B. TUMBLER SECTION ELECTRICAL MALFUNCTIONS

INTRODUCTION

There are a number of electrical components associated with the ADS-464 tumbler section. These components are all interfaced to the tumbler junction box, and connected to the main electrical enclosure through a dis- connectable cable.

The “tumbler junction box” is located on the left side of the tumbler, in the same area as the left drum motor. The title of the wiring for the tumbler section is “ADS-464 Tumbler Electrical Junction Box Wiring Diagram.” The tumbler section electrical components provide:

-Front and rear door position information

-Drum rotation information

-Rear panel controls for unloading

-EMERGENCY STOP (E-STOP)

The “tumbler junction box” is located on the left side of the tumbler section, in the same area as the left drum motor. The title of the wiring diagram for the tumbler section is “ADS-464 Tumbler Electrical Junction Box Wiring Diagram.” The tumbler section electrical components provide:

The following information will provide a means to respond to fault messages associated with the tumbler section, and verify all the electrical signals associated with it.

Refer to the ADS-464 Tumbler Junction Box Wiring Diagram for detailed wiring information.

1.0Tumbler Section Electrical Components

1.Load Door Switch - DS1

The load door switch is located on the left side of the ADS-464 front doors and compromises of four (4) parts: head, arm, body and cord grip device. The head is a rotating type, with a spring arm attached for switch actuation. The body contains a double pole, double throw, normally open switch. DS1 has two

(2) electrical functions, A and B.

2.Unload Door Switch - DS2

The unload door switch is located on the right side of the ADS-464 rear doors and compromises of four (4) parts: Head, Arm, Body, Cord Grip device. The head is rotating type, with a spring arm attached for switch actuation. The body contains a double pole, double throw, switch. DS2 has two (2) electrical functions, A and B.

“A” provides rear door position signal to the PLC (Programmable Logic Controller).

“B” is a rear interlock to the burner controller circuit.

56

Image 60
Contents ADS-464 Installation/Operators Manual For Your Safety Pour Votre Sécurité Retain This Manual In a Safe Place For Future ReferenceFor Your Safety Page Table of Contents Service Parts Section Important InformationSafety Precautions Explosion could ResultPage SPECIFICATIONS/DIMENSIONS SpecificationsDimensions Installation Procedures Reassembly of DryerPage Page Location Requirements Internal AIR, Electrical and Water Connections Page Page Page Page Page External Supply Connections Page MAN2371 Page Electrical Requirements Latest EditionElectrical Service Specifications PER Dryer Dedicated Sprinkler ServicePage Fresh AIR Supply Requirements Steam Information 900 kg/hrShut Down Instructions PRE START-UP Preparation for OperationRoutine Maintenance CleaningSuggested Cleaning Schedule Monthly Component System Descriptions Tumbler Basket Support and Drive SystemPage Page Main AIR Blower and Heat Reclaimer System Heat Reclaim ER Settings Compressed AIR System Page Internal and External Pilot Air Supply Safety Devices Door Open SERVICE/PARTS Information ServiceParts Warranty Information Returning Warranty CardsWarranty Returning Warranty PartsPage Troubleshooting StandardsPower Malfunctions Probable CausesNo Control Power Blue Light Off Machine Main Power Shuts Down Blue Indicator Off 3CRB Not Used Sprinkler Circuit ComponentsSprinkler Circuit Description Page ADS-464 on button does respond Possible Solutions General Description Unless the Water Valve to the Sprinkler is ClosedPage Page Tumbler Section Electrical Malfunctions IntroductionPage Rear Panel Control Problems Emergency Stop E-Stop Function Drum Forward and Reverse Function PLC OUT PIN 7 = Unload Door Open PLC OUT PIN 10 = Front UP DS1-B=LOAD Door Switch DS2-B=UNLOAD Door Switch Probable Solutions Page Base Section Electrical Malfunctions LS1-B=FRONT Down Switch LS2-B=REAR Down Switch Lint Screen Must be Cleaned Every Five 5 Drying Cycles Clogged Lint Screen or Lint BAG AIR Pressure Setting Pendant Control Malfunctions SEL a = Load SEL B = UnloadTumbler Forward Pendant --- PB1 Fuse 4 on Main Electrical Panel Faulty Switches Temperature Sensing Temperature Sensing Component Descriptions Exhaust Dsfl Message a Probable CausesDefective Analog Input Module or Channel Circuit Wiring to the Analog Input Module MotorsProbable Solutions ADS-464 Idling ADS-464 Running ADC 06/18/96-3 06/24/96-25 11/12/99-20