b)POSSIBLE SOLUTIONS;
1b) For Air Flow problems refer to SECTION III - Item D (External Supply Connections) - paragraph #4 (Exhaust Air Ducting) on page 20 and page 21.
NOTE: An illuminated “RED” L.E.D. (light emitting diode) indicator on the
•If anyone of the
•If a
HLS1 = MAXIMUM INTAKE TEMPERATURE
HLS2 = MAXIMUM OVER BURNER TEMPERATURE HLS3 = MAXIMUM EXHAUST TEMPERATURE
•The
•Let the dryer cool and verify that “GREEN” L.E.D.’s resume scanning. Reset the controller by pressing the “REST” on the controller. This will verify that an over temperature condition occurred and the controller is operational.
•Go to paragraph #1b above and check air flow.
•If the
2b) If either RTD (Resistive Temperature Device) 1, 2, 3 were to open or become disconnected, the associated temperature channel, of the
Check the resistance of the RTD (Resistive Temperature Device) at its connector, located in the right hand cable through.
•If 0 ohms (0 Ω) is measured;
•Check RTD (Resistive Temperature Device)
•Check wiring to the RTD (refer to the main panel wiring diagram)
•Check wiring to the
71