Configuration Examples

Rosemount 2051

Reference Manual

00809-0200-4101, Rev AA July 2008

L_TYPE is Indirect Square Root

When an inferred measurement is made based on the sensor measurement AND the relationship between the inferred measurement and sensor measurement is square root, set the XD_SCALE to represent the operating range that the sensor will see in the process. Determine the inferred measurement values that correspond to the XD_SCALE 0 and

100% points and set these for the OUT_SCALE.:

Pressure (Channel 1)

Temperature (Channel 2)

 

 

Pa

°C

 

 

kPa

°F

bar

 

 

 

mbar

 

torr

 

 

 

atm

 

psi

 

 

 

g/cm2

 

kg/cm2

 

inH2O at 68 °F

 

mmH2O at 68 °F

 

mmH2O at 4 °F

 

inHg at 0 °C

 

 

 

mmHg at 0 °C

 

 

 

NOTE

When the engineering units of the XD_SCALE are selected, this causes the engineering units of the PRIMARY_VALUE_RANGE in the Transducer Block to change to the same units. THIS IS THE ONLY WAY TO CHANGE THE ENGINEERING UNITS IN THE SENSOR TRANSDUCER BLOCK, PRIMARY_VALUE_RANGE parameter.

Configuration Examples

Pressure transmitter

Table 3-2. Analog Input function block configuration for a typical pressure transmitter.

Pressure transmitter used to measure level in an open tank

Situation #1

A pressure transmitter with a range of 0 – 100 psi.

Solution

Table 3-2 lists the appropriate configuration settings.

.

Parameter

Configured Values

 

 

L_TYPE

Direct

XD_SCALE

Primary_Value_Range

 

 

OUT_SCALE

Primary_Value_Range

Channel

1 - pressure

 

 

Situation #2

The level of an open tank is to be measured using a pressure tap at the bottom of the tank. The maximum level at the tank is 16 ft. The liquid in the tank has a density that makes the maximum level correspond to a pressure of 7.0 psi at the pressure tap (see Figure 3-1).

