Emerson 5400, 5300 specifications Bit information in bitfield

Page 26

Rosemount 5300/5400 Series

Manual Supplement

00809-0500-4530, Rev AA October 2010

Table 1-13. Output Variables for the Configurable Floating Point Format (default code 1)

Register Name

Register

Note

Number

 

 

 

 

Bit information in bitfield.

 

 

Bit 0: Invalid Measurement Slave 1 PV.

 

 

Bit 1: Invalid Measurement Slave 1 Non PV.

 

 

Bit 2: Invalid Measurement Slave 1 Non PV.

Slave 1 Status

 

Bit 3: Invalid Measurement Slave 1 Non PV.

1300

Bit 14: HART bus busy (slave in burst or other

Conf

master present)

 

 

 

Bit 15: HTM Task not running (option not

 

 

available).

 

 

Note: Bit 1-3 is set when Invalid Measurement of

 

 

Slave 1 Non PV. i.e. all three bits are set

 

 

simultaneously.

 

 

Primary variable from slave 1 represented in

Slave 1 PV Conf

1302

IEEE 754 format, using the byte order set in the

 

 

FloatingPointFormatCode register.

 

 

Secondary variable from slave 1 represented in

Slave 1 SV Conf

1304

IEEE 754 format, using the byte order set in the

 

 

FloatingPointFormatCode register.

 

 

Tertiary variable from slave 1 represented in

Slave 1 TV Conf

1306

IEEE 754 format, using the byte order set in the

 

 

FloatingPointFormatCode register.

 

 

Fourth variable from slave 1 represented in IEEE

Slave 1 FV Conf

1308

754 format, using the byte order set in the

 

 

FloatingPointFormatCode register.

Slave 2 data

1310-1318

Same data as for Slave 1.

Slave 3 data

1320-1328

Same data as for Slave 1.

Slave 4 data

1330-1338

Same data as for Slave 1.

Slave 5 data

1340-1348

Same data as for Slave 1.

 

 

 

The Rosemount 5300/5400 register area starting with register 2000 is used for hosts that require Floating Point Format Code 0 (see Table 1-14).

Floating Point Format Codes 2 and 3 use register areas 2100 and 2200, respectively (see Table 1-15and Table 1-16).

1-26

Image 26
Contents Rosemount 5300/5400 Series with Hart to Modbus Converter Manual SupplementSafety Messages Explosions could result in death or serious injuryIntroduction WorkflowMechanical Installation Electrical Installation Field Wiring Connections Hart + Installation cases RS-485 BusStar Topology Alternative Multidrop Connection of 5300/5400 TransmittersNo. of devices Approx. update rate Slaves External Hart Devices SlavesEstablish Hart Communication Connect to the MA/MB terminalsRosemount 5300/5400 Series Connect to the Hart terminals Transmitter Configuration Modbus Communication Protocol Configuration Using RRM to change communication parametersModbus Setup Modbus RTU Parameter Configuration Example HMC A127 Levelmaster Communication SetupHMC A44 B4800 PO S2 Levelmaster Parameter Configuration Example HMC M2 A2 B9600 D7 PN S1Implemented Functions of Levelmaster Protocol Modbus Ascii Communication Setup HMC M1 A246 B9600 D7 PN S1Rosemount 5300/5400 Series Alarm Handling Modbus Ascii Modbus RTULevelmaster Rosemount 5300/5400 Series Common Modbus Host Configuration Input RegistersBit information in bitfield 14. Output Variables for Floating Point Format Code Rosemount 5300/5400 Series Volume Length Measurement UnitsSpecific Modbus Host Configuration Emerson Process Management ROC800 SeriesEmerson Process Management FloBoss ABB TotalFlowThermo Electron Autopilot Bristol ControlWave MicroScadaPack Kimray Dacc 2000/3000No communication with Modbus RTU protocol Troubleshooting No communication on RS-485 bus MA, MBNo 5300/5400 communication in RRM No communication with Modbus Ascii protocolHMC Firmware Upgrade in Rosemount Radar Master Select Enable Modbus Communication and click OKRosemount 5300/5400 Series Click Browse Checksum Rosemount 5300/5400 Series Specifications Rosemount 5300/5400 Series Emerson Process Management Rosemount Measurement