Installation instructions for the RFI-shielded Statox 4120 rack:

Use well shielded signal cable. The shield must make good contact with the RFI resistant cable glands. It must not be interrupted by connection boxes. If the signal cable is run through such, these must also be equipped with RFI resistant cable glands. They must be installed isolated from ground, and the shield must make good contact with the metal housing of the box.

Do not remove the conductive silicon bearing of the sensor head housing.

The sensor head housing must be installed isolated from ground to avoid ground loops. The entire system must only be grounded by the mains ground wire.

All control modules must be well connected and secured with the screws. Empty rack positions must be closed with blind panels.

3.3 Statox 4120 control module

Control module Circuit board includes power supply, fuses, relays, microprocessor control electronics, DIP switches and a terminal connecting with the backplane.

Front pcb with bar graph display. Foil keyboard.

pic.11: Control module Statox 4120

Each sensor head requires one control module. Before starting the system please check the DIP switch position. The following list comprises all possible DIP switch positions:

14

Image 14
Contents Compur Statox Compur Statox Maintenance and calibration Installation and electrical connectionsTrouble shooting Compur Statox 4120 operationImportant notice Statox 4120 system Purpose of use and descriptionStatox 4120 sensor head Areas Statox 4120 rackOperation principle Construction ConnectionsLED SR 7 „System ready Statox 4120 control moduleBargraph display LED SF 8 „System FailDiagnostic box Mounting Installation and electrical connectionsStatox 4120 sensor head Connecting the signal cable Example of cable specifications Sensor head connection procedureInstallation instructions Statox 4120 rackStatox 4120 control module Toggle switch S3 Switch positions of the sensor head pcbSlide switch S1 Switch position for COCl2 Switch position for H2SSwitch position for HCN Switch position for HCl Switch position for ClO2 Switch position for Cl2Switch position for CO Compur Statox 4120 operation Alarm thresholdsDetection mode Start upManually triggered self test of the system Trouble shootingSF flashing System failureDiagnostic box queries Button Display Using the diagnostic boxOperation and error codes of the diagnostic box Diagnostic box error messagesCompur Statox Maintenance and calibration Inspection Statox 4120 Sensor headUsing span gas Filter cartridge replacementGenerator cell replacement Sensor head calibrationUse ex works calibration ProcedureThis is the last opportunity to abort the procedure Maintenace request option Service mode control module Error C3 Too low sensitivity during self testMounting the maintenance request pcb Key Mode Relay PCS Relay WB Analog signal ReadingBridge Analog 20 mA 40-20mA Option analog output inhibition Analog Terminal Solder strapsSystem requirements Technical data General Gas Measuring range Sensor headRack Diagnostic boxControl module Art.Nr Accessories and spare partsArt. Nr Sensors & Generator Cells 558435