GENERAL

Rosemount 2051

Reference Manual

00809-0200-4101, Rev AA July 2008

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electrical shock can result in death or serious injury.

 

 

• Avoid contact with the leads and terminals.

 

 

Process leaks could result in death or serious injury.

 

 

• Install and tighten all four flange bolts before applying pressure.

 

 

• Do not attempt to loosen or remove flange bolts while the transmitter is

 

 

in service.

 

 

Replacement equipment or spare parts not approved by Emerson Process

 

 

Management for use as spare parts could reduce the pressure retaining

 

 

capabilities of the transmitter and may render the instrument dangerous.

 

 

• Use only bolts supplied or sold by Emerson Process Management as spare

 

 

parts.

 

 

• Refer to page A-25 for a complete list of spare parts.

 

 

Improper assembly of manifolds to traditional flange can damage sensor module.

 

 

• For safe assembly of manifold to traditional flange, bolts must break back

 

 

plane of flange web (i.e., bolt hole) but must not contact sensor module

 

 

housing.

GENERAL

 

 

 

 

Measurement accuracy depends upon proper installation of the transmitter

CONSIDERATIONS

and impulse piping. Mount the transmitter close to the process and use a

 

minimum of piping to achieve best accuracy. Also, consider the need for easy

 

access, personnel safety, practical field calibration, and a suitable transmitter

 

environment. Install the transmitter to minimize vibration, shock, and

 

temperature fluctuation.

 

 

 

 

 

 

IMPORTANT

 

Install the enclosed pipe plug (found in the box) in unused conduit opening

 

with a minimum of five threads engaged to comply with explosion-proof

 

requirements.

 

For material compatibility considerations, see document number

 

00816-0100-3045 on www.emersonprocess.com/rosemount.

MECHANICAL

 

 

 

 

 

 

 

 

NOTE

CONSIDERATIONS

For steam service or for applications with process temperatures greater than

 

the limits of the transmitter, do not blow down impulse piping through the

 

transmitter. Flush lines with the blocking valves closed and refill lines with

 

water before resuming measurement.

 

 

 

 

 

 

 

 

 

 

 

NOTE

 

When the transmitter is mounted on its side, position the Coplanar flange to

 

ensure proper venting or draining. Mount the flange as shown in Figure 2-8 on

 

page 2-16, keeping drain/vent connections on the bottom for gas service and

 

on the top for liquid service.

ENVIRONMENTAL

 

 

 

 

Best practice is to mount the transmitter in an environment that has minimal

CONSIDERATIONS

ambient temperature change. The transmitter electronics temperature

 

operating limits are –40 to 185 °F (–40 to 85 °C). Refer to Appendix A:

 

Reference Data that lists the sensing element operating limits. Mount the

 

transmitter so that it is not susceptible to vibration and mechanical shock and

 

does not have external contact with corrosive materials.

