Emerson 5300, 5400 specifications Implemented Functions of Levelmaster Protocol

Page 19

Manual Supplement

00809-0500-4530, Rev AA October 2010

Rosemount 5300/5400 Series

Table 1-8. Implemented Functions of Levelmaster Protocol

Table 1-9. Letters and Expressions Used in Previous Tables

In Table 1-8 and Table 1-9 is a description of the implemented functions of Levelmaster protocol in the HMC.

Input format

Description

Output format

UnnN?

Return ID number

UnnNnnCcccc

UnnNmm

Set ID number

UnnNOKCcccc

UnnF?

Return number of floats

UnnFxCcccc

UnnFx?

Set number of floats

UnnFOKCcccc

Unn?

Return floats and other data

UnnDddd.ddFfffEeeee

WwwwCcccc(1)

 

 

(1)In this case, number of floats is set to 1. If number of floats is set to 2, the Output Format would be: UnnDddd.ddDddd.ddFfffEeeeeWwwwCcccc

NOTE

If one float is sent, it is “Float1”. If two floats are sent, it is “Float 1” before “Float 0”.

Letter

Description

 

nn is used to identify slave to respond,

nn

nn is a number 00-99 or ** (wildcard).

The EmulCtrl Address Holding register can be configured to a higher

 

 

value than 99. In that case, the address will be truncated to 99.

mm

mm is the new ID number for the slave; mm is a number 00-99.

x

x is the number of floats returned when slave receives Unn?, x is a

number 0-2.

 

cccc

Is the 16 bit CRC checksum, cccc are hexadecimal characters.

ddd.dd

ddd.dd is the distance value from slave 1. Note that the first d can also be

a ‘-’ (minus).

 

Float 1

Slave 1 PV.

Float 0

Slave 1 SV.

fff

The temperature value. Configured by Holding Register 3208 in HMC.(1)

 

An error value.

eeee

Bit 0: Invalid SV value (Float 0).

Bit 8: Invalid Temperature value.

 

 

Bit 12: Invalid PV value (Float 1).

Wwww

A warning value, not used in this implementation.

 

 

(1)Any of the four available variables from any of the five HART slaves can be selected as the temperature source.

The least four significant bits (bit 0-3) select the variable number. Bits 4-7 select the HART slave address. If invalid values are used, the temperature value will be invalid, with no Error bit set.

For example, if we want to use FV from HART Slave 3 as temperature source, we have to write the value 34 Hex (52 decimal).

1-19

Image 19
Contents Manual Supplement Rosemount 5300/5400 Series with Hart to Modbus ConverterExplosions could result in death or serious injury Safety MessagesWorkflow IntroductionMechanical Installation Electrical Installation Field Wiring Connections Hart + RS-485 Bus Installation casesAlternative Multidrop Connection of 5300/5400 Transmitters Star TopologyExternal Hart Devices Slaves No. of devices Approx. update rate SlavesConnect to the MA/MB terminals Establish Hart CommunicationRosemount 5300/5400 Series Connect to the Hart terminals Transmitter Configuration Using RRM to change communication parameters Modbus Communication Protocol ConfigurationModbus Setup Modbus RTU Parameter Configuration Example HMC A44 B4800 PO S2 Levelmaster Communication SetupHMC A127 HMC M2 A2 B9600 D7 PN S1 Levelmaster Parameter Configuration ExampleImplemented Functions of Levelmaster Protocol HMC M1 A246 B9600 D7 PN S1 Modbus Ascii Communication SetupRosemount 5300/5400 Series Alarm Handling Levelmaster Modbus RTUModbus Ascii Rosemount 5300/5400 Series Input Registers Common Modbus Host ConfigurationBit information in bitfield 14. Output Variables for Floating Point Format Code Rosemount 5300/5400 Series Measurement Units Volume LengthEmerson Process Management ROC800 Series Specific Modbus Host ConfigurationABB TotalFlow Emerson Process Management FloBossBristol ControlWave Micro Thermo Electron AutopilotKimray Dacc 2000/3000 ScadaPackNo communication with Modbus Ascii protocol Troubleshooting No communication on RS-485 bus MA, MBNo 5300/5400 communication in RRM No communication with Modbus RTU protocolSelect Enable Modbus Communication and click OK HMC Firmware Upgrade in Rosemount Radar MasterRosemount 5300/5400 Series Click Browse Checksum Rosemount 5300/5400 Series Specifications Rosemount 5300/5400 Series Emerson Process Management Rosemount Measurement