3.Electrical Service
The electrical power is connected the dryer at the high voltage section of the control cabinet. On the ADG-464 dryer, this section is located at the bottom left of the main electrical enclosure.
The ADG-464 dryer must be supplied with two (2) independent input power lines. One is 3-phase ( 3ø) electric service that feeds the dryer itself, and the other is 1ø electric service that feeds the safety sprinkler system. Both input lines must be independent of each other and individually protected by their individual fused disconnect.
NOTE: The ADG-464 with sprinkler option will not operate without an independent power source fed to the Safety Sprinkler System.
Feed the electrical service cables to the dryer using the pre-punched knockouts at the bottom section of the electrical cabinet right wall.
Connect the ground wires directly to the ground lug located at the same approximate area.
NOTE: The sprinkler operates off of single-phase (1ø) nameplate voltage of the dryer.
Before turning power on to the dryer, measure the supply voltage to ensure that it matches the dryer’s specified input voltage. This input voltage is marked on the aluminum data plate located on the inner right wall of the electrical cabinet.