Emerson Star Topology, Alternative Multidrop Connection of 5300/5400 Transmitters

Page 8

Rosemount 5300/5400 Series

Manual Supplement

00809-0500-4530, Rev AA October 2010

Alternatively, the Rosemount 5300/5400 Series Transmitters can be installed as shown in Figure 1-5. If this wiring layout is used, there is an increased risk for communication disturbances due to differences in potential between grounding points. By using the same grounding point for Modbus Master and Power Supply, this risk is reduced.

Figure 1-5. Alternative Multidrop

Connection of 5300/5400

Transmitters

120Ω

RS-485 Bus

HART to Modbus Converter

MB

 

MODBUS MA

-

 

(RS-485)

-

POWER

 

+

 

 

HART Ambients > 60 ºC

+

Use wiring rated

 

for min 90 ºC

 

HART to Modbus Converter

MB

 

MODBUS MA

-

 

(RS-485)

-

POWER

 

 

+

 

 

 

HART Ambients > 60 ºC

+

Use wiring rated

 

 

for min 90 ºC

 

 

120Ω

BModbus

A Master

Z

Internal

Internal

Ground Screw

Ground Screw

External

External

Ground Screw

Ground Screw

Star Topology

Power Supply

For a Star Topology Connection of the 5300/5400 transmitters, the transmitter with the longest cable run needs to be fitted with a 120-Ωtermination resistor.

Figure 1-6. Star Topology

Connection of 5300/5400

Transmitters

verter

MB

MODBUS MA

(RS-485) -

For Star Topology connection, connect the 120Ω termination resistor to the transmitter with the longest cable run.

1-8

Image 8
Contents Rosemount 5300/5400 Series with Hart to Modbus Converter Manual SupplementSafety Messages Explosions could result in death or serious injuryIntroduction WorkflowMechanical Installation Electrical Installation Field Wiring Connections Hart + Installation cases RS-485 BusStar Topology Alternative Multidrop Connection of 5300/5400 TransmittersNo. of devices Approx. update rate Slaves External Hart Devices SlavesEstablish Hart Communication Connect to the MA/MB terminalsRosemount 5300/5400 Series Connect to the Hart terminals Transmitter Configuration Modbus Communication Protocol Configuration Using RRM to change communication parametersModbus Setup Modbus RTU Parameter Configuration Example HMC A127 Levelmaster Communication SetupHMC A44 B4800 PO S2 Levelmaster Parameter Configuration Example HMC M2 A2 B9600 D7 PN S1Implemented Functions of Levelmaster Protocol Modbus Ascii Communication Setup HMC M1 A246 B9600 D7 PN S1Rosemount 5300/5400 Series Alarm Handling Modbus Ascii Modbus RTULevelmaster Rosemount 5300/5400 Series Common Modbus Host Configuration Input RegistersBit information in bitfield 14. Output Variables for Floating Point Format Code Rosemount 5300/5400 Series Volume Length Measurement UnitsSpecific Modbus Host Configuration Emerson Process Management ROC800 SeriesEmerson Process Management FloBoss ABB TotalFlowThermo Electron Autopilot Bristol ControlWave MicroScadaPack Kimray Dacc 2000/3000Troubleshooting No communication on RS-485 bus MA, MB No 5300/5400 communication in RRMNo communication with Modbus RTU protocol No communication with Modbus Ascii protocolHMC Firmware Upgrade in Rosemount Radar Master Select Enable Modbus Communication and click OKRosemount 5300/5400 Series Click Browse Checksum Rosemount 5300/5400 Series Specifications Rosemount 5300/5400 Series Emerson Process Management Rosemount Measurement