Compur Installation and electrical connections, Statox 4120 sensor head, Mounting

Page 10

Compur Statox 4120

3. Installation and electrical connections

3.1. Statox 4120 sensor head

3.1.1. Mounting

The sensor head should be installed as close as possible to potential leaks. If it is used as industrial hygiene device it should be located between a potential leak and personnel working in the area. Parameters such as:

Air flow (wind, ventilation, thermal conditions)

Access from top (removing the cover) and bottom (loosening the screws) Specifications of the gas to be detected (specific weight)

Protection from direct sunlight, splash water and dust must be taken care of.

Fasten the sensor head with three nylon screws on the mounting brackets using the rubber bearings as electrical isolation (these accessories are included).

pic.6: Mounting the sensor head

Mount the sensor head in horizontal position +/ 15%. Assure there is free gas access to the sensor.

10

Image 10
Contents Compur Statox Compur Statox Maintenance and calibration Installation and electrical connectionsTrouble shooting Compur Statox 4120 operationImportant notice Statox 4120 system Purpose of use and descriptionStatox 4120 sensor head Operation principle Statox 4120 rackAreas Construction ConnectionsLED SR 7 „System ready Statox 4120 control moduleBargraph display LED SF 8 „System FailDiagnostic box Statox 4120 sensor head Installation and electrical connectionsMounting Connecting the signal cable Example of cable specifications Sensor head connection procedureInstallation instructions Statox 4120 rackStatox 4120 control module Slide switch S1 Switch positions of the sensor head pcbToggle switch S3 Switch position for HCN Switch position for H2SSwitch position for COCl2 Switch position for CO Switch position for Cl2Switch position for HCl Switch position for ClO2 Compur Statox 4120 operation Alarm thresholdsDetection mode Start upManually triggered self test of the system Trouble shootingSF flashing System failureDiagnostic box queries Button Display Using the diagnostic boxOperation and error codes of the diagnostic box Diagnostic box error messagesCompur Statox Maintenance and calibration Inspection Statox 4120 Sensor headUsing span gas Filter cartridge replacementGenerator cell replacement Sensor head calibrationThis is the last opportunity to abort the procedure ProcedureUse ex works calibration Maintenace request option Service mode control module Error C3 Too low sensitivity during self testMounting the maintenance request pcb Key Mode Relay PCS Relay WB Analog signal ReadingBridge Analog 20 mA 40-20mA Option analog output inhibition Analog Terminal Solder strapsSystem requirements Technical data General Gas Measuring range Sensor headControl module Diagnostic boxRack Art. Nr Accessories and spare partsArt.Nr Sensors & Generator Cells 558435