Emerson 5400, 5300 specifications Connect to the Hart terminals

Page 12

Rosemount 5300/5400 Series

Manual Supplement

00809-0500-4530, Rev AA October 2010

6.Connect to the transmitter and perform the necessary configuration.

7.After completing the configuration, disconnect the RS-485 Converter, connect the Modbus communication wires and cycle power to the transmitter

8.Verify communication between the transmitter and the RTU is established (can take up to 60 seconds from startup).

NOTE

Take the following into consideration if there are multiple 5300/5400 Modbus units on the bus:

By default, the transmitters have HART address 1. It will not be possible to establish communication on HART address 1 if several transmitters have the same address. In this case, there are alternative solutions to establish communication:

Connect to the HART terminals

1.Select the Scan by Tag option in the Search Device window in RRM and enter the HART Device Tag of the transmitter. Communication can now be established with an individual transmitter even if several devices have the same HART address.

2.Make sure the 5300/5400 transmitter is alone on bus. Disconnect or turn off power from any other devices.

To configure the 5300/5400 transmitter, connect the communicator or PC to the HART terminals using a HART modem, see Figure 1-3 on page 1-6. Both the configuration tool and the RS-485 bus can be connected simultaneously. Configuration data is sent with HART commands through the HMC to the 5300/5400 transmitter electronics, as illustrated in Figure 1-1 on page 1-3. Note that the power supply must be connected during configuration, see also “Electrical Installation” on page 1-4.

NOTE

Measurement data is not updated to the Modbus Master when a configuration tool is connected.

1-12

Image 12
Contents Rosemount 5300/5400 Series with Hart to Modbus Converter Manual SupplementSafety Messages Explosions could result in death or serious injuryIntroduction WorkflowMechanical Installation Electrical Installation Field Wiring Connections Hart + Installation cases RS-485 BusStar Topology Alternative Multidrop Connection of 5300/5400 Transmitters No. of devices Approx. update rate Slaves External Hart Devices SlavesEstablish Hart Communication Connect to the MA/MB terminalsRosemount 5300/5400 Series Connect to the Hart terminals Transmitter Configuration Modbus Communication Protocol Configuration Using RRM to change communication parametersModbus Setup Modbus RTU Parameter Configuration Example Levelmaster Communication Setup HMC A44 B4800 PO S2HMC A127 Levelmaster Parameter Configuration Example HMC M2 A2 B9600 D7 PN S1Implemented Functions of Levelmaster Protocol Modbus Ascii Communication Setup HMC M1 A246 B9600 D7 PN S1Rosemount 5300/5400 Series Alarm Handling Modbus RTU LevelmasterModbus Ascii Rosemount 5300/5400 Series Common Modbus Host Configuration Input RegistersBit information in bitfield 14. Output Variables for Floating Point Format Code Rosemount 5300/5400 Series Volume Length Measurement UnitsSpecific Modbus Host Configuration Emerson Process Management ROC800 SeriesEmerson Process Management FloBoss ABB TotalFlowThermo Electron Autopilot Bristol ControlWave MicroScadaPack Kimray Dacc 2000/3000Troubleshooting No communication on RS-485 bus MA, MB No 5300/5400 communication in RRMNo communication with Modbus RTU protocol No communication with Modbus Ascii protocolHMC Firmware Upgrade in Rosemount Radar Master Select Enable Modbus Communication and click OKRosemount 5300/5400 Series Click Browse Checksum Rosemount 5300/5400 Series Specifications Rosemount 5300/5400 Series Emerson Process Management Rosemount Measurement