Emerson 5400, 5300 specifications Modbus Ascii Communication Setup, HMC M1 A246 B9600 D7 PN S1

Page 20

Rosemount 5300/5400 Series

Manual Supplement

00809-0500-4530, Rev AA October 2010

Modbus ASCII Communication Setup

Table 1-10. Modbus ASCII Communication Parameters

Table 1-11. Parameters Used by the Host (in case of Modbus ASCII, example)

The parameter, default, and configurable values are shown in Table 1-10 below.

Parameter

Default value

Configurable values

Baud Rate

9600

1200, 2400, 4800, 9600, 19200

Start Bits

One

One

Data Bits

Seven

Seven, Eight

Parity

None

None, Odd, even

Stop Bits

One

One or Two

Address

1

1-255

 

 

 

To reset the communication parameters to default Modbus ASCII settings, use the following Modbus Message:

HMC M1

Modbus ASCII Parameter Configuration Example

You want to use address 246 for the 5300/5400 transmitter and the host uses the following parameters:

Parameter

Value

Baud Rate

9600

Start Bits

One

Data Bits

Seven

Parity

None

Stop Bits

One

 

 

To configure the 5300/5400 transmitter to communicate with the Host in this example, the following text string is written to the Modbus Message area.

HMC M1 A246 B9600 D7 PN S1.

NOTE

Include all the parameters when writing to the message area.

Note that an address must be unique on the bus.

HMC: These three letters are used for safety and will eliminate the risk of changing the configuration data by mistake.

M1: This means that the Modbus ASCII protocol is to be used.

A246: A indicates that the following number is the new address (address 246). Leading zeroes are not needed.

B9600: B indicates that the following number is the new baud rate (1200, 2400, 4800, 9600, 19200).

1-20

Image 20
Contents Rosemount 5300/5400 Series with Hart to Modbus Converter Manual SupplementSafety Messages Explosions could result in death or serious injuryIntroduction WorkflowMechanical Installation Electrical Installation Field Wiring Connections Hart + Installation cases RS-485 BusStar Topology Alternative Multidrop Connection of 5300/5400 TransmittersNo. of devices Approx. update rate Slaves External Hart Devices SlavesEstablish Hart Communication Connect to the MA/MB terminalsRosemount 5300/5400 Series Connect to the Hart terminals Transmitter Configuration Modbus Communication Protocol Configuration Using RRM to change communication parametersModbus Setup Modbus RTU Parameter Configuration Example HMC A127 Levelmaster Communication SetupHMC A44 B4800 PO S2 Levelmaster Parameter Configuration Example HMC M2 A2 B9600 D7 PN S1Implemented Functions of Levelmaster Protocol Modbus Ascii Communication Setup HMC M1 A246 B9600 D7 PN S1Rosemount 5300/5400 Series Alarm Handling Modbus Ascii Modbus RTULevelmaster Rosemount 5300/5400 Series Common Modbus Host Configuration Input RegistersBit information in bitfield 14. Output Variables for Floating Point Format Code Rosemount 5300/5400 Series Volume Length Measurement UnitsSpecific Modbus Host Configuration Emerson Process Management ROC800 SeriesEmerson Process Management FloBoss ABB TotalFlowThermo Electron Autopilot Bristol ControlWave MicroScadaPack Kimray Dacc 2000/3000Troubleshooting No communication on RS-485 bus MA, MB No 5300/5400 communication in RRMNo communication with Modbus RTU protocol No communication with Modbus Ascii protocolHMC Firmware Upgrade in Rosemount Radar Master Select Enable Modbus Communication and click OKRosemount 5300/5400 Series Click Browse Checksum Rosemount 5300/5400 Series Specifications Rosemount 5300/5400 Series Emerson Process Management Rosemount Measurement