General Description:

The six (6) channels accept independent RTD (Resistive Temperature Device) inputs (spare channels have a 100 ohm [100 Ω] 5% tolerance resistors installed) and there is an individual set point for each channel. In operation, the scan rate between channels is four (4) to six (6) seconds, and the display will have the temperature measured by the individual RTD’s. A “red” L.E.D. indicates an alarm condition; in the event of an alarm, scanning is halted and the “ALARM” relay de-energizes until the manual reset button is depressed.

IMPORTANT: If a hi-limit alarm occurs, check that a hi-temperature has not occurred. If no, correct the condition and test.

IMPORTANT: DO NOT TROUBLESHOOT THE SHLC (Sprinkler High Limit Controller)

UNLESS THE WATER VALVE TO THE SPRINKLER IS CLOSED.

SHLC will cause:

The sprinkler water valve to open.

The entire dryer to power down.

The “SPRINKLER RESET” button on the main panel to light.

With the dryer control voltage “ON,” not executing a drying cycle, one should be able to adjust the temperature settings on any of the hi-limit controllers and cause their respective “GREEN” L.E.D.’s (light emitting diodes) to cycle “ON” and “OFF.”

If their corresponding L.E.D.’s (light emitting diodes) do not cycle, check their respective:

temperature sensors (RTD’s [Resistive Temperature Device])

power connections

electrical circuits (refer to the ADG-464 main electrical wiring diagram)

If the previous items are “OK,” replace the hi-limit controller.

60

Image 64
Contents ADG-464 Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Returning Warranty Cards Parts Returning Warranty Parts Service PartsTroubleshooting TOC Section Safety Precautions What to do if YOU Smell GASPage SPECIFICATIONS/DIMENSIONS SpecificationsDimensions Installation Procedures Reassembly of DryerPage Page Location Requirements Internal AIR, Electric and Water Connections Page Page Page Page Page Left Drum Motor External Supply Connections Page Page Electrical Requirements Electrical RequirementsElectrical Service Specifications PER Dryer Page Fresh AIR Supply Requirements PRE START-UP Preparation for OperationRoutine Maintenance CleaningMonthly Component System Descriptions Page Page Main AIR Blower and Heat Reclaimer System Page Compressed AIR System Additives or SolventsPage Page GAS Burner and Ignition System Switch #1 Recycling Mode Page Page Page Page Page Page Page Safety Devices Level Fault Service PartsWarranty Returning Warranty CardsReturning Warranty Parts Page Troubleshooting Possible Solutions Power MalfunctionsProbable Causes No Control Power Blue Light Off Machine Main Power Shuts Down Blue Indicator Off 2CRB Sprinkler Circuit Description Page If no, go to on Possible Solutions General Description Unless the Water Valve to the Sprinkler is ClosedBurner Controller Input Signal Components Burner IgnitionIntroduction Burner Section Input Circuit Component DescriptionLoad Door Switch DS1B Output Signal Component Description Stop Detector Relay Contact SMD noGAS Fault Message gas system only Heater Fault Message Possible Solutions Page Page AIR Fault Message HI-TEMP Fault Message Possible Solutions Drum Fault Message Page Tumbler Basket Section Electrical Malfunctions Tumbler Basket Section Electrical ComponentsFollowing is for 2-Door Models only Rear Panel Control Problems Probable Causes Possible Solutions Unload 1 Selection Probable Causes PLC OUT PIN 7 = Unload Door Open PLC OUT PIN 10 = Front UPDoor Open Problem Drum Fault Message Malfunction Probable Causes Page Front Door Switch Rear Down Switch LS2Lint Drawer Proximity Switches Base Section Electrical MalfunctionsTumbler Basket Tilt Problems Level Fault Lint Chamber Pressure Switch PS3Probable Solutions Page Lint Screen Mechanism Problem Screen Fault Lint Chamber Air Pressure Problem AIR Fault Pendant Control Malfunctions Pendant Electrical ComponentsVerify Pendant Electrical Signals Wiring Diagram Temperature Sensing Page Temperature Measurement and Sensing Problems Circuit Wiring to the Analog Input Module MotorsMotor Actuation Problems Probable Causes Motor Protection Device DescriptionsPLC Programmable Logic Controller Error Messages Burner Controller stops heat