American Dryer Corp ADS-464 manual General Description

Page 57

General Description:

The six (6) channels accept independent RTD (Resistive Temperature Device) inputs (spare channels have a 100 ohm [100 Ω] 5% tolerance resistors installed) and there is an individual set point for each channel. In operation, the scan rate between channels is four (4) to six (6) seconds, and the display will have the temperature measured by the individual RTD’s. A “red” L.E.D. indicates an alarm condition; in the event of an alarm, scanning is halted and the “ALARM” relay de-energizes until the manual reset button is depressed.

IMPORTANT: If a hi-limit alarm occurs, check that a hi-temperature has not occurred. If no, correct the condition and test.

IMPORTANT: DO NOT TROUBLESHOOT THE SHLC (Sprinkler High Limit Controller)

UNLESS THE WATER VALVE TO THE SPRINKLER IS CLOSED.

SHLC will cause:

The sprinkler water valve to open.

The entire dryer to power down.

The “SPRINKLER RESET” button on the main panel to light.

With the dryer control voltage “ON,” not executing a drying cycle, one should be able to adjust the temperature settings on any of the hi-limit controllers and cause their respective “GREEN” L.E.D.’s (light emitting diodes) to cycle “ON” and “OFF.”

If their corresponding L.E.D.’s (light emitting diodes) do not cycle, check their respective:

temperature sensors (RTD’s [Resistive Temperature Device])

power connections

electrical circuits (refer to the ADS-464 main electrical wiring diagram)

If the previous items are “OK,” replace the hi-limit controller.

6.“HI-TEMP FAULT” Message

PLC MESSAGE “HI-TEMP FAULT”

a.PROBABLE CAUSES;

1.Airflow

2.Hi-limit temperature controllers (channel 1 and channel 2)

3.RTD 1 and 2

4.Fuse 10

b.POSSIBLE SOLUTIONS;

1.For airflow problems refer to D. External Supply Connections - 4. exhaust air ducting.

2.An illuminated red indicator on the HI-LIMIT TEMP CONTROLLER indicates that the hi-limit control relay is in “ALARM” and in internal relay is “OPEN.”

53

Image 57
Contents ADS-464 Installation/Operators Manual Retain This Manual In a Safe Place For Future Reference For Your Safety Pour Votre SécuritéFor Your Safety Page Table of Contents Service Parts Important Information SectionExplosion could Result Safety PrecautionsPage Specifications SPECIFICATIONS/DIMENSIONSDimensions Reassembly of Dryer Installation ProceduresPage Page Location Requirements Internal AIR, Electrical and Water Connections Page Page Page Page Page External Supply Connections Page MAN2371 Page Latest Edition Electrical RequirementsDedicated Sprinkler Service Electrical Service Specifications PER DryerPage Fresh AIR Supply Requirements 900 kg/hr Steam InformationShut Down Instructions Preparation for Operation PRE START-UPRoutine Maintenance CleaningSuggested Cleaning Schedule Monthly Tumbler Basket Support and Drive System Component System DescriptionsPage Page Main AIR Blower and Heat Reclaimer System Heat Reclaim ER Settings Compressed AIR System Page Internal and External Pilot Air Supply Safety Devices Door Open SERVICE/PARTS Information ServiceParts Returning Warranty Cards Warranty InformationWarranty Returning Warranty PartsPage Standards TroubleshootingProbable Causes Power MalfunctionsNo Control Power Blue Light Off Machine Main Power Shuts Down Blue Indicator Off Sprinkler Circuit Components 3CRB Not UsedSprinkler Circuit Description Page ADS-464 on button does respond Possible Solutions Unless the Water Valve to the Sprinkler is Closed General DescriptionPage Page Introduction Tumbler Section Electrical MalfunctionsPage Rear Panel Control Problems Emergency Stop E-Stop Function Drum Forward and Reverse Function PLC OUT PIN 7 = Unload Door Open PLC OUT PIN 10 = Front UP DS1-B=LOAD Door Switch DS2-B=UNLOAD Door Switch Probable Solutions Page Base Section Electrical Malfunctions LS1-B=FRONT Down Switch LS2-B=REAR Down Switch Lint Screen Must be Cleaned Every Five 5 Drying Cycles Clogged Lint Screen or Lint BAG AIR Pressure Setting SEL a = Load SEL B = Unload Pendant Control MalfunctionsTumbler Forward Pendant --- PB1 Fuse 4 on Main Electrical Panel Faulty Switches Temperature Sensing Exhaust Dsfl Message a Probable Causes Temperature Sensing Component DescriptionsDefective Analog Input Module or Channel Motors Circuit Wiring to the Analog Input ModuleProbable Solutions ADS-464 Idling ADS-464 Running ADC 06/18/96-3 06/24/96-25 11/12/99-20