G. STEAM INFORMATION

It is your responsibility to have ALL plumbing connections made by a qualified professional to assure that the steam plumbing installation is adequate and conforms with local and state regulations or codes.

IMPORTANT: Failure to comply with the requirements stipulated in this manual can result in component failure which will VOID THE WARRANTY.

NOTE: The ADS-464 is manufactured with a pneumatic (piston) damper system which requires an external supply of air (80 psi ± 10 psi).

1.Steam Coil PH Level

The normal PH level for copper type steam coils must be maintained between a value of 8.5 to 9.5. For steel type steam coils the PH level must be maintained between a value of 9.5 to 10.5. These limits are set to limit the acid attack of the steam coils.

IMPORTANT: Coil failure due to improper PH level will VOID THE WARRANTY.

2.Steam Requirements

Inlet ----- 2” supply line connection Return -- 1-1/4” return line connection

OPERATING STEAM PRESSURE

MAXIMUM

150 psig

 

10.5 kg/sq cm.

 

 

 

 

MINIMUM

100 psig

 

7.03 kg/sq cm.

 

 

 

 

HEAT INPUT (NORMAL LOAD)

 

60 bph

 

 

 

 

CONSU MPTION (APPROXIMATE)

1,980 lbs/hr

 

900 kg/hr

 

 

 

 

Shaded areas are in meric equivalents

3.Installation Instructions

To ensure an adequate supply of steam is provided, be sure that the steam lines and return lines are sized and laid out as stipulated in this manual. Inadequate steam lines and return lines or improper steam plumbing will result in poor performance and can cause component failure. Clean dry steam must be provided to the dryer.

IMPORTANT: Steam coil failure due to hammer by wet steam will VOID THE WARRANTY.

a.The presence of the condensate in the steam supply will cause water hammer and subsequent heat exchanger (steam coil) failure. The steam supply connection into the main supply line must be made with a minimum 10-inch riser. This will prevent any condensate from draining toward the dryer.

b.The steam supply piping to the dryer must include a 12-inch rise along with a drip trap and check valve. This will prevent and condensate from entering the steam coil.

26

Image 30
Contents ADS-464 Installation/Operators Manual For Your Safety Pour Votre Sécurité Retain This Manual In a Safe Place For Future ReferenceFor Your Safety Page Table of Contents Service Parts Section Important InformationSafety Precautions Explosion could ResultPage SPECIFICATIONS/DIMENSIONS SpecificationsDimensions Installation Procedures Reassembly of DryerPage Page Location Requirements Internal AIR, Electrical and Water Connections Page Page Page Page Page External Supply Connections Page MAN2371 Page Electrical Requirements Latest Edition Electrical Service Specifications PER Dryer Dedicated Sprinkler ServicePage Fresh AIR Supply Requirements Steam Information 900 kg/hrShut Down Instructions PRE START-UP Preparation for OperationRoutine Maintenance CleaningSuggested Cleaning Schedule Monthly Component System Descriptions Tumbler Basket Support and Drive SystemPage Page Main AIR Blower and Heat Reclaimer System Heat Reclaim ER Settings Compressed AIR System Page Internal and External Pilot Air Supply Safety Devices Door Open SERVICE/PARTS Information ServiceParts Warranty Warranty InformationReturning Warranty Cards Returning Warranty PartsPage Troubleshooting StandardsPower Malfunctions Probable CausesNo Control Power Blue Light Off Machine Main Power Shuts Down Blue Indicator Off 3CRB Not Used Sprinkler Circuit ComponentsSprinkler Circuit Description Page ADS-464 on button does respond Possible Solutions General Description Unless the Water Valve to the Sprinkler is ClosedPage Page Tumbler Section Electrical Malfunctions IntroductionPage Rear Panel Control Problems Emergency Stop E-Stop Function Drum Forward and Reverse Function PLC OUT PIN 7 = Unload Door Open PLC OUT PIN 10 = Front UP DS1-B=LOAD Door Switch DS2-B=UNLOAD Door Switch Probable Solutions Page Base Section Electrical Malfunctions LS1-B=FRONT Down Switch LS2-B=REAR Down Switch Lint Screen Must be Cleaned Every Five 5 Drying Cycles Clogged Lint Screen or Lint BAG AIR Pressure Setting Pendant Control Malfunctions SEL a = Load SEL B = UnloadTumbler Forward Pendant --- PB1 Fuse 4 on Main Electrical Panel Faulty Switches Temperature Sensing Temperature Sensing Component Descriptions Exhaust Dsfl Message a Probable CausesDefective Analog Input Module or Channel Circuit Wiring to the Analog Input Module MotorsProbable Solutions ADS-464 Idling ADS-464 Running ADC 06/18/96-3 06/24/96-25 11/12/99-20