-If “NO,” check associated:

-Switch and Wiring

-Check wiring back to the base electrical junction box

-Check PLC (Programmable Logic Controller)

-Refer toblueprints: Main Electrical Panel Diagram, Base Electrical Junction Box Wiring Diagram

-Re-test; verify that the signal is operational

1b) Place the ADS-464 in the UNLOAD position; TILTED FORWARD

-Actuate the Rear Down Switch by hand

-Have someone verify that PLC (Programmable Logic Controller) input L.E.D. #12 lights when the switch actuator is down, and is OFF when the actuator is up

-Does L.E.D. #12 come “ON” when the switch is down?

-If “YES,” wiring is OK

-Check switch, actuator placement and tilt actuation

NOTE: If actuator is at 90ºor greater angle with the base, the actuator will be damaged if machine is lowered.

-If “NO,” check assoicated:

-Switch and wiring

-Check wiring back to the base electrical junction box

-Check PLC (Programmable Logic Controller)

-Refer to blueprints: Main Elecrtical Panel Diagram, Base Electrical Junction Box Wiring Diagram

-Re-test; verify that the signal is operational

3.0Lint Screen Mechanism Problem “SCREEN FAULT”

A “SCREEN FAULT” message is generated by the incorrect state of the lint screen mehanism sensor switch. The following information will address the correct signal, since it is associated with the Base Electrical Junction Box.

a)PROBABLE CAUSES

1.THE LINT SCREEN MUST BE CLEANED EVERY FIVE (5) DRYING CYCLES

66

Image 70
Contents ADS-464 Installation/Operators Manual For Your Safety Pour Votre Sécurité Retain This Manual In a Safe Place For Future ReferenceFor Your Safety Page Table of Contents Service Parts Section Important InformationSafety Precautions Explosion could ResultPage SPECIFICATIONS/DIMENSIONS SpecificationsDimensions Installation Procedures Reassembly of DryerPage Page Location Requirements Internal AIR, Electrical and Water Connections Page Page Page Page Page External Supply Connections Page MAN2371 Page Electrical Requirements Latest EditionElectrical Service Specifications PER Dryer Dedicated Sprinkler ServicePage Fresh AIR Supply Requirements Steam Information 900 kg/hrShut Down Instructions PRE START-UP Preparation for OperationCleaning Routine MaintenanceSuggested Cleaning Schedule Monthly Component System Descriptions Tumbler Basket Support and Drive SystemPage Page Main AIR Blower and Heat Reclaimer System Heat Reclaim ER Settings Compressed AIR System Page Internal and External Pilot Air Supply Safety Devices Door Open Service SERVICE/PARTS InformationParts Warranty Warranty InformationReturning Warranty Cards Returning Warranty PartsPage Troubleshooting StandardsPower Malfunctions Probable CausesNo Control Power Blue Light Off Machine Main Power Shuts Down Blue Indicator Off 3CRB Not Used Sprinkler Circuit ComponentsSprinkler Circuit Description Page ADS-464 on button does respond Possible Solutions General Description Unless the Water Valve to the Sprinkler is ClosedPage Page Tumbler Section Electrical Malfunctions IntroductionPage Rear Panel Control Problems Emergency Stop E-Stop Function Drum Forward and Reverse Function PLC OUT PIN 7 = Unload Door Open PLC OUT PIN 10 = Front UP DS1-B=LOAD Door Switch DS2-B=UNLOAD Door Switch Probable Solutions Page Base Section Electrical Malfunctions LS1-B=FRONT Down Switch LS2-B=REAR Down Switch Lint Screen Must be Cleaned Every Five 5 Drying Cycles Clogged Lint Screen or Lint BAG AIR Pressure Setting Pendant Control Malfunctions SEL a = Load SEL B = UnloadTumbler Forward Pendant --- PB1 Fuse 4 on Main Electrical Panel Faulty Switches Temperature Sensing Temperature Sensing Component Descriptions Exhaust Dsfl Message a Probable CausesDefective Analog Input Module or Channel Circuit Wiring to the Analog Input Module MotorsProbable Solutions ADS-464 Idling ADS-464 Running ADC 06/18/96-3 06/24/96-25 11/12/99-20