American Dryer Corp ADS-464 manual Clogged Lint Screen or Lint BAG AIR Pressure Setting

Page 71

2.WIRING BACK TO THE PLC (Programmable Logic Controller), 0, 8

a)PROBABLE CAUSES;

1.CLOGGED LINT SCREEN OR LINT BAG

2.AIR PRESSURE SETTING

3.AIR PRESSURE SWITCH - PS3 OR WIRING BACK TO THE PLC (Programmable Logic Controller)

b)POSSIBLE SOLUTIONS;

1.Perform preventive maintenance and screen cleaning procedures.

2.Set correct pressure settings.

3.For a quick check of the AIR PRESSURE SWITCH WIRING, perform the following:

-Run a drying cycle

-Does the pressure switch’s indicator come “ON”?

-If “YES,” switch and its adjustment

-If “NO,” check switch and its adjustment

-Verify that PLC (Programmable Logic Controller) input L.E.D. #5 comes “ON”

-Does L.E.D. #5 come “ON” when the switch is active?

-If “YES,” wiring is OK

-If “NO,” check:

-Switch, its setting and wiring

-Check wiring back to the base electrical junction box

-Check PLC (Programmable Logic Controller)

-Refer to blueprints: Main Electrical Panel Diagram, Base Junction Box Wiring Diagram

-Re-test; verify that the signal is operational

67

Image 71
Contents ADS-464 Installation/Operators Manual Retain This Manual In a Safe Place For Future Reference For Your Safety Pour Votre SécuritéFor Your Safety Page Table of Contents Service Parts Important Information SectionExplosion could Result Safety PrecautionsPage Specifications SPECIFICATIONS/DIMENSIONSDimensions Reassembly of Dryer Installation ProceduresPage Page Location Requirements Internal AIR, Electrical and Water Connections Page Page Page Page Page External Supply Connections Page MAN2371 Page Latest Edition Electrical RequirementsDedicated Sprinkler Service Electrical Service Specifications PER DryerPage Fresh AIR Supply Requirements 900 kg/hr Steam InformationShut Down Instructions Preparation for Operation PRE START-UPSuggested Cleaning Schedule Routine MaintenanceCleaning Monthly Tumbler Basket Support and Drive System Component System DescriptionsPage Page Main AIR Blower and Heat Reclaimer System Heat Reclaim ER Settings Compressed AIR System Page Internal and External Pilot Air Supply Safety Devices Door Open Parts SERVICE/PARTS InformationService Returning Warranty Parts Warranty InformationReturning Warranty Cards WarrantyPage Standards TroubleshootingProbable Causes Power MalfunctionsNo Control Power Blue Light Off Machine Main Power Shuts Down Blue Indicator Off Sprinkler Circuit Components 3CRB Not UsedSprinkler Circuit Description Page ADS-464 on button does respond Possible Solutions Unless the Water Valve to the Sprinkler is Closed General DescriptionPage Page Introduction Tumbler Section Electrical MalfunctionsPage Rear Panel Control Problems Emergency Stop E-Stop Function Drum Forward and Reverse Function PLC OUT PIN 7 = Unload Door Open PLC OUT PIN 10 = Front UP DS1-B=LOAD Door Switch DS2-B=UNLOAD Door Switch Probable Solutions Page Base Section Electrical Malfunctions LS1-B=FRONT Down Switch LS2-B=REAR Down Switch Lint Screen Must be Cleaned Every Five 5 Drying Cycles Clogged Lint Screen or Lint BAG AIR Pressure Setting SEL a = Load SEL B = Unload Pendant Control MalfunctionsTumbler Forward Pendant --- PB1 Fuse 4 on Main Electrical Panel Faulty Switches Temperature Sensing Exhaust Dsfl Message a Probable Causes Temperature Sensing Component DescriptionsDefective Analog Input Module or Channel Motors Circuit Wiring to the Analog Input ModuleProbable Solutions ADS-464 Idling ADS-464 Running ADC 06/18/96-3 06/24/96-25 11/12/99-20