Special Conditions for Safe Use (X):

The device is not capable of withstanding the 500V insulation test required by Clause 6.3.12 of EN60079-11. This must be taken into account when installing the apparatus.

E1 ATEX Flame-Proof

Certification No. KEMA 08ATEX0090X G Manual background II 1/2 G

Ex d IIC T6 (Tamb = –50 to 65 °C)

Ex d IIC T5 (Tamb = –50 to 80 °C)

IP66

Manual background 1180

Vmax = 32 V dc

Special Conditions for Safe Use (X):

1.Appropriate ex d blanking plugs, cable glands, and wiring needs to be suitable for a temperature of 90 °C.

2.This device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for maintenance shall be followed in detail to assure safety during its expected lifetime.

3.The 2051 does not comply with the requirements of IEC 60079-1 Clause 5 for flameproof joints. Contact Emerson Process Management for information on the dimensions of flameproof joints.

ND ATEX Dust

Certification No. Baseefa08ATEX0182X Manual background II 1 D Dust Rating: T80 °C (–20 ≤ Ta ≤ 40 °C) IP66 IP68 Vmax = 42.4 V dc

A = 22 mA Manual background 1180

Special Conditions for Safe Use (X):

1.The user must ensure that the maximum rated voltage and current (42.4 volts, 22 milliampere, DC) are not exceeded. All connections to other apparatus or associated apparatus shall have control over this voltage and current equivalent to a category “ib” circuit according to EN 60079-1.

2.Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66.

3.Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66.

4.Cable entries and blanking plugs must be suitable for the ambient range of the apparatus and capable of withstanding a 7J impact test.

