Rosemount 5300/5400 Series
Manual Supplement
Alternatively, the Rosemount 5300/5400 Series Transmitters can be installed as shown in Figure
Figure 1-5. Alternative Multidrop
Connection of 5300/5400
Transmitters
120Ω |
HART to Modbus Converter
MB
| MODBUS MA | - | |
| |||
- | POWER |
| + |
| |||
| HART Ambients > 60 ºC | ||
+ | Use wiring rated |
| |
for min 90 ºC |
|
HART to Modbus Converter
MB
| MODBUS MA | - | ||
| ||||
- | POWER |
|
| + |
|
| |||
| HART Ambients > 60 ºC | |||
+ | Use wiring rated |
|
| |
for min 90 ºC |
|
|
120Ω
BModbus
A Master
Z
Internal | Internal |
Ground Screw | Ground Screw |
External | External |
Ground Screw | Ground Screw |
Star Topology
Power Supply
For a Star Topology Connection of the 5300/5400 transmitters, the transmitter with the longest cable run needs to be fitted with a
Figure 1-6. Star Topology
Connection of 5300/5400
Transmitters
verter
MB
MODBUS MA
For Star Topology connection, connect the 120Ω termination resistor to the transmitter with the longest cable run.