Page 13

Compur Statox 4120

3.2 Statox 4120 rack

Statox 4120 Rack must not be installed in hazardous areas. Observe local safety- and installation regulations.

Protect any cable from tensile strain. The five - and the nine - contact terminals are plugged in. They can be removed to ease wire connection.

pic.10: Backplane Statox 4120 Rack

Installation instructions:

The signal cable from sensor head to backplane must be shielded. The shield must make good contact to the ground contact on the backplane as well as to the sensor head metal shield.

Do not remove the conductive silicon bearing of the sensor head housing.

The sensor head housing must be installed isolated from ground to avoid ground loops. The entire system must only be grounded by the mains ground wire.

All control modules must be well connected and secured with the screws.

Connecting the mains cable initiates the system.

13

Image 13
Contents Compur Statox Compur Statox Trouble shooting Installation and electrical connectionsMaintenance and calibration Compur Statox 4120 operationStatox 4120 system Purpose of use and description Important noticeStatox 4120 sensor head Operation principle Statox 4120 rackAreas Connections ConstructionBargraph display Statox 4120 control moduleLED SR 7 „System ready LED SF 8 „System FailDiagnostic box Statox 4120 sensor head Installation and electrical connectionsMounting Connecting the signal cable Sensor head connection procedure Example of cable specificationsStatox 4120 rack Installation instructionsStatox 4120 control module Slide switch S1 Switch positions of the sensor head pcbToggle switch S3 Switch position for HCN Switch position for H2SSwitch position for COCl2 Switch position for CO Switch position for Cl2Switch position for HCl Switch position for ClO2 Detection mode Alarm thresholdsCompur Statox 4120 operation Start upSF flashing Trouble shootingManually triggered self test of the system System failureOperation and error codes of the diagnostic box Using the diagnostic boxDiagnostic box queries Button Display Diagnostic box error messagesCompur Statox Inspection Statox 4120 Sensor head Maintenance and calibrationGenerator cell replacement Filter cartridge replacementUsing span gas Sensor head calibrationThis is the last opportunity to abort the procedure ProcedureUse ex works calibration Maintenace request option Mounting the maintenance request pcb Error C3 Too low sensitivity during self testService mode control module Key Mode Relay PCS Relay WB Analog signal ReadingBridge Analog 20 mA 40-20mA Analog Terminal Solder straps Option analog output inhibitionSystem requirements Sensor head Technical data General Gas Measuring rangeControl module Diagnostic boxRack Art. Nr Accessories and spare partsArt.Nr Sensors & Generator Cells 558435