B-4

Image 104
Contents Rosemount 2051 Pressure Transmitter with FOUNDATION Fieldbus ProtocolReference Manual Page Rosemount 2051 Pressure Transmitter with FOUNDATION FieldbusRosemount Reference ManualPage Table of Contents SECTION 1 Introduction SECTION 2 InstallationSECTION 3 Configuration RosemountSECTION Operation and Maintenance SECTION 5 TroubleshootingAPPENDIX A Reference Data RosemountAPPENDIX B Approval Information APPENDIX C Block InformationRosemount Reference ManualTOC-4 RosemountReference Manual USING THIS MANUAL SERVICE SUPPORT SectionIntroduction RosemountReference Manual MODELS COVEREDRosemount Installation OVERVIEW SAFETY MESSAGES WarningsSection RosemountGENERAL CONSIDERATIONSMECHANICAL ENVIRONMENTALINSTALLATION PROCEDURES Dimensional Drawings2051C Coplanar Flange Dimensional Drawing RosemountCoplanar Flange Mounting Configurations with RosemountReference Manual 00809-0200-4101,Rev AAReference Manual 2051C Coplanar with Traditional FlangeRosemount Traditional Flange Mounting Configurations with Optional Brackets for 2-in.Pipe or Panel MountingRosemount Reference Manual2051T Dimensional Drawings 2051T with Rosemount 306 Integral ManifoldRosemount Reference ManualRosemount Reference ManualPipe Mounting Panel MountingReference Manual 2051L Liquid LevelRosemount Reference Manual Mount the TransmitterRosemount 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Figure 2-6.Traditional Flange Bolt Configurations RosemountReference Manual 00809-0200-4101,Rev AA JulyReference Manual Impulse PipingRosemount Flow RosemountReference Manual Reference Manual Process ConnectionsRosemount 00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual Housing RotationRosemount LCD Display TaggingRosemount Reference ManualConduit Installation ELECTRICALRosemount Reference ManualReference Manual WiringRosemount Reference Manual Transient Protection Terminal BlockRosemount Reference Manual JumpersSecurityRosemount Reference Manual GroundingRosemount Figure 2-17.External Ground Assembly External Ground AssemblyRosemount Reference ManualHAZARDOUS LOCATIONS CERTIFICATIONS ROSEMOUNT 305, 306 AND 304 MANIFOLDSRosemount Reference ManualRosemount 305 Integral Manifold Installation Procedure Rosemount 306 IntegralManifold Installation Procedure Rosemount Conventional Manifold Installation ProcedureReference Manual Integral Manifold OperationRosemount 00809-0200-4101,Rev AA July RosemountReference Manual LIQUID LEVEL MEASUREMENT Open Vessels Closed VesselsRosemount Reference Manual00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Rosemount Reference ManualConfiguration OVERVIEW SAFETY MESSAGES WarningsSection RosemountDEVICE CAPABILITIES Link Active Scheduler CapabilitiesGENERAL BLOCK INFORMATION Modes RosemountRESOURCE BLOCK FEATURES and FEATURES SEL SimulationRosemount Reference ManualReference Manual MAX_NOTIFYRosemount Configure the AI block ANALOG INPUT AI FUNCTION BLOCKRosemount Reference ManualReference Manual Configuration ExamplesRosemount 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Filtering Low CutoffRosemount Reference ManualProcess Alarms Alarm Priority Status OptionsRosemount Reference ManualReference Manual Advanced Features LCD BLOCKRosemount 00809-0200-4101,Rev AA July RosemountReference Manual Section 4 Operation and Maintenance OVERVIEW SAFETY MESSAGES WarningsRosemount Reference ManualReference Manual STATUS Master Reset Method SimulationRosemount CALIBRATION Sensor Calibration Upper and Lower Trim MethodsRosemount Reference ManualSensor Calibration, Zero Trim Method Factory Calibration MethodRosemount Reference ManualSection 5 Troubleshooting OVERVIEW SAFETY MESSAGES WarningsRosemount Reference ManualTROUBLESHOOTING GUIDES RosemountReference Manual 00809-0200-4101,Rev AA JulyFigure 5-2.Problems with communications flowchart RosemountReference Manual 00809-0200-4101,Rev AA JulyTable 5-1.Troubleshooting guide RosemountReference Manual 00809-0200-4101,Rev AA JulyReference Manual RESOURCE BLOCKRosemount Reference Manual SENSOR TRANSDUCER BLOCKRosemount LCD TRANSDUCER BLOCK RosemountReference Manual ANALOG INPUT AI FUNCTION BLOCK1.Put Resource block into OOS Out of Service RosemountReference Manual 00809-0200-4101,Rev AA JulyDISASSEMBLY PROCEDURES Remove from Service Remove Terminal BlockRosemount Reference ManualReference Manual Remove the Electronics BoardRosemount REASSEMBLY PROCEDURES Attach the Electronics Board Install the Terminal BlockReassemble the 2051C Process Flange RosemountReference Manual Install the Drain/Vent ValveRosemount PERFORMANCE SPECIFICATIONS Conformance To Specification ±3σ SigmaAppendix A Reference DataLong Term Stability Dynamic PerformanceLine Pressure Effect per 1000 psi 6,9 MPa RosemountVibration Effect Power Supply Effect Ambient Temperature Effect per 50F 28CMounting Position Effects Electromagnetic Compatibility EMCFUNCTIONAL SPECIFICATIONS Range and Sensor Limits ServiceProtocols Rosemount00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual Overpressure LimitsRosemount Static Pressure Limit Burst Pressure Limits Temperature LimitsRosemount Reference ManualHumidity Limits Volumetric Displacement Damping Failure Mode AlarmRosemount Reference ManualPHYSICAL SPECIFICATIONS Electrical Connections Process Connections 2051C Process Wetted Parts2051T Process Wetted Parts 2051L Process Wetted PartsReference Manual Non-WettedParts for 2051C/T/LRosemount Shipping Weights Table A-4.Transmitter Weights without OptionsTable A-5.2051L Weights without Options Table A-6.Transmitter Options WeightsReference Manual ORDERING INFORMATIONRosemount Alternate Process Connection: Flange2 RosemountReference Manual CSA FISCO Intrinsically Safe RosemountReference Manual A-15 RosemountReference Manual GGage AAbsolute RosemountReference Manual FM Intrinsically Safe, Division RosemountReference Manual Rosemount Reference ManualSpecial Certifications Q4 Calibration Certificate Prior-usecertificate of FMEDA data4 -300to 300 psi/3 psi -20,7to 20,7 bar/0,2 bar RosemountReference Manual Syltherm XLT RosemountReference Manual Reference Manual ATEX Flameproof, Intrinsic Safety, Type n, DustRosemount Reference Manual OPTIONSRosemount 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual SPARE PARTS RosemountReference Manual LCD Display, FOUNDATION fieldbusNickel-platedcarbon steel RosemountReference Manual Gage Flange and Adapter Bolt Kit Set of RosemountReference Manual A-28 RosemountReference Manual OVERVIEW SAFETY MESSAGES Appendix B Approval InformationWarnings Approved Manufacturing LocationsEuropean Directive Information FIELDBUS PROTOCOLHazardous Locations Certifications Rosemount00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual APPROVAL DRAWINGS Factory Mutual FMRosemount Rosemount Reference ManualB-10 RosemountReference Manual B-11 RosemountReference Manual B-12 RosemountReference Manual B-13 RosemountReference Manual B-14 RosemountReference Manual B-15 RosemountReference Manual B-16 RosemountReference Manual B-17 RosemountReference Manual B-18 RosemountReference Manual B-19 RosemountReference Manual B-20 RosemountReference Manual Canadian Standards Association CSA RosemountReference Manual B-21B-22 RosemountReference Manual B-23 RosemountReference Manual B-24 RosemountReference Manual B-25 RosemountReference Manual B-26 RosemountReference Manual B-27 RosemountReference Manual B-28 RosemountReference Manual B-29 RosemountReference Manual B-30 RosemountReference Manual Appendix C Block InformationTRANSDUCER BLOCK Overview RosemountReference Manual Parameters and DescriptionsRosemount PRIMARY_VALUE_RANGE RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Troubleshooting OverviewRosemount Reference ManualRosemount Reference ManualParameters and Descriptions 00809-0200-4101,Rev AA JulyFLANGE_MTL RosemountReference Manual REM_SEAL_FILL RosemountReference Manual Simulate_STATE RosemountReference Manual Block Errors RosemountReference Manual 00809-0200-4101,Rev AA July00809-0200-4101,Rev AA July RosemountReference Manual Mode will not leave RosemountReference Manual C-14 RosemountReference Manual Reference Manual IndexRosemount 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Index-4 RosemountReference Manual 00809-0200-4101,Rev AA July NOTES RosemountReference Manual Rosemount Reference ManualPage Reference Manual Rosemount¢00809-0100-4801V¤