Compur 4120 operation manual Maintenace request option

Page 25

Compur Statox 4120

7. The maintenace request option

Purpose:

This option can differentiate between fatal errors in the sensor head and maintenance requirements. It requires a Statox 4120 control module equipped with EPROM Index ≥ 03. It also sets the analog output to 4 mA during the self test, if required.

Operation modes:

The Statox 4120 can operate in 9 different modes. The relevant mode can be seen by the control module LED`s and relays.

Operation mode Statox

Analog output

SR-LED

SF-LED

SF-Relay

MR-

PCS-*

 

 

Control

Control

 

Relay

Relay

 

 

module

module

 

 

 

O Self test

0mA / 4mA / 0V

„on“

„on“

active

passive

active

 

 

 

 

 

 

 

O Diagnostic box connected:

0mA / 4mA / 0V

flashing

„off“

active

passive

active

 

 

 

 

 

 

 

O Alarm threshold adjustment:

0mA / 4mA / 0V

„on“

„off“

active

passive

active

 

 

 

 

 

 

 

O Start-mode

4mA / 0V

flashing

„off“

active

passive

passive

 

 

 

 

 

 

 

O Detection mode:

Analog signal

„on“

„off“

active

passive

passive

 

 

 

 

 

 

 

O Maintenance request:

 

 

 

 

 

 

B1 Battery Low

 

 

 

 

 

 

B2 Battery low under load

 

 

 

 

 

 

C1 Purge before test

 

 

 

 

 

 

C2 Purge between test peaks

 

 

 

 

 

 

C3 Sensitivity

Analog signal

flashing

„off“

active

active

passive

(programmable by S3)

 

 

 

 

 

 

C4 Purge

 

 

 

 

 

 

PU Pump current too high

 

 

 

 

 

 

T2 Temperature out of specs

 

 

 

 

 

 

 

 

 

 

 

 

 

O System failure:

 

 

 

 

 

 

A1 Amplifier

4mA / 0V

„off“

„on“

open

passive

passive

C3 Sensitivity

 

 

 

 

 

 

(programmable by S3)

 

 

 

 

 

 

 

 

 

 

 

 

 

O Data transmission error

4mA/0V

„off“

„on“

open

passive

passive

 

 

 

 

 

 

 

O Power failure

0mA/0V

„off“

„off“

open

passive

passive

 

 

 

 

 

 

 

*(PCS=Process control system)

25

Image 25
Contents Compur Statox Compur Statox Trouble shooting Installation and electrical connectionsMaintenance and calibration Compur Statox 4120 operationStatox 4120 system Purpose of use and description Important noticeStatox 4120 sensor head Operation principle Statox 4120 rackAreas Connections ConstructionBargraph display Statox 4120 control moduleLED SR 7 „System ready LED SF 8 „System FailDiagnostic box Statox 4120 sensor head Installation and electrical connectionsMounting Connecting the signal cable Sensor head connection procedure Example of cable specificationsStatox 4120 rack Installation instructionsStatox 4120 control module Slide switch S1 Switch positions of the sensor head pcbToggle switch S3 Switch position for HCN Switch position for H2SSwitch position for COCl2 Switch position for CO Switch position for Cl2Switch position for HCl Switch position for ClO2 Detection mode Alarm thresholdsCompur Statox 4120 operation Start upSF flashing Trouble shootingManually triggered self test of the system System failureOperation and error codes of the diagnostic box Using the diagnostic boxDiagnostic box queries Button Display Diagnostic box error messagesCompur Statox Inspection Statox 4120 Sensor head Maintenance and calibrationGenerator cell replacement Filter cartridge replacementUsing span gas Sensor head calibrationThis is the last opportunity to abort the procedure ProcedureUse ex works calibration Maintenace request option Mounting the maintenance request pcb Error C3 Too low sensitivity during self testService mode control module Key Mode Relay PCS Relay WB Analog signal ReadingBridge Analog 20 mA 40-20mA Analog Terminal Solder straps Option analog output inhibitionSystem requirements Sensor head Technical data General Gas Measuring rangeControl module Diagnostic boxRack Art. Nr Accessories and spare partsArt.Nr Sensors & Generator Cells 558435