4 ELECTRICAL CONNECTIONS

 

 

SITRANS FX300

 

 

 

 

4.3.1 Power supply

INFORMATION!

The supply voltage has to be between 14 VDC and 36 VDC. This is based on the total resistance of the measuring loop. To determine this, add up the resistances of each component in the measuring loop (not including the measuring device).

The required supply voltage can be calculated using the formula below:

Uext. = RL * 22mA + 14V

where

Uext. = the minimum supply voltage and

RL = the total measuring loop resistance is.

INFORMATION!

The power supply has to be able to supply a minimum of 22 mA.

4.3.2 Totalizer / pulse output

The basic units for the totalizer and the pulse output are m3 for volume,

m3norm. for standard volume and kg for mass.

The unit and the conversion factor can be changed in menu item 3.2.8 "Conf.Tot". User specific units (User Def.) can also be entered but the conversion factor must always be entered based on the base unit. For a sample calculation see chapter 6.2.5 "Change units".

The maximum frequency of the pulse output is 0.5 Hz.

Figure 4-3: Pulse output

1fmax 0.5 Hz

2closed

3open

4Pulse 250 ms

34

www.siemens.com/flow

06/2009 - SFIDK.PS.050.F2.02 A5E02100423

Image 34
Contents Page Imprint Contents Contents Technical data Devices are particularly suitable for the measurement Safety InstructionsIntended use Devices are rated for the following flow velocitiesCertifications CE markingCopyright and data protection Safety instructions from the manufacturerDisclaimer Product liability and warranty Information concerning the documentationSafety instructions for the operator Safety warnings are indicated by the following symbolsDevices come in the following versions Scope of deliveryInstrument versions Following designs are available as optionsDevices with connection flange Sandwich versionFree air delivery measurement FAD optional Gross heat meter Dual seal Nameplate Storage TransportInstallation Installation condtitionsProhibited installation Measurement of liquidsRecommended installations for measurement of liquids Prohibited installation Measurement of vapours and gasesPreferred mounting position Pipelines with control valvePreferred mounting position Turning the connection housing Allen screws on connection housingTurning the display Turn the display as followsHeat insulation Inlet and outlet runs Minimum inlet runsMinimum outlet runs Flow straightenerInstallation General installation notesInstalling devices in flange design Installing devices in sandwich design Safety instructions Electrical ConnectionsFollowing procedures are to be performed Electrical ConnectionsElectrical connection of current and pulse output Maximum load resistance is calculated as followsPower supply Totalizer / pulse outputElectrical Connections Maximum frequency of the pulse output is fmax = 0.5 HzGrounding connections Protection category Therefore it is essential to observe the following pointsStart START-UPStart-up and control Operation Display and operating elementsOperating principles Switch from measuring mode to menu modeOperation Functional description of the keysChanging the settings in the menu Navigation within the menu structureChanging units Max. pulses per hour Measures in the event of faulty indicationsTotalizer / pulse output ExampleOverview of the most important functions and units Volume Standard volume Mass Liquids, steams, gases Air GasLevel Designation Explanation Volume Standard volume Mass Liquids, steams, gases Gas Temp Absolute Power Energy Density Pressure OverError messages Error message Cause MeasureMenu structure Overview of firmware versionsEntering values in change mode Character selection in change modeMenu item Quick Setup Level Designation Selection / entry Explanation Menu item TestsTest current is maintained until the menu has been exited Menu item Setup firmware version basic Hart SV Operation Menu item Setup firmware version steam Reset heat energy Hart tertiary variable Temp. ↑ Pressure ↑ Density Operation Menu item Setup firmware version gas Hart SV RPM Pressure, temperature and density Operation Replacing signal converter / LCD display Following steps are to be performedSpare parts availability ServiceAvailability of services Returning the device to the manufacturerForm for copying to accompany a returned device Technical Data Functional principleMeasuring system Technical dataMeasuring accuracy Operating conditions Installation conditionsMaterials Electrical connections Process connectionsApprovals and certifications Flange versions Dimensions and weightsFlange version EN Technical Data Flange version Asme B16.5 NPSSandwich version EN Sandwich version Asme Size Pressure Dimensions inches Weight lbs RatingWith Without Pressure sensor Water Flow tablesMeasuring ranges AirProduct Nominal sizes Minimum flow rates Maximum flow rates Flow rate limitsFt/s Kg/h Measuring range saturated steam 1...7 barMeasuring range saturated steam 10.5...20 bar 1092-1Measuring range saturated steam 150...300 psig Measuring range saturated steam 15...100 psigLbs/h Sitrans FX300