American Dryer Corp ADS-464 manual DS1-B=LOAD Door Switch DS2-B=UNLOAD Door Switch

Page 65

-Check wiring on the MAIN ENCLOSURE PANEL (Refer to the ADS-464 Main Panel Wiring Diagram)

-Check wiring associated with Solenoid Junction Box.

-See troubleshooting procedures associated with the Solenoid Junction Box.

3b) Input L.E.D. (light emitting doide) not illuminating correctly on the PLC (Programmable Logic Controller) indicates that the signal to the PLC input is missing or the PLC is defective.

-Check FUSE 2 on the main electrical panel

-Check wiring back to the tumbler junction box

-Check wiring back to the rear controls

-Check PLC

-Refer to blueprints

-Main electrical panel diagram

-Tumbler Jjunction box wiring PLC (Programmable Logic Controller) diagram

-Rear panel controls wiring diagram

-Re-test; verify that the signal is operational

3.0“DOOR Open” Problem

A “DOOR OPEN” message is generated by either the heater, load, or unload doors. The following information will address the load and unload doors signals, since they are associated with the tumbler junction box.

a)PROBABLE CAUSES;

1.WIRING BACK THE PLC (Programmable Logic Controller)

DS1-B=LOAD DOOR SWITCH DS2-B=UNLOAD DOOR SWITCH

b)POSSIBLE SOLUTIONS;

1.For quick check of LOAD and UNLOAD signals of the PLC perform the following:

-Remove factory air from the dryer

-With the Control Voltage “ON”, open the LOAD doors and locate the LOAD door switch actuator

-Cycle the switch by hand and have someone watch PLC input indicator #6. It should go “ON” when the switch is down.

61

Image 65
Contents ADS-464 Installation/Operators Manual Retain This Manual In a Safe Place For Future Reference For Your Safety Pour Votre SécuritéFor Your Safety Page Table of Contents Service Parts Important Information SectionExplosion could Result Safety PrecautionsPage Specifications SPECIFICATIONS/DIMENSIONSDimensions Reassembly of Dryer Installation ProceduresPage Page Location Requirements Internal AIR, Electrical and Water Connections Page Page Page Page Page External Supply Connections Page MAN2371 Page Latest Edition Electrical RequirementsDedicated Sprinkler Service Electrical Service Specifications PER DryerPage Fresh AIR Supply Requirements 900 kg/hr Steam InformationShut Down Instructions Preparation for Operation PRE START-UPSuggested Cleaning Schedule Routine MaintenanceCleaning Monthly Tumbler Basket Support and Drive System Component System DescriptionsPage Page Main AIR Blower and Heat Reclaimer System Heat Reclaim ER Settings Compressed AIR System Page Internal and External Pilot Air Supply Safety Devices Door Open Parts SERVICE/PARTS InformationService Returning Warranty Cards Warranty InformationWarranty Returning Warranty PartsPage Standards TroubleshootingProbable Causes Power MalfunctionsNo Control Power Blue Light Off Machine Main Power Shuts Down Blue Indicator Off Sprinkler Circuit Components 3CRB Not UsedSprinkler Circuit Description Page ADS-464 on button does respond Possible Solutions Unless the Water Valve to the Sprinkler is Closed General DescriptionPage Page Introduction Tumbler Section Electrical MalfunctionsPage Rear Panel Control Problems Emergency Stop E-Stop Function Drum Forward and Reverse Function PLC OUT PIN 7 = Unload Door Open PLC OUT PIN 10 = Front UP DS1-B=LOAD Door Switch DS2-B=UNLOAD Door Switch Probable Solutions Page Base Section Electrical Malfunctions LS1-B=FRONT Down Switch LS2-B=REAR Down Switch Lint Screen Must be Cleaned Every Five 5 Drying Cycles Clogged Lint Screen or Lint BAG AIR Pressure Setting SEL a = Load SEL B = Unload Pendant Control MalfunctionsTumbler Forward Pendant --- PB1 Fuse 4 on Main Electrical Panel Faulty Switches Temperature Sensing Exhaust Dsfl Message a Probable Causes Temperature Sensing Component DescriptionsDefective Analog Input Module or Channel Motors Circuit Wiring to the Analog Input ModuleProbable Solutions ADS-464 Idling ADS-464 Running ADC 06/18/96-3 06/24/96-25 11/12/99-20