-Open the UNLOAD doors and locate the UNLOAD doors switch actuator.

-Cycle the switch by hand and have someone watch PLC (Programmable Logic Controller) input indicator #7. It should go “ON” when the switch is down. Do the associated L.E.D.’s (light emitting diode) come “ON” when switch is down?

-If “YES,” wiring is OK

-Check switch placement and door actuation

-If “NO,” check associated:

-Switch and wiring

-Check wiring back to the tumbler junction box

-Check wiring back to the rear controls

-Check PLC (Programmable Logic Controller)

-Refer to blueprints: Main Electrical Panel Diagram

-Tumbler junction box diagram

-Rare panel controls wiring diagram

-Re-test; verify that the signal is operational

4.0“DRUM FAULT MESSAGE” Malfuntion a) PROBABLE CAUSES;

1.Stop Motion Detector module or sensor

2.Wiring back to main electrical enclosure

b)PROBABLE SOLUTIONS;

1.Open the Main Electrical Enclosure locate input #0, 10 on the PLC (Programmable Logic Controller). With control voltage “ON” (Green Push-Button), use the pendant to rotate the tumbler. Notice a L.E.D. (light emitting diode) on as the tumbler is rotating.

- If the L.E.D. if off, refer to section 1a

1a) If the LED is off:

-Check Fuse 2; replace if necessary

-Rotate the tumbler using the pendant control, and adjust the stop

-Does the module’s L.E.D. respond?

62

Image 66
Contents ADS-464 Installation/Operators Manual For Your Safety Pour Votre Sécurité Retain This Manual In a Safe Place For Future ReferenceFor Your Safety Page Table of Contents Service Parts Section Important InformationSafety Precautions Explosion could ResultPage SPECIFICATIONS/DIMENSIONS SpecificationsDimensions Installation Procedures Reassembly of DryerPage Page Location Requirements Internal AIR, Electrical and Water Connections Page Page Page Page Page External Supply Connections Page MAN2371 Page Electrical Requirements Latest EditionElectrical Service Specifications PER Dryer Dedicated Sprinkler ServicePage Fresh AIR Supply Requirements Steam Information 900 kg/hrShut Down Instructions PRE START-UP Preparation for OperationRoutine Maintenance CleaningSuggested Cleaning Schedule Monthly Component System Descriptions Tumbler Basket Support and Drive SystemPage Page Main AIR Blower and Heat Reclaimer System Heat Reclaim ER Settings Compressed AIR System Page Internal and External Pilot Air Supply Safety Devices Door Open SERVICE/PARTS Information ServiceParts Warranty Warranty InformationReturning Warranty Cards Returning Warranty PartsPage Troubleshooting StandardsPower Malfunctions Probable CausesNo Control Power Blue Light Off Machine Main Power Shuts Down Blue Indicator Off 3CRB Not Used Sprinkler Circuit ComponentsSprinkler Circuit Description Page ADS-464 on button does respond Possible Solutions General Description Unless the Water Valve to the Sprinkler is ClosedPage Page Tumbler Section Electrical Malfunctions IntroductionPage Rear Panel Control Problems Emergency Stop E-Stop Function Drum Forward and Reverse Function PLC OUT PIN 7 = Unload Door Open PLC OUT PIN 10 = Front UP DS1-B=LOAD Door Switch DS2-B=UNLOAD Door Switch Probable Solutions Page Base Section Electrical Malfunctions LS1-B=FRONT Down Switch LS2-B=REAR Down Switch Lint Screen Must be Cleaned Every Five 5 Drying Cycles Clogged Lint Screen or Lint BAG AIR Pressure Setting Pendant Control Malfunctions SEL a = Load SEL B = UnloadTumbler Forward Pendant --- PB1 Fuse 4 on Main Electrical Panel Faulty Switches Temperature Sensing Temperature Sensing Component Descriptions Exhaust Dsfl Message a Probable CausesDefective Analog Input Module or Channel Circuit Wiring to the Analog Input Module MotorsProbable Solutions ADS-464 Idling ADS-464 Running ADC 06/18/96-3 06/24/96-25 11/12/99-20