadaPackNo 5300/5400 communication in RRM Troubleshooting No communication on RS-485 bus MA, MBNo communication with Modbus RTU protocol No communication with Modbus Ascii protocolSelect Enable Modbus Communication and click OK HMC Firmware Upgrade in Rosemount Radar MasterRosemount 5300/5400 Series Click Browse Checksum Rosemount 5300/5400 Series Specifications Rosemount 5300/5400 Series Emerson Process Management Rosemount Measurement