Siemens FX300 manual Turning the display, Turn the display as follows

Page 24

3 INSTALLATION

 

 

SITRANS FX300

 

 

 

 

3.4.6 Turning the display

DANGER!

All work on the device electrics may only be carried out by appropriately trained personnel. The regional occupational health and safety directives must always be observed.

INFORMATION!

If the measuring device is installed in a vertical pipe, you will have to turn the display by 90°; if installed below a pipe, turn 180°.

Figure 3-6: Turning the display

Turn the display as follows:

Disconnect the power supply from the measuring device.

Unscrew the cover in front of the display 1 from the connection housing.

Pull the display 2 carefully a few centimetres out of the anchor fitting and turn it to the required position 3.

Press the display onto the spacer pins 4, until it clicks.

Turn the cover with gasket 5 back onto the housing and tighten it by hand.

24

www.siemens.com/flow

06/2009 - SFIDK.PS.050.F2.02 A5E02100423

Image 24
Contents Page Imprint Contents Contents Technical data Safety Instructions Intended useDevices are particularly suitable for the measurement Devices are rated for the following flow velocitiesCertifications CE markingSafety instructions from the manufacturer Copyright and data protectionDisclaimer Product liability and warranty Information concerning the documentationSafety instructions for the operator Safety warnings are indicated by the following symbolsScope of delivery Instrument versionsDevices come in the following versions Following designs are available as optionsDevices with connection flange Sandwich versionFree air delivery measurement FAD optional Gross heat meter Dual seal Nameplate Storage TransportInstallation Installation condtitionsProhibited installation Measurement of liquidsRecommended installations for measurement of liquids Prohibited installation Measurement of vapours and gasesPipelines with control valve Preferred mounting positionPreferred mounting position Turning the connection housing Allen screws on connection housingTurning the display Turn the display as followsHeat insulation Inlet and outlet runs Minimum inlet runsMinimum outlet runs Flow straightenerInstallation General installation notesInstalling devices in flange design Installing devices in sandwich design Safety instructions Electrical ConnectionsFollowing procedures are to be performed Electrical ConnectionsElectrical connection of current and pulse output Maximum load resistance is calculated as followsPower supply Totalizer / pulse outputElectrical Connections Maximum frequency of the pulse output is fmax = 0.5 HzGrounding connections Protection category Therefore it is essential to observe the following pointsSTART-UP StartStart-up and control Operation Display and operating elementsSwitch from measuring mode to menu mode OperationOperating principles Functional description of the keysChanging the settings in the menu Navigation within the menu structureChanging units Measures in the event of faulty indications Totalizer / pulse outputMax. pulses per hour ExampleVolume Standard volume Mass Liquids, steams, gases Air Gas Overview of the most important functions and unitsLevel Designation Explanation Volume Standard volume Mass Liquids, steams, gases Gas Temp Absolute Power Energy Density Pressure OverError messages Error message Cause MeasureMenu structure Overview of firmware versionsEntering values in change mode Character selection in change modeMenu item Quick Setup Menu item Tests Level Designation Selection / entry ExplanationTest current is maintained until the menu has been exited Menu item Setup firmware version basic Hart SV Operation Menu item Setup firmware version steam Reset heat energy Hart tertiary variable Temp. ↑ Pressure ↑ Density Operation Menu item Setup firmware version gas Hart SV RPM Pressure, temperature and density Operation Replacing signal converter / LCD display Following steps are to be performedService Availability of servicesSpare parts availability Returning the device to the manufacturerForm for copying to accompany a returned device Technical Data Functional principleTechnical data Measuring systemMeasuring accuracy Installation conditions Operating conditionsMaterials Process connections Electrical connectionsApprovals and certifications Dimensions and weights Flange versionsFlange version EN Technical Data Flange version Asme B16.5 NPSSandwich version EN Size Pressure Dimensions inches Weight lbs Rating Sandwich version AsmeWith Without Pressure sensor Flow tables Measuring rangesWater AirFlow rate limits Product Nominal sizes Minimum flow rates Maximum flow ratesFt/s Measuring range saturated steam 1...7 bar Measuring range saturated steam 10.5...20 barKg/h 1092-1Measuring range saturated steam 15...100 psig Measuring range saturated steam 150...300 psigLbs/h Sitrans FX300