The duct work must be smooth on the inside with no projections from sheet metal screws or other obstructions which would collect lint. Inspection doors must be installed at strategic points in the duct work for periodic lint removal.

Use smooth sweeping elbows instead of sharp 90º elbows. The radius of an elbow should be at least 1-1/2 times the duct diameter.

When the exhaust duct goes through a combustible wall on a roof, leave a 2-inch clearance space between the exhaust ducting and the wall or roof.

When adding ducts, the duct that leaves the building must be protected from the weather. For horizontal ducting use a 90º turned downward . For vertical duct work use a 180º turned downward. In either case, allow at least twice the diameter of the duct between the duct opening and nearest obstruction. (If the duct is rectangular, leave twice the smallest face dimension.)

IMPORTANT: DO NOT use screen or caps on the outside opening of the exhaust duct work. Screens will clog with lint and caps will restrict the exhaust airflow.

21

Image 25
Contents ADS-464 Installation/Operators Manual Retain This Manual In a Safe Place For Future Reference For Your Safety Pour Votre SécuritéFor Your Safety Page Table of Contents Service Parts Important Information SectionExplosion could Result Safety PrecautionsPage Specifications SPECIFICATIONS/DIMENSIONSDimensions Reassembly of Dryer Installation ProceduresPage Page Location Requirements Internal AIR, Electrical and Water Connections Page Page Page Page Page External Supply Connections Page MAN2371 Page Latest Edition Electrical RequirementsDedicated Sprinkler Service Electrical Service Specifications PER DryerPage Fresh AIR Supply Requirements 900 kg/hr Steam InformationShut Down Instructions Preparation for Operation PRE START-UPCleaning Routine MaintenanceSuggested Cleaning Schedule Monthly Tumbler Basket Support and Drive System Component System DescriptionsPage Page Main AIR Blower and Heat Reclaimer System Heat Reclaim ER Settings Compressed AIR System Page Internal and External Pilot Air Supply Safety Devices Door Open Service SERVICE/PARTS InformationParts Returning Warranty Cards Warranty InformationWarranty Returning Warranty PartsPage Standards TroubleshootingProbable Causes Power MalfunctionsNo Control Power Blue Light Off Machine Main Power Shuts Down Blue Indicator Off Sprinkler Circuit Components 3CRB Not UsedSprinkler Circuit Description Page ADS-464 on button does respond Possible Solutions Unless the Water Valve to the Sprinkler is Closed General DescriptionPage Page Introduction Tumbler Section Electrical MalfunctionsPage Rear Panel Control Problems Emergency Stop E-Stop Function Drum Forward and Reverse Function PLC OUT PIN 7 = Unload Door Open PLC OUT PIN 10 = Front UP DS1-B=LOAD Door Switch DS2-B=UNLOAD Door Switch Probable Solutions Page Base Section Electrical Malfunctions LS1-B=FRONT Down Switch LS2-B=REAR Down Switch Lint Screen Must be Cleaned Every Five 5 Drying Cycles Clogged Lint Screen or Lint BAG AIR Pressure Setting SEL a = Load SEL B = Unload Pendant Control MalfunctionsTumbler Forward Pendant --- PB1 Fuse 4 on Main Electrical Panel Faulty Switches Temperature Sensing Exhaust Dsfl Message a Probable Causes Temperature Sensing Component DescriptionsDefective Analog Input Module or Channel Motors Circuit Wiring to the Analog Input ModuleProbable Solutions ADS-464 Idling ADS-464 Running ADC 06/18/96-3 06/24/96-25 11/12/99-20