2-2

Image 12
Contents with FOUNDATION Fieldbus Protocol Reference ManualRosemount 2051 Pressure Transmitter Page Rosemount 2051 Pressure Transmitter with FOUNDATION FieldbusRosemount Reference ManualPage Table of Contents SECTION 1 Introduction SECTION 2 InstallationSECTION 3 Configuration RosemountSECTION Operation and Maintenance SECTION 5 TroubleshootingAPPENDIX A Reference Data RosemountAPPENDIX B Approval Information APPENDIX C Block InformationRosemount Reference ManualRosemount Reference ManualTOC-4 USING THIS MANUAL SERVICE SUPPORT SectionIntroduction RosemountMODELS COVERED RosemountReference Manual Installation OVERVIEW SAFETY MESSAGES WarningsSection RosemountGENERAL CONSIDERATIONSMECHANICAL ENVIRONMENTALINSTALLATION PROCEDURES Dimensional Drawings2051C Coplanar Flange Dimensional Drawing RosemountCoplanar Flange Mounting Configurations with RosemountReference Manual 00809-0200-4101,Rev AA2051C Coplanar with Traditional Flange RosemountReference Manual Traditional Flange Mounting Configurations with Optional Brackets for 2-in.Pipe or Panel MountingRosemount Reference Manual2051T Dimensional Drawings 2051T with Rosemount 306 Integral ManifoldRosemount Reference ManualRosemount Reference ManualPipe Mounting Panel Mounting2051L Liquid Level RosemountReference Manual Mount the Transmitter RosemountReference Manual Rosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference Manual00809-0200-4101,Rev AA July Figure 2-6.Traditional Flange Bolt Configurations RosemountReference Manual 00809-0200-4101,Rev AA JulyImpulse Piping RosemountReference Manual Rosemount Reference ManualFlow Process Connections RosemountReference Manual Rosemount Reference Manual00809-0200-4101,Rev AA July Housing Rotation RosemountReference Manual LCD Display TaggingRosemount Reference ManualConduit Installation ELECTRICALRosemount Reference ManualWiring RosemountReference Manual Transient Protection Terminal Block RosemountReference Manual JumpersSecurity RosemountReference Manual Grounding RosemountReference Manual Figure 2-17.External Ground Assembly External Ground AssemblyRosemount Reference ManualHAZARDOUS LOCATIONS CERTIFICATIONS ROSEMOUNT 305, 306 AND 304 MANIFOLDSRosemount Reference ManualRosemount 305 Integral Manifold Installation Procedure Rosemount 306 IntegralManifold Installation Procedure Rosemount Conventional Manifold Installation ProcedureIntegral Manifold Operation RosemountReference Manual Rosemount Reference Manual00809-0200-4101,Rev AA July LIQUID LEVEL MEASUREMENT Open Vessels Closed VesselsRosemount Reference ManualRosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference ManualConfiguration OVERVIEW SAFETY MESSAGES WarningsSection RosemountDEVICE CAPABILITIES Link Active Scheduler CapabilitiesGENERAL BLOCK INFORMATION Modes RosemountRESOURCE BLOCK FEATURES and FEATURES SEL SimulationRosemount Reference ManualMAX_NOTIFY RosemountReference Manual Configure the AI block ANALOG INPUT AI FUNCTION BLOCKRosemount Reference ManualConfiguration Examples RosemountReference Manual Rosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference Manual00809-0200-4101,Rev AA July Filtering Low CutoffRosemount Reference ManualProcess Alarms Alarm Priority Status OptionsRosemount Reference ManualAdvanced Features LCD BLOCK RosemountReference Manual Rosemount Reference Manual00809-0200-4101,Rev AA July Section 4 Operation and Maintenance OVERVIEW SAFETY MESSAGES WarningsRosemount Reference ManualSTATUS Master Reset Method Simulation RosemountReference Manual CALIBRATION Sensor Calibration Upper and Lower Trim MethodsRosemount Reference ManualSensor Calibration, Zero Trim Method Factory Calibration MethodRosemount Reference ManualSection 5 Troubleshooting OVERVIEW SAFETY MESSAGES WarningsRosemount Reference ManualTROUBLESHOOTING GUIDES RosemountReference Manual 00809-0200-4101,Rev AA JulyFigure 5-2.Problems with communications flowchart RosemountReference Manual 00809-0200-4101,Rev AA JulyTable 5-1.Troubleshooting guide RosemountReference Manual 00809-0200-4101,Rev AA JulyRESOURCE BLOCK RosemountReference Manual SENSOR TRANSDUCER BLOCK RosemountReference Manual LCD TRANSDUCER BLOCK RosemountReference Manual ANALOG INPUT AI FUNCTION BLOCK1.Put Resource block into OOS Out of Service RosemountReference Manual 00809-0200-4101,Rev