Page 133
PRIMARY_VALUE_RANGE

Reference Manual

00809-0200-4101, Rev AA July 2008

Rosemount 2051

 

Index

 

 

 

Parameter

Number

Description

 

 

 

PRIMARY_VALUE_RANGE

15

The high and low range limit values, the engineering unit code, and the number of

 

 

digits to the right of the decimal point to be used to display the final value.

 

 

Valid engineering units are the following:

 

 

1130

= Pa

 

 

1133

= kPa

 

 

1137

= bar

 

 

1138

= mbar

 

 

1139

= torr

 

 

1140

= atm

 

 

1141

= psi

 

 

1144

= g/cm2

 

 

1145

= kg/cm2

 

 

1148

= inH2O @ 68 °F

 

 

1151

= mmH2O @ 68 °F

 

 

1154

= ftH2O @ 68 °F

 

 

1156

= inHg @ 0 °C

 

 

1158

= mmHg @ 0 °C

 

 

 

PRIMARY_VALUE_TYPE

13

Type of measurement represented by the primary value.

 

 

107 = Differential pressure

 

 

108 = Gage pressure

 

 

109 = Absolute pressure

SECONDARY_VALUE

29

The secondary value, related to the sensor.

 

 

 

SECONDARY_VALUE_UNIT

30

Engineering units to be used with SECONDARY_VALUE.

 

 

1001 °C

 

 

1002 °F

SENSOR_CAL_DATE

25

The last date on which the calibration was performed.This is intended to reflect the

 

 

calibration of that part of the sensor that is usually wetted by the process.

 

 

 

SENSOR_CAL_LOC

24

The last location of the sensor calibration. This describes the physical location at

 

 

which the calibration was performed.

SENSOR_CAL_METHOD

23

The last method used to calibrate the device.

 

 

103 = factory trim standard

 

 

104 = user trim standard

 

 

 

SENSOR_CAL_TYPE

35

The type of last sensor calibration.

 

 

0

= Differential pressure

 

 

1

= Gage pressures

 

 

2

= Absolute pressure

 

 

252 = Unknown

SENSOR_CAL_WHO

26

The name of the person responsible for the last sensor calibration.

 

 

 

SENSOR_FILL_FLUID

28

Type of fill fluid used in sensor.

 

 

0

= Undefined

 

 

1

= Silicone

 

 

2

= Inert

 

 

3

= Undefined

 

 

7

- Neobee

 

 

251 = "None"

 

 

252 = "Unknown"

 

 

253 = "Special"

SENSOR_ISOLATOR_MTL

27

Defines the construction material for the isolating diaphragms.

 

 

2

= 316 Stainless Steel

 

 

3

= Hastelloy C

 

 

4

= Monel

 

 

5

= Tantalum

 

 

253 = "Special"

 

 

 

SENSOR_RANGE

21

The high and low range limit values, the engineering units code, and the number of

 

 

digits to the right of the decimal point for the sensor.

SENSOR_SN

22

Serial number of the sensor.

