American Dryer Corp ADG-464 manual Lint Chamber Pressure Switch PS3, Probable Solutions

Page 87

4.Lint Chamber Pressure Switch - PS3

The “Lint Chamber Pressure Sensing Switch” is located on the left rear side of the AD-464 base. It is an Adjustable pressure switch, which incorporate a single-pole-single-throw (SPST) switch. PS3’s electrical function is to close its switch when the “present pressure” in the lint chamber is sufficient. This switch is wired in series with other switches to form an interlock to the Burner Control Module (BCM).

5.Tumbler (Basket) Tilt Problems “LEVEL FAULT”

A “LEVEL FAULT” message is generated by the incorrect state of either the FRONT or REAR sensor switches. The following information will address the “LEVEL” signals, since they are associated with the Base Electrical Junction Box.

a)PROBABLE CAUSES;

1a) Wiring back to the PLC (Programmable Logic Controller)

LS1-B = FRONT DOWN SWITCH LS2-B = REAR DOWN SWITCH

b)PROBABLE SOLUTIONS;

1b) For a quick check of the FRONT DOWN and REAR DOWN signals to the PLC (Programmable Logic Controller) perform the following:

FRONT DOWN signal test procedure: paragraph 5a above

REAR DOWN signal test procedure: paragraph 5b above

2b) Place the AD-464 in the LOAD position; Front Up

Actuate the Front Down switch by hand.

Have someone verify that PLC (Programmable Logic Controller) input L.E.D. (light emitting diode) #11 lights when the switch actuator is down, and is OFF when the actuator is up.

Does L.E.D. (light emitting diode) #11 come “ON” when the switch is down?

If yes, wiring is OK.

Check switch and actuator placement and tilt actuation.

NOTE: If actuator is at a 90° or greater angle with the base, the actuator will damage if machine is lowered.

83

Image 87
Contents ADG-464 Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Service Parts Returning Warranty Cards Parts Returning Warranty PartsTroubleshooting TOC Section What to do if YOU Smell GAS Safety PrecautionsPage Specifications SPECIFICATIONS/DIMENSIONSDimensions Reassembly of Dryer Installation ProceduresPage Page Location Requirements Internal AIR, Electric and Water Connections Page Page Page Page Page Left Drum Motor External Supply Connections Page Page Electrical Requirements Electrical RequirementsElectrical Service Specifications PER Dryer Page Fresh AIR Supply Requirements Preparation for Operation PRE START-UPCleaning Routine MaintenanceMonthly Component System Descriptions Page Page Main AIR Blower and Heat Reclaimer System Page Additives or Solvents Compressed AIR SystemPage Page GAS Burner and Ignition System Switch #1 Recycling Mode Page Page Page Page Page Page Page Safety Devices Level Fault Parts ServiceReturning Warranty Cards WarrantyReturning Warranty Parts Page Troubleshooting Power Malfunctions Possible SolutionsProbable Causes No Control Power Blue Light Off Machine Main Power Shuts Down Blue Indicator Off 2CRB Sprinkler Circuit Description Page If no, go to on Possible Solutions Unless the Water Valve to the Sprinkler is Closed General DescriptionBurner Section Input Circuit Component Description Burner Controller Input Signal ComponentsBurner Ignition IntroductionLoad Door Switch DS1B Stop Detector Relay Contact SMD no Output Signal Component DescriptionGAS Fault Message gas system only Heater Fault Message Possible Solutions Page Page AIR Fault Message HI-TEMP Fault Message Possible Solutions Drum Fault Message Page Tumbler Basket Section Electrical Components Tumbler Basket Section Electrical MalfunctionsFollowing is for 2-Door Models only Rear Panel Control Problems Probable Causes Possible Solutions PLC OUT PIN 7 = Unload Door Open PLC OUT PIN 10 = Front UP Unload 1 Selection Probable CausesDoor Open Problem Drum Fault Message Malfunction Probable Causes Page Base Section Electrical Malfunctions Front Door SwitchRear Down Switch LS2 Lint Drawer Proximity SwitchesLint Chamber Pressure Switch PS3 Tumbler Basket Tilt Problems Level FaultProbable Solutions Page Lint Screen Mechanism Problem Screen Fault Lint Chamber Air Pressure Problem AIR Fault Pendant Electrical Components Pendant Control MalfunctionsVerify Pendant Electrical Signals Wiring Diagram Temperature Sensing Page Temperature Measurement and Sensing Problems Motors Circuit Wiring to the Analog Input ModuleMotor Protection Device Descriptions Motor Actuation Problems Probable CausesBurner Controller stops heat PLC Programmable Logic Controller Error Messages