4 |
Example 5: Role switches allowed on both units Secondary Unit Active
Note: Secondary unit active is not a recommended mode of operation when using the GHS Control Strategy.
| Primary Unit | Secondary Unit |
|
|
|
Role | Backup | Active |
|
|
|
Operating Mode | RUN/ENABLED | RUN/ENABLED |
|
|
|
OK LED on RCM | ON | ON |
|
|
|
LOC_RDY LED on RCM and %S Bit | ON | ON |
|
|
|
LOC_ACT LED on RCM and %S Bit | OFF | ON |
|
|
|
REM_RDY LED on RCM and %S Bit | ON | ON |
|
|
|
REM_ACT LED on RCM and %S Bit | ON | OFF |
|
|
|
Example 6: Role switches not allowed on either unit, Secondary Unit Active
Note: Secondary unit active is not a recommended mode of operation when using the GHS Control Strategy.
| Primary Unit | Secondary Unit |
|
|
|
Role | Backup | Active |
|
|
|
Operating Mode | RUN/DISABLED | RUN/ENABLED |
|
|
|
OK LED on RCM | ON | ON |
|
|
|
LOC_RDY LED on RCM and %S Bit | OFF | ON |
|
|
|
LOC_ACT LED on RCM and %S Bit | OFF | ON |
|
|
|
REM_RDY LED on RCM and %S Bit | ON | OFF |
|
|
|
REM_ACT LED on RCM and %S Bit | ON | OFF |
|
|
|
Example 7: Role switches allowed on both units, Secondary Unit Active
Note: Secondary unit active is not a recommended mode of operation when using the GHS Control Strategy.
| Primary Unit | Secondary Unit |
|
|
|
Role | Backup | Active |
|
|
|
Operating Mode | RUN/DISABLED | RUN/DISABLED |
|
|
|
OK LED on RCM | ON | ON |
|
|
|
LOC_RDY LED on RCM and %S Bit | OFF | OFF |
|
|
|
LOC_ACT LED on RCM and %S Bit | OFF | ON |
|
|
|
REM_RDY LED on RCM and %S Bit | OFF | OFF |
|
|
|
REM_ACT LED on RCM and %S Bit | ON | OFF |
|
|
|
| Chapter 4 Normal Operation |