Manual Supplement
Rosemount 5300/5400 Series
RS-485 Bus
•The 5300/5400 transmitters do not provide electrical isolation between the
•Maintain a bus topology and minimize stub length
•Figure 1-4 identifies multidrop wiring topology, where up to 32 devices may be wired on one RS-485 bus
•The RS-485 bus needs to be terminated once at each end, but should not be terminated elsewhere on the bus
Installation cases
Install the Rosemount 5300/5400 Series Transmitters as shown in Figure
•Use common ground for Modbus Master and Power Supply
•The Power cables and
•An ground cable is installed and shall be used (cable size ≥4 mm according to
•The cable shielding is grounded at master site (optional)
NOTE
The HMC equipped transmitter contains intrinsically safe circuits that require the housing to be grounded in accordance with national and local electrical codes. Failure to do so may impair the protection provided by the equipment.
Figure 1-4. Multidrop Connection of 5300/5400 Transmitters
120Ω |
|
HART to Modbus Converter
MB
| MODBUS MA | - | |
| |||
- | POWER |
| + |
| |||
| HART Ambients > 60 ºC | ||
+ | Use wiring rated |
| |
for min 90 ºC |
|