Compur 4120 operation manual Diagnostic box

Page 9

Compur Statox 4120

LED A1 (9)

- On if pre - alarm threshold is exceeded

Display A2 (10)

- On if main alarm threshold is exceeded

Button A1 (4)

- Press and hold button A1 to display A1 threshold. Adjust with Pot. (12). A1 must be < A2.

Button A2 (3)

- Press and hold button A2 to display A2 threshold. Adjust with Pot. (11).

Button T (5) „Test“

- Initiates self test.

Button R (6) „Reset“

-Rests Alarms A1, A2 und SF provided the reason for the alarm has disappeared. (If SF has been triggered by a not passed self test, only a successful self test will reset it).

2.4Diagnostic box

pic.5: Diagnostic box

The diagnostic box must not be charged in classified areas or with other than charger Art.# 518850. It has the following purposes:

Calibration

Fault diagnosis

On site display

Function test

9

Image 9
Contents Compur Statox Compur Statox Trouble shooting Installation and electrical connectionsMaintenance and calibration Compur Statox 4120 operationStatox 4120 system Purpose of use and description Important noticeStatox 4120 sensor head Statox 4120 rack Operation principleAreas Connections ConstructionBargraph display Statox 4120 control moduleLED SR 7 „System ready LED SF 8 „System FailDiagnostic box Installation and electrical connections Statox 4120 sensor headMounting Connecting the signal cable Sensor head connection procedure Example of cable specificationsStatox 4120 rack Installation instructionsStatox 4120 control module Switch positions of the sensor head pcb Slide switch S1Toggle switch S3 Switch position for H2S Switch position for HCNSwitch position for COCl2 Switch position for Cl2 Switch position for COSwitch position for HCl Switch position for ClO2 Detection mode Alarm thresholdsCompur Statox 4120 operation Start upSF flashing Trouble shootingManually triggered self test of the system System failureOperation and error codes of the diagnostic box Using the diagnostic boxDiagnostic box queries Button Display Diagnostic box error messagesCompur Statox Inspection Statox 4120 Sensor head Maintenance and calibrationGenerator cell replacement Filter cartridge replacementUsing span gas Sensor head calibrationProcedure This is the last opportunity to abort the procedureUse ex works calibration Maintenace request option Mounting the maintenance request pcb Error C3 Too low sensitivity during self testService mode control module Key Mode Relay PCS Relay WB Analog signal ReadingBridge Analog 20 mA 40-20mA Analog Terminal Solder straps Option analog output inhibitionSystem requirements Sensor head Technical data General Gas Measuring rangeDiagnostic box Control moduleRack Accessories and spare parts Art. NrArt.Nr Sensors & Generator Cells 558435