3.Machine Main Power Shuts Down (“BLUE” Indicator Off)

a.PROBABLE CAUSES;

1a) Sprinkler activated.

2a) OL12 (overload #12) tripped.

3a) “UNDER VOLTAGE FEATURE” of main disconnect has tripped.

4a) Sprinkler circuit defective.

b.POSSIBLE SOLUTIONS;

1b) Check if the sprinkler is activated, is “SPRINKLER RESET” button lit? Is the sprinkler alarm horn “ON”? Does the sprinkler water valve have its “ON” indicator extended?

If yes, it indicates that the sprinkler circuit has shutdown the Main Disconnect, press the lit “SPRINKLER RESET” button, does it reset?

If “NO,” go to paragraph 2b below

2b) Verify that OL12 (overload #12) has not tripped

If “YES,” check circuit, reset OL12, and test

If “NO,” go to paragraph 3b below

3b) The main disconnect has an “UNDER VOLTAGE DROP OUT FEATURE.” This feature requires that 110 VAC be present to engage the disconnect switch. If 110 VAC is removed from Pin #51 and Pin #52 on the switch, the disconnect will drop out automatically. Verify that 110 volts AC is supplied to the disconnect and that wires are secure.

If 110 VAC is present, the disconnect may be defective

If 110 VAC is not present go to the beginning of section 3 at the top of the page

4.Sprinkler circuit may be defective.

47

Image 51
Contents ADS-464 Installation/Operators Manual Retain This Manual In a Safe Place For Future Reference For Your Safety Pour Votre SécuritéFor Your Safety Page Table of Contents Service Parts Important Information SectionExplosion could Result Safety PrecautionsPage Specifications SPECIFICATIONS/DIMENSIONSDimensions Reassembly of Dryer Installation ProceduresPage Page Location Requirements Internal AIR, Electrical and Water Connections Page Page Page Page Page External Supply Connections Page MAN2371 Page Latest Edition Electrical RequirementsDedicated Sprinkler Service Electrical Service Specifications PER DryerPage Fresh AIR Supply Requirements 900 kg/hr Steam InformationShut Down Instructions Preparation for Operation PRE START-UPRoutine Maintenance CleaningSuggested Cleaning Schedule Monthly Tumbler Basket Support and Drive System Component System DescriptionsPage Page Main AIR Blower and Heat Reclaimer System Heat Reclaim ER Settings Compressed AIR System Page Internal and External Pilot Air Supply Safety Devices Door Open SERVICE/PARTS Information ServiceParts Returning Warranty Parts Warranty InformationReturning Warranty Cards WarrantyPage Standards TroubleshootingProbable Causes Power MalfunctionsNo Control Power Blue Light Off Machine Main Power Shuts Down Blue Indicator Off Sprinkler Circuit Components 3CRB Not UsedSprinkler Circuit Description Page ADS-464 on button does respond Possible Solutions Unless the Water Valve to the Sprinkler is Closed General DescriptionPage Page Introduction Tumbler Section Electrical MalfunctionsPage Rear Panel Control Problems Emergency Stop E-Stop Function Drum Forward and Reverse Function PLC OUT PIN 7 = Unload Door Open PLC OUT PIN 10 = Front UP DS1-B=LOAD Door Switch DS2-B=UNLOAD Door Switch Probable Solutions Page Base Section Electrical Malfunctions LS1-B=FRONT Down Switch LS2-B=REAR Down Switch Lint Screen Must be Cleaned Every Five 5 Drying Cycles Clogged Lint Screen or Lint BAG AIR Pressure Setting SEL a = Load SEL B = Unload Pendant Control MalfunctionsTumbler Forward Pendant --- PB1 Fuse 4 on Main Electrical Panel Faulty Switches Temperature Sensing Exhaust Dsfl Message a Probable Causes Temperature Sensing Component DescriptionsDefective Analog Input Module or Channel Motors Circuit Wiring to the Analog Input ModuleProbable Solutions ADS-464 Idling ADS-464 Running ADC 06/18/96-3 06/24/96-25 11/12/99-20