Emerson 5400, 5300 specifications Modbus RTU Parameter Configuration Example

Page 16

Rosemount 5300/5400 Series

Manual Supplement

00809-0500-4530, Rev AA October 2010

Using a Field Communicator to change communication parameters

Modbus RTU Communication Setup

Table 1-4. Modbus RTU Communication Parameters

NOTE

To change Modbus communication parameters, the Rosemount 5300/5400 must use HART address 1, the default address.

NOTE

After changing communication parameters, disconnect the Field Communicator and wait up to 60 seconds for the change to take effect.

The Modbus communication parameters can be changed by entering a text string in the HART Message parameter. See separate sections below for details regarding each Modbus protocol and what strings to use.

When using the Field Communicator, the Message Area is reached using HART command [2,2,1], and then selecting Message (menu item 11 for Rosemount 5300 and menu item 10 for Rosemount 5400).

The Rosemount 5300/5400 is configured with the default Modbus RTU address 246, and with the following Modbus RTU communication parameter default settings:

Parameter

Default Value

Configurable Values

Baud Rate

9600

1200, 2400, 4800, 9600, 19200

Start Bits(1)

One

One

Data Bits(1)

Eight

Eight

Parity

None

None, Odd, Even

Stop Bits

One

One or Two

Address

246

1-255

range

 

 

 

 

 

(1) Start Bits and Data Bits cannot be changed.

Table 1-5. Communication Parameters Used by the Host (example)

To reset the communication parameters to default Modbus RTU settings, use the following Modbus Message:

HMC

Modbus RTU Parameter Configuration Example

You want to use address 44 for the 5300/5400 transmitter, and the following communication parameters are used by the host:

Parameter

Value

Baud Rate

4800

Start Bits

One

Data Bits

Eight

Parity

Odd

Stop Bits

Two

 

 

1-16

Image 16
Contents Rosemount 5300/5400 Series with Hart to Modbus Converter Manual SupplementSafety Messages Explosions could result in death or serious injuryIntroduction WorkflowMechanical Installation Electrical Installation Field Wiring Connections Hart + Installation cases RS-485 BusStar Topology Alternative Multidrop Connection of 5300/5400 TransmittersNo. of devices Approx. update rate Slaves External Hart Devices SlavesEstablish Hart Communication Connect to the MA/MB terminalsRosemount 5300/5400 Series Connect to the Hart terminals Transmitter Configuration Modbus Communication Protocol Configuration Using RRM to change communication parametersModbus Setup Modbus RTU Parameter Configuration Example HMC A44 B4800 PO S2 Levelmaster Communication SetupHMC A127 Levelmaster Parameter Configuration Example HMC M2 A2 B9600 D7 PN S1Implemented Functions of Levelmaster Protocol Modbus Ascii Communication Setup HMC M1 A246 B9600 D7 PN S1Rosemount 5300/5400 Series Alarm Handling Levelmaster Modbus RTUModbus Ascii Rosemount 5300/5400 Series Common Modbus Host Configuration Input RegistersBit information in bitfield 14. Output Variables for Floating Point Format Code Rosemount 5300/5400 Series Volume Length Measurement UnitsSpecific Modbus Host Configuration Emerson Process Management ROC800 SeriesEmerson Process Management FloBoss ABB TotalFlowThermo Electron Autopilot Bristol ControlWave MicroScadaPack Kimray Dacc 2000/3000Troubleshooting No communication on RS-485 bus MA, MB No 5300/5400 communication in RRMNo communication with Modbus RTU protocol No communication with Modbus Ascii protocolHMC Firmware Upgrade in Rosemount Radar Master Select Enable Modbus Communication and click OKRosemount 5300/5400 Series Click Browse Checksum Rosemount 5300/5400 Series Specifications Rosemount 5300/5400 Series Emerson Process Management Rosemount Measurement