American Dryer Corp ADS-464 manual Heat Reclaim ER Settings

Page 39

The dryer is equipped with a pneumatically operated heat reclaimer damper, which when opened, will recirculate approximately fifteen percent (15%) of the dryer’s exhaust air.

The heat reclaimer damper is closed until ignition of flame has been established. Then, the damper piston is actuated, opening the dampers recirculating fifteen percent (15%) of the exhaust air back over the gas burner and into the tumbler (basket). The damper remains open for the rest of the drying cycle. On cool down, the damper closes, exhausting ALL of the 13,000 cfm which ensures a fast cool down of the load.

HEAT RECLAIMER ADJUSTMENT

1. REMOVE ELECTRICITY FROM THE UNIT.

2. LOOSEN HEAT RECLAIMER ADJUSTMENT NUTS ON ALL FOUR(4) CORNERS OF THE HEAT RECLAIMER PISTON.

3. ADJUST THE BOTTOM HEAT RECLAIMER NUTS

DOWN TO THEIR DESIRED POSITION WHICH

WILL GIVE THE PROPER PISTON STROKE.

EXAMPLE: IF THE DESIRED PISTON STROKE IS

TWO (2) INCHES (5.1 CM), THAN THE

DISTANCE "X" IN THE ILLUSTRATION

MUST BE TWO (2) INCHES (5.1 CM).

4. TIGHTEN TOP HEAT RECLAIMER NUTS DOWN ONTO THE BOTTOM HEAT RECLAIMER NUTS.

HEAT RECLAIM ER SETTINGS

Z = 1-5/8"

 

 

 

Y+Z=X

Y

%HR

Inches Reclaimed

1-1/8"

1/2"

7.46

1-1/4"

2-5/8"

1"

15.67

2-5/8"

3-1/8"

1-1/2"

25.37

4-1/4"

3-5/8"

2"

34.32

5-3/4"

4-1/8"

2-1/2"

43.28

7-1/4"

4-5/8"

3"

50.74

8-1/2"

5-1/8"

3-1/2"

58.95

9-7/8"

FULL OPEN 16-3/4"

35

Image 39
Contents ADS-464 Installation/Operators Manual Retain This Manual In a Safe Place For Future Reference For Your Safety Pour Votre SécuritéFor Your Safety Page Table of Contents Service Parts Important Information SectionExplosion could Result Safety PrecautionsPage Specifications SPECIFICATIONS/DIMENSIONSDimensions Reassembly of Dryer Installation ProceduresPage Page Location Requirements Internal AIR, Electrical and Water Connections Page Page Page Page Page External Supply Connections Page MAN2371 Page Latest Edition Electrical RequirementsDedicated Sprinkler Service Electrical Service Specifications PER DryerPage Fresh AIR Supply Requirements 900 kg/hr Steam InformationShut Down Instructions Preparation for Operation PRE START-UPRoutine Maintenance CleaningSuggested Cleaning Schedule Monthly Tumbler Basket Support and Drive System Component System DescriptionsPage Page Main AIR Blower and Heat Reclaimer System Heat Reclaim ER Settings Compressed AIR System Page Internal and External Pilot Air Supply Safety Devices Door Open SERVICE/PARTS Information ServiceParts Returning Warranty Parts Warranty InformationReturning Warranty Cards WarrantyPage Standards TroubleshootingProbable Causes Power MalfunctionsNo Control Power Blue Light Off Machine Main Power Shuts Down Blue Indicator Off Sprinkler Circuit Components 3CRB Not UsedSprinkler Circuit Description Page ADS-464 on button does respond Possible Solutions Unless the Water Valve to the Sprinkler is Closed General DescriptionPage Page Introduction Tumbler Section Electrical MalfunctionsPage Rear Panel Control Problems Emergency Stop E-Stop Function Drum Forward and Reverse Function PLC OUT PIN 7 = Unload Door Open PLC OUT PIN 10 = Front UP DS1-B=LOAD Door Switch DS2-B=UNLOAD Door Switch Probable Solutions Page Base Section Electrical Malfunctions LS1-B=FRONT Down Switch LS2-B=REAR Down Switch Lint Screen Must be Cleaned Every Five 5 Drying Cycles Clogged Lint Screen or Lint BAG AIR Pressure Setting SEL a = Load SEL B = Unload Pendant Control MalfunctionsTumbler Forward Pendant --- PB1 Fuse 4 on Main Electrical Panel Faulty Switches Temperature Sensing Exhaust Dsfl Message a Probable Causes Temperature Sensing Component DescriptionsDefective Analog Input Module or Channel Motors Circuit Wiring to the Analog Input ModuleProbable Solutions ADS-464 Idling ADS-464 Running ADC 06/18/96-3 06/24/96-25 11/12/99-20