3-6

Image 50
Contents Rosemount 2051 Pressure Transmitter with FOUNDATION Fieldbus ProtocolReference Manual Page Rosemount Rosemount 2051 PressureTransmitter with FOUNDATION Fieldbus Reference ManualPage SECTION 3 Configuration Table of ContentsSECTION 1 Introduction SECTION 2 Installation RosemountAPPENDIX A Reference Data SECTION Operation and MaintenanceSECTION 5 Troubleshooting RosemountRosemount APPENDIX B Approval InformationAPPENDIX C Block Information Reference ManualTOC-4 RosemountReference Manual Introduction USING THIS MANUAL SERVICE SUPPORTSection RosemountReference Manual MODELS COVEREDRosemount Section InstallationOVERVIEW SAFETY MESSAGES Warnings RosemountMECHANICAL GENERALCONSIDERATIONS ENVIRONMENTAL2051C Coplanar Flange Dimensional Drawing INSTALLATION PROCEDURESDimensional Drawings RosemountReference Manual Coplanar Flange Mounting Configurations withRosemount 00809-0200-4101,Rev AAReference Manual 2051C Coplanar with Traditional FlangeRosemount Rosemount Traditional Flange Mounting Configurations withOptional Brackets for 2-in.Pipe or Panel Mounting Reference ManualRosemount 2051T Dimensional Drawings2051T with Rosemount 306 Integral Manifold Reference ManualPipe Mounting RosemountReference Manual Panel MountingReference Manual 2051L Liquid LevelRosemount Reference Manual Mount the TransmitterRosemount 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual Figure 2-6.Traditional Flange Bolt ConfigurationsRosemount 00809-0200-4101,Rev AA JulyReference Manual Impulse PipingRosemount Flow RosemountReference Manual Reference Manual Process ConnectionsRosemount 00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual Housing RotationRosemount Rosemount LCD DisplayTagging Reference ManualRosemount Conduit InstallationELECTRICAL Reference ManualReference Manual WiringRosemount Reference Manual Transient Protection Terminal BlockRosemount Reference Manual JumpersSecurityRosemount Reference Manual GroundingRosemount Rosemount Figure 2-17.External Ground AssemblyExternal Ground Assembly Reference ManualRosemount HAZARDOUS LOCATIONS CERTIFICATIONSROSEMOUNT 305, 306 AND 304 MANIFOLDS Reference ManualManifold Installation Procedure Rosemount Rosemount 305 Integral Manifold InstallationProcedure Rosemount 306 Integral Conventional Manifold Installation ProcedureReference Manual Integral Manifold OperationRosemount 00809-0200-4101,Rev AA July RosemountReference Manual Rosemount LIQUID LEVEL MEASUREMENTOpen Vessels Closed Vessels Reference Manual00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Rosemount Reference ManualSection ConfigurationOVERVIEW SAFETY MESSAGES Warnings RosemountGENERAL BLOCK INFORMATION Modes DEVICE CAPABILITIES Link Active SchedulerCapabilities RosemountRosemount RESOURCE BLOCK FEATURES and FEATURES SELSimulation Reference ManualReference Manual MAX_NOTIFYRosemount Rosemount Configure the AI blockANALOG INPUT AI FUNCTION BLOCK Reference ManualReference Manual Configuration ExamplesRosemount 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Rosemount FilteringLow Cutoff Reference ManualRosemount Process Alarms Alarm PriorityStatus Options Reference ManualReference Manual Advanced Features LCD BLOCKRosemount 00809-0200-4101,Rev AA July RosemountReference Manual Rosemount Section 4 Operation and MaintenanceOVERVIEW SAFETY MESSAGES Warnings Reference ManualReference Manual STATUS Master Reset Method SimulationRosemount Rosemount CALIBRATION Sensor CalibrationUpper and Lower Trim Methods Reference ManualRosemount Sensor Calibration, Zero Trim MethodFactory Calibration Method Reference ManualRosemount Section 5 TroubleshootingOVERVIEW SAFETY MESSAGES Warnings Reference ManualReference Manual TROUBLESHOOTING GUIDESRosemount 00809-0200-4101,Rev AA JulyReference Manual Figure 5-2.Problems with communications flowchartRosemount 00809-0200-4101,Rev AA JulyReference Manual Table 5-1.Troubleshooting guideRosemount 00809-0200-4101,Rev AA JulyReference Manual RESOURCE BLOCKRosemount Reference Manual SENSOR TRANSDUCER BLOCKRosemount Reference Manual LCD TRANSDUCER BLOCKRosemount ANALOG INPUT AI FUNCTION BLOCKReference Manual 1.Put Resource block into OOS Out of ServiceRosemount 00809-0200-4101,Rev AA JulyRosemount DISASSEMBLY PROCEDURES Remove from ServiceRemove Terminal Block Reference ManualReference Manual Remove the Electronics BoardRosemount Reassemble the 2051C Process Flange REASSEMBLY PROCEDURES Attach theElectronics Board Install the Terminal Block RosemountReference Manual Install the Drain/Vent ValveRosemount Appendix A PERFORMANCE SPECIFICATIONSConformance To Specification ±3σ Sigma Reference DataLine Pressure Effect per 1000 psi 6,9 MPa Long Term StabilityDynamic Performance RosemountMounting Position Effects Vibration Effect Power Supply EffectAmbient Temperature Effect per 50F 28C Electromagnetic Compatibility EMCProtocols FUNCTIONAL SPECIFICATIONS Range and Sensor LimitsService Rosemount00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual Overpressure LimitsRosemount Rosemount Static Pressure Limit Burst Pressure LimitsTemperature Limits Reference ManualRosemount Humidity Limits Volumetric Displacement DampingFailure Mode Alarm Reference Manual2051T Process Wetted Parts PHYSICAL SPECIFICATIONS Electrical ConnectionsProcess Connections 2051C Process Wetted Parts 2051L Process Wetted PartsReference Manual Non-WettedParts for 2051C/T/LRosemount Table A-5.2051L Weights without Options Shipping WeightsTable A-4.Transmitter Weights without Options Table A-6.Transmitter Options WeightsReference Manual ORDERING INFORMATIONRosemount Alternate Process Connection: Flange2 RosemountReference Manual CSA FISCO Intrinsically Safe RosemountReference Manual A-15 RosemountReference Manual GGage AAbsolute RosemountReference Manual FM Intrinsically Safe, Division RosemountReference Manual Special Certifications Q4 Calibration Certificate RosemountReference Manual Prior-usecertificate of FMEDA data4 -300to 300 psi/3 psi -20,7to 20,7 bar/0,2 bar RosemountReference Manual Syltherm XLT RosemountReference Manual Reference Manual ATEX Flameproof, Intrinsic Safety, Type n, DustRosemount Reference Manual OPTIONSRosemount 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual SPARE PARTSRosemount LCD Display, FOUNDATION fieldbusNickel-platedcarbon steel RosemountReference Manual Gage Flange and Adapter Bolt Kit Set of RosemountReference Manual A-28 RosemountReference Manual Warnings OVERVIEW SAFETY MESSAGESAppendix B Approval Information Approved Manufacturing LocationsHazardous Locations Certifications European Directive InformationFIELDBUS PROTOCOL Rosemount00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual APPROVAL DRAWINGS Factory Mutual FMRosemount Rosemount Reference ManualB-10 RosemountReference Manual B-11 RosemountReference Manual B-12 RosemountReference Manual B-13 RosemountReference Manual B-14 RosemountReference Manual B-15 RosemountReference Manual B-16 RosemountReference Manual B-17 RosemountReference Manual B-18 RosemountReference Manual B-19 RosemountReference Manual B-20 RosemountReference Manual Reference Manual Canadian Standards Association CSARosemount B-21B-22 RosemountReference Manual B-23 RosemountReference Manual B-24 RosemountReference Manual B-25 RosemountReference Manual B-26 RosemountReference Manual B-27 RosemountReference Manual B-28 RosemountReference Manual B-29 RosemountReference Manual B-30 RosemountReference Manual TRANSDUCER BLOCK Overview Appendix CBlock Information RosemountReference Manual Parameters and DescriptionsRosemount PRIMARY_VALUE_RANGE RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Rosemount TroubleshootingOverview Reference ManualParameters and Descriptions RosemountReference Manual 00809-0200-4101,Rev AA JulyFLANGE_MTL RosemountReference Manual REM_SEAL_FILL RosemountReference Manual Simulate_STATE RosemountReference Manual Reference Manual Block ErrorsRosemount 00809-0200-4101,Rev AA July00809-0200-4101,Rev AA July RosemountReference Manual Mode will not leave RosemountReference Manual C-14 RosemountReference Manual Reference Manual IndexRosemount 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Index-4 RosemountReference Manual 00809-0200-4101,Rev AA July NOTES RosemountReference Manual Rosemount Reference ManualPage Reference Manual Rosemount¢00809-0100-4801V¤