Rosemount 5300/5400 Series

RS-485 Bus

The 5300/5400 transmitters do not provide electrical isolation between the RS-485 bus and the transmitter power supply

Maintain a bus topology and minimize stub length

Figure 1-4 identifies multidrop wiring topology, where up to 32 devices may be wired on one RS-485 bus

The RS-485 bus needs to be terminated once at each end, but should not be terminated elsewhere on the bus

Installation cases

Install the Rosemount 5300/5400 Series Transmitters as shown in Figure 1-4.

Use common ground for Modbus Master and Power Supply

The Power cables and RS-485 Bus are in the same cable installation

An ground cable is installed and shall be used (cable size ≥4 mm according to IEC60079-14, or size according to applicable national regulations and standards). A properly installed threaded conduit connection may provide sufficient ground.

The cable shielding is grounded at master site (optional)

NOTE

The HMC equipped transmitter contains intrinsically safe circuits that require the housing to be grounded in accordance with national and local electrical codes. Failure to do so may impair the protection provided by the equipment.

Figure 1-4. Multidrop Connection of 5300/5400 Transmitters

120Ω

RS-485 Bus

HART to Modbus Converter

MB

 

MODBUS MA

-

 

(RS-485)

-

POWER

 

+

 

 

HART Ambients > 60 ºC

+

Use wiring rated

 

for min 90 ºC

 

HART to Modbus Converter

MB

 

MODBUS MA

-

 

(RS-485)

-

POWER

 

 

+

 

 

 

HART Ambients > 60 ºC

+

Use wiring rated

 

 

for min 90 ºC

 

 

120Ω

BModbus

A Master

Z

Power

Supply

Internal

 

Internal

 

Ground Screw

External

Ground Screw

External

 

Ground Screw

 

Ground Screw

1-7

Image 7
Contents Manual Supplement Rosemount 5300/5400 Series with Hart to Modbus ConverterExplosions could result in death or serious injury Safety MessagesWorkflow IntroductionMechanical Installation Electrical Installation Field Wiring Connections Hart + RS-485 Bus Installation casesAlternative Multidrop Connection of 5300/5400 Transmitters Star TopologyExternal Hart Devices Slaves No. of devices Approx. update rate SlavesConnect to the MA/MB terminals Establish Hart CommunicationRosemount 5300/5400 Series Connect to the Hart terminals Transmitter Configuration Using RRM to change communication parameters Modbus Communication Protocol ConfigurationModbus Setup Modbus RTU Parameter Configuration Example HMC A44 B4800 PO S2 Levelmaster Communication SetupHMC A127 HMC M2 A2 B9600 D7 PN S1 Levelmaster Parameter Configuration ExampleImplemented Functions of Levelmaster Protocol HMC M1 A246 B9600 D7 PN S1 Modbus Ascii Communication SetupRosemount 5300/5400 Series Alarm Handling Levelmaster Modbus RTUModbus Ascii Rosemount 5300/5400 Series Input Registers Common Modbus Host ConfigurationBit information in bitfield 14. Output Variables for Floating Point Format Code Rosemount 5300/5400 Series Measurement Units Volume LengthEmerson Process Management ROC800 Series Specific Modbus Host ConfigurationABB TotalFlow Emerson Process Management FloBossBristol ControlWave Micro Thermo Electron AutopilotKimray Dacc 2000/3000 ScadaPackNo communication with Modbus Ascii protocol Troubleshooting No communication on RS-485 bus MA, MBNo 5300/5400 communication in RRM No communication with Modbus RTU protocolSelect Enable Modbus Communication and click OK HMC Firmware Upgrade in Rosemount Radar MasterRosemount 5300/5400 Series Click Browse Checksum Rosemount 5300/5400 Series Specifications Rosemount 5300/5400 Series Emerson Process Management Rosemount Measurement