American Dryer Corp ADS-464 manual Fuse 4 on Main Electrical Panel Faulty Switches

Page 74

Release the REVERSE Push-button

Does PLC (Programmable Logic Controller) input L.E.D. #18 go “OFF”?

If the answers to these questions are “YES,” wiring to the PLC is correct.

If any answer to these questions is “NO,” refer to Probable Causes below

Tumbler Forward Switch --- PB1

For quick check of the wiring of PB1 to the PLC (Programmable Logic Controller) perform the following test with the control voltage “ON” (“GREEN” button).

Press the FORWARD Push-button.

Does PLC (Programmable Logic Controller) input L.E.D. #17 light?

Release the REVERSE Push-button.

Does PLC (Programmable Logic Controller) input L.E.D. #17 go “OFF”?

If the answer to these questions are “YES,” wiring to the PLC (Programmable Logic Controller) is correct.

If the answer to these questions are “NO,” refer to Probable Causes below

a)PROBABLE CAUSES;

1.FUSE 4 ON MAIN ELECTRICAL PANEL

2.FAULTY SWITCHES

3.WIRING BACK TO PLC (Programmable Logic Controller)

b)POSSIBLE SOLUTIONS;

1.Check fuse blown indicator on fuse 4; replace fuse, if necessary and re-test.

2.Check switches using an OHM meter; replace if necessary, and re-test.

3.Refer to ADS-464 Pendant associated wiring diagrams for detailed assemblyand wiring information. Check ALL circiuts back to PLC (Programmable Logic Controller).

ADS-464 PENDANT ASSEMBLY DIAGRAM

ADS-464 ANNUNCIATOR, PENDANT, and UPPER RTD’S (Resistive Temperature Device)

WIRING DIAGRAM

EMERGENCY STOP (E-Stop) SWITCH --- PB6

If the “Emergency Stop” switch (pendant) does not respond:

70

Image 74
Contents ADS-464 Installation/Operators Manual For Your Safety Pour Votre Sécurité Retain This Manual In a Safe Place For Future ReferenceFor Your Safety Page Table of Contents Service Parts Section Important InformationSafety Precautions Explosion could ResultPage SPECIFICATIONS/DIMENSIONS SpecificationsDimensions Installation Procedures Reassembly of DryerPage Page Location Requirements Internal AIR, Electrical and Water Connections Page Page Page Page Page External Supply Connections Page MAN2371 Page Electrical Requirements Latest EditionElectrical Service Specifications PER Dryer Dedicated Sprinkler ServicePage Fresh AIR Supply Requirements Steam Information 900 kg/hrShut Down Instructions PRE START-UP Preparation for OperationSuggested Cleaning Schedule Routine MaintenanceCleaning Monthly Component System Descriptions Tumbler Basket Support and Drive SystemPage Page Main AIR Blower and Heat Reclaimer System Heat Reclaim ER Settings Compressed AIR System Page Internal and External Pilot Air Supply Safety Devices Door Open Parts SERVICE/PARTS InformationService Warranty Warranty InformationReturning Warranty Cards Returning Warranty PartsPage Troubleshooting StandardsPower Malfunctions Probable CausesNo Control Power Blue Light Off Machine Main Power Shuts Down Blue Indicator Off 3CRB Not Used Sprinkler Circuit ComponentsSprinkler Circuit Description Page ADS-464 on button does respond Possible Solutions General Description Unless the Water Valve to the Sprinkler is ClosedPage Page Tumbler Section Electrical Malfunctions IntroductionPage Rear Panel Control Problems Emergency Stop E-Stop Function Drum Forward and Reverse Function PLC OUT PIN 7 = Unload Door Open PLC OUT PIN 10 = Front UP DS1-B=LOAD Door Switch DS2-B=UNLOAD Door Switch Probable Solutions Page Base Section Electrical Malfunctions LS1-B=FRONT Down Switch LS2-B=REAR Down Switch Lint Screen Must be Cleaned Every Five 5 Drying Cycles Clogged Lint Screen or Lint BAG AIR Pressure Setting Pendant Control Malfunctions SEL a = Load SEL B = UnloadTumbler Forward Pendant --- PB1 Fuse 4 on Main Electrical Panel Faulty Switches Temperature Sensing Temperature Sensing Component Descriptions Exhaust Dsfl Message a Probable CausesDefective Analog Input Module or Channel Circuit Wiring to the Analog Input Module MotorsProbable Solutions ADS-464 Idling ADS-464 Running ADC 06/18/96-3 06/24/96-25 11/12/99-20