AA JulyDISASSEMBLY PROCEDURES Remove from Service Remove Terminal BlockRosemount Reference ManualRemove the Electronics Board RosemountReference Manual REASSEMBLY PROCEDURES Attach the Electronics Board Install the Terminal BlockReassemble the 2051C Process Flange RosemountInstall the Drain/Vent Valve RosemountReference Manual PERFORMANCE SPECIFICATIONS Conformance To Specification ±3σ SigmaAppendix A Reference DataLong Term Stability Dynamic PerformanceLine Pressure Effect per 1000 psi 6,9 MPa RosemountVibration Effect Power Supply Effect Ambient Temperature Effect per 50F 28CMounting Position Effects Electromagnetic Compatibility EMCFUNCTIONAL SPECIFICATIONS Range and Sensor Limits ServiceProtocols RosemountRosemount Reference Manual00809-0200-4101,Rev AA July Overpressure Limits RosemountReference Manual Static Pressure Limit Burst Pressure Limits Temperature LimitsRosemount Reference ManualHumidity Limits Volumetric Displacement Damping Failure Mode AlarmRosemount Reference ManualPHYSICAL SPECIFICATIONS Electrical Connections Process Connections 2051C Process Wetted Parts2051T Process Wetted Parts 2051L Process Wetted PartsNon-WettedParts for 2051C/T/L RosemountReference Manual Shipping Weights Table A-4.Transmitter Weights without OptionsTable A-5.2051L Weights without Options Table A-6.Transmitter Options WeightsORDERING INFORMATION RosemountReference Manual Rosemount Reference ManualAlternate Process Connection: Flange2 Rosemount Reference ManualCSA FISCO Intrinsically Safe Rosemount Reference ManualA-15 Rosemount Reference ManualGGage AAbsolute Rosemount Reference ManualFM Intrinsically Safe, Division Rosemount Reference ManualSpecial Certifications Q4 Calibration Certificate Prior-usecertificate of FMEDA dataRosemount Reference Manual4 -300to 300 psi/3 psi -20,7to 20,7 bar/0,2 bar Rosemount Reference ManualSyltherm XLT ATEX Flameproof, Intrinsic Safety, Type n, Dust RosemountReference Manual OPTIONS RosemountReference Manual Rosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference Manual00809-0200-4101,Rev AA July SPARE PARTS RosemountReference Manual LCD Display, FOUNDATION fieldbusRosemount Reference ManualNickel-platedcarbon steel Rosemount Reference ManualGage Flange and Adapter Bolt Kit Set of Rosemount Reference ManualA-28 OVERVIEW SAFETY MESSAGES Appendix B Approval InformationWarnings Approved Manufacturing LocationsEuropean Directive Information FIELDBUS PROTOCOLHazardous Locations Certifications RosemountRosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference Manual00809-0200-4101,Rev AA July APPROVAL DRAWINGS Factory Mutual FM RosemountReference Manual Rosemount Reference ManualRosemount Reference ManualB-10 Rosemount Reference ManualB-11 Rosemount Reference ManualB-12 Rosemount Reference ManualB-13 Rosemount Reference ManualB-14 Rosemount Reference ManualB-15 Rosemount Reference ManualB-16 Rosemount Reference ManualB-17 Rosemount Reference ManualB-18 Rosemount Reference ManualB-19 Rosemount Reference ManualB-20 Canadian Standards Association CSA RosemountReference Manual B-21Rosemount Reference ManualB-22 Rosemount Reference ManualB-23 Rosemount Reference ManualB-24 Rosemount Reference ManualB-25 Rosemount Reference ManualB-26 Rosemount Reference ManualB-27 Rosemount Reference ManualB-28 Rosemount Reference ManualB-29 Rosemount Reference ManualB-30 Appendix C Block InformationTRANSDUCER BLOCK Overview RosemountParameters and Descriptions RosemountReference Manual Rosemount Reference ManualPRIMARY_VALUE_RANGE Rosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference Manual00809-0200-4101,Rev AA July Troubleshooting OverviewRosemount Reference ManualRosemount Reference ManualParameters and Descriptions 00809-0200-4101,Rev AA JulyRosemount Reference ManualFLANGE_MTL Rosemount Reference ManualREM_SEAL_FILL Rosemount Reference ManualSimulate_STATE Block Errors RosemountReference Manual 00809-0200-4101,Rev AA JulyRosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference ManualMode will not leave Rosemount Reference ManualC-14 Index RosemountReference Manual Rosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference ManualIndex-4 Rosemount Reference Manual00809-0200-4101,Rev AA July NOTES Rosemount Reference ManualPage Rosemount ¢00809-0100-4801V¤Reference Manual