4.Internal and External Pilot Air Supply

On two-way tilt dryers, a pneumatic safety circuit is incorporated to prevent both front and rear tilting pistons from extending their rods at the same time. When 120 volts is supplied to the “S5” side of the front tilting piston solenoid valve coil, the round internal spool in the core of the solenoid will move, allowing 80 PSI air to flow into the bottom ports of the front tilting pistons, while the top ports of these pistons are bled to the atmosphere. In addition to this 120 volt electrical signal, the spool also requires a 30 PSI supply of compressed air to change its position. This pilot air can either be supplied internally, tapped off the 80 PSI air supply connected to port no. 1 through holes in the body of the solenoid valve or it can be supplied externally through the 1/8-inch F.P.T. connection located on either end of the solenoid valve. If no pilot air is supplied to the solenoid valve. Then the spool cannot move, even with voltage supplied to the solenoid valve coil.

This can be used to prevent both sets of tilting pistons from extending their rods at the same time. When the front tilting piston rods are extended, 80 PSI air is connected to the bottom piston ports, while the top piston ports are bled to the atmosphere. So, by tapping the external pilot air supply to the rear tilting rods are extended, then there is no pilot pressure available to the rear tilting piston solenoid valve so that its spool cannot move and the rear tilting piston rods cannot extend if a 120 volt signal is sent to its “12” side solenoid valve coil.

The external pilot air supply to the front tilting piston is tapped off the rear tilting piston top port air line so that whenever the rear piston rods are extended, there is no pilot air supplied to the front tilting piston solenoid valve and the front tilting piston rods cannot extend. On the solenoid valve supplied on the dryer, the “12” side valve is externally piloted, while “14” side valve is internally piloted.

A valve can easily be checked for internal or external piloting by removing the two (2) screws which hold the solenoid operator onto the valve. For an internal pilot air to be supplied to the valve spool. For an external pilot, the solid sealing disc must be positioned on top of the internal port.

5.Loading Doors and Heat Reclaimer, Cool Down and Intake Air Damper

These solenoid valves are located in the 6-station manifold block on the pneumatic control panel. Each door piston is controlled by two (2) 2-port/2-position solenoid valve. The heat reclaimer is controlled by one (1) 2-port/2-position solenoid valves.

The three (3) pistons that control the heat reclaimer damper, cool down damper, and intake air damper are controlled by a single 3-way double acting solenoid valve.

To open the front loading door, a 120 volt signal is applied to “S1,” the coil of the valve that supplies air to the load door or the heat reclaimer’s bottom port. The valve will open, and 80 PSI of air is supplied to the bottom port of the piston. The piston rod will extend, and the door will open. No voltage is applied to “S2,” the coil of the valve that controls the air supply to the door pistons top port so that this line is bled to the atmosphere.

To close the front loading door or heat reclaimer damper, the voltage signals are reversed, and the loading door will close.

38

Image 42
Contents ADS-464 Installation/Operators Manual For Your Safety Pour Votre Sécurité Retain This Manual In a Safe Place For Future ReferenceFor Your Safety Page Table of Contents Service Parts Section Important InformationSafety Precautions Explosion could ResultPage SPECIFICATIONS/DIMENSIONS SpecificationsDimensions Installation Procedures Reassembly of DryerPage Page Location Requirements Internal AIR, Electrical and Water Connections Page Page Page Page Page External Supply Connections Page MAN2371 Page Electrical Requirements Latest EditionElectrical Service Specifications PER Dryer Dedicated Sprinkler ServicePage Fresh AIR Supply Requirements Steam Information 900 kg/hrShut Down Instructions PRE START-UP Preparation for OperationRoutine Maintenance CleaningSuggested Cleaning Schedule Monthly Component System Descriptions Tumbler Basket Support and Drive SystemPage Page Main AIR Blower and Heat Reclaimer System Heat Reclaim ER Settings Compressed AIR System Page Internal and External Pilot Air Supply Safety Devices Door Open SERVICE/PARTS Information ServiceParts Warranty Warranty InformationReturning Warranty Cards Returning Warranty PartsPage Troubleshooting StandardsPower Malfunctions Probable CausesNo Control Power Blue Light Off Machine Main Power Shuts Down Blue Indicator Off 3CRB Not Used Sprinkler Circuit ComponentsSprinkler Circuit Description Page ADS-464 on button does respond Possible Solutions General Description Unless the Water Valve to the Sprinkler is ClosedPage Page Tumbler Section Electrical Malfunctions IntroductionPage Rear Panel Control Problems Emergency Stop E-Stop Function Drum Forward and Reverse Function PLC OUT PIN 7 = Unload Door Open PLC OUT PIN 10 = Front UP DS1-B=LOAD Door Switch DS2-B=UNLOAD Door Switch Probable Solutions Page Base Section Electrical Malfunctions LS1-B=FRONT Down Switch LS2-B=REAR Down Switch Lint Screen Must be Cleaned Every Five 5 Drying Cycles Clogged Lint Screen or Lint BAG AIR Pressure Setting Pendant Control Malfunctions SEL a = Load SEL B = UnloadTumbler Forward Pendant --- PB1 Fuse 4 on Main Electrical Panel Faulty Switches Temperature Sensing Temperature Sensing Component Descriptions Exhaust Dsfl Message a Probable CausesDefective Analog Input Module or Channel Circuit Wiring to the Analog Input Module MotorsProbable Solutions ADS-464 Idling ADS-464 Running ADC 06/18/96-3 06/24/96-25 11/12/99-20