C-3

Image 133
Contents Reference Manual with FOUNDATION Fieldbus ProtocolRosemount 2051 Pressure Transmitter Page Transmitter with FOUNDATION Fieldbus Rosemount 2051 PressureRosemount Reference ManualPage SECTION 1 Introduction SECTION 2 Installation Table of ContentsSECTION 3 Configuration RosemountSECTION 5 Troubleshooting SECTION Operation and MaintenanceAPPENDIX A Reference Data RosemountAPPENDIX C Block Information APPENDIX B Approval InformationRosemount Reference ManualReference Manual RosemountTOC-4 Section USING THIS MANUAL SERVICE SUPPORTIntroduction RosemountRosemount MODELS COVEREDReference Manual OVERVIEW SAFETY MESSAGES Warnings InstallationSection RosemountCONSIDERATIONS GENERALMECHANICAL ENVIRONMENTALDimensional Drawings INSTALLATION PROCEDURES2051C Coplanar Flange Dimensional Drawing RosemountRosemount Coplanar Flange Mounting Configurations withReference Manual 00809-0200-4101,Rev AARosemount 2051C Coplanar with Traditional FlangeReference Manual Optional Brackets for 2-in.Pipe or Panel Mounting Traditional Flange Mounting Configurations withRosemount Reference Manual2051T with Rosemount 306 Integral Manifold 2051T Dimensional DrawingsRosemount Reference ManualReference Manual RosemountPipe Mounting Panel MountingRosemount 2051L Liquid LevelReference Manual Rosemount Mount the TransmitterReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Rosemount Figure 2-6.Traditional Flange Bolt ConfigurationsReference Manual 00809-0200-4101,Rev AA JulyRosemount Impulse PipingReference Manual Reference Manual RosemountFlow Rosemount Process ConnectionsReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July Rosemount Housing RotationReference Manual Tagging LCD DisplayRosemount Reference ManualELECTRICAL Conduit InstallationRosemount Reference ManualRosemount WiringReference Manual Rosemount Transient Protection Terminal BlockReference Manual Rosemount JumpersSecurityReference Manual Rosemount GroundingReference Manual External Ground Assembly Figure 2-17.External Ground AssemblyRosemount Reference ManualROSEMOUNT 305, 306 AND 304 MANIFOLDS HAZARDOUS LOCATIONS CERTIFICATIONSRosemount Reference ManualProcedure Rosemount 306 Integral Rosemount 305 Integral Manifold InstallationManifold Installation Procedure Rosemount Conventional Manifold Installation ProcedureRosemount Integral Manifold OperationReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July Open Vessels Closed Vessels LIQUID LEVEL MEASUREMENTRosemount Reference ManualReference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual RosemountOVERVIEW SAFETY MESSAGES Warnings ConfigurationSection RosemountCapabilities DEVICE CAPABILITIES Link Active SchedulerGENERAL BLOCK INFORMATION Modes RosemountSimulation RESOURCE BLOCK FEATURES and FEATURES SELRosemount Reference ManualRosemount MAX_NOTIFYReference Manual ANALOG INPUT AI FUNCTION BLOCK Configure the AI blockRosemount Reference ManualRosemount Configuration ExamplesReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Low Cutoff FilteringRosemount Reference ManualStatus Options Process Alarms Alarm PriorityRosemount Reference ManualRosemount Advanced Features LCD BLOCKReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July OVERVIEW SAFETY MESSAGES Warnings Section 4 Operation and MaintenanceRosemount Reference ManualRosemount STATUS Master Reset Method SimulationReference Manual Upper and Lower Trim Methods CALIBRATION Sensor CalibrationRosemount Reference ManualFactory Calibration Method Sensor Calibration, Zero Trim MethodRosemount Reference ManualOVERVIEW SAFETY MESSAGES Warnings Section 5 TroubleshootingRosemount Reference ManualRosemount TROUBLESHOOTING GUIDESReference Manual 00809-0200-4101,Rev AA JulyRosemount Figure 5-2.Problems with communications flowchartReference Manual 00809-0200-4101,Rev AA JulyRosemount Table 5-1.Troubleshooting guideReference Manual 00809-0200-4101,Rev AA JulyRosemount RESOURCE BLOCKReference Manual Rosemount SENSOR TRANSDUCER BLOCKReference Manual Rosemount LCD TRANSDUCER BLOCKReference Manual ANALOG INPUT AI FUNCTION BLOCKRosemount 1.Put Resource block into OOS Out of ServiceReference Manual 00809-0200-4101,Rev AA JulyRemove Terminal Block DISASSEMBLY PROCEDURES Remove from ServiceRosemount Reference ManualRosemount Remove the Electronics BoardReference Manual Electronics Board Install the Terminal Block REASSEMBLY PROCEDURES Attach theReassemble the 2051C Process Flange RosemountRosemount Install the Drain/Vent ValveReference Manual Conformance To Specification ±3σ Sigma PERFORMANCE SPECIFICATIONSAppendix A Reference DataDynamic Performance Long Term StabilityLine Pressure Effect per 1000 psi 6,9 MPa RosemountAmbient Temperature Effect per 50F 28C Vibration Effect Power Supply EffectMounting Position Effects Electromagnetic Compatibility EMCService FUNCTIONAL SPECIFICATIONS Range and Sensor LimitsProtocols RosemountReference Manual Rosemount00809-0200-4101,Rev AA July Rosemount Overpressure LimitsReference Manual Temperature Limits Static Pressure Limit Burst Pressure LimitsRosemount Reference ManualFailure Mode Alarm Humidity Limits Volumetric Displacement DampingRosemount Reference ManualProcess Connections 2051C Process Wetted Parts PHYSICAL SPECIFICATIONS Electrical Connections2051T Process Wetted Parts 2051L Process Wetted PartsRosemount Non-WettedParts for 2051C/T/LReference Manual Table A-4.Transmitter Weights without Options Shipping WeightsTable A-5.2051L Weights without Options Table A-6.Transmitter Options WeightsRosemount ORDERING INFORMATIONReference Manual Reference Manual RosemountAlternate Process Connection: Flange2 Reference Manual RosemountCSA FISCO Intrinsically Safe Reference Manual RosemountA-15 Reference Manual RosemountGGage AAbsolute Reference Manual RosemountFM Intrinsically Safe, Division Reference Manual RosemountSpecial Certifications Q4 Calibration Certificate Prior-usecertificate of FMEDA dataReference Manual Rosemount4 -300to 300 psi/3 psi -20,7to 20,7 bar/0,2 bar Reference Manual RosemountSyltherm XLT Rosemount ATEX Flameproof, Intrinsic Safety, Type n, DustReference Manual Rosemount OPTIONSReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Rosemount SPARE PARTSReference Manual LCD Display, FOUNDATION fieldbusReference Manual RosemountNickel-platedcarbon steel Reference Manual RosemountGage Flange and Adapter Bolt Kit Set of Reference Manual RosemountA-28 Appendix B Approval Information OVERVIEW SAFETY MESSAGESWarnings Approved Manufacturing LocationsFIELDBUS PROTOCOL European Directive InformationHazardous Locations Certifications RosemountReference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Rosemount APPROVAL DRAWINGS Factory Mutual FMReference Manual Reference Manual RosemountReference Manual RosemountB-10 Reference Manual RosemountB-11 Reference Manual RosemountB-12 Reference Manual RosemountB-13 Reference Manual RosemountB-14 Reference Manual RosemountB-15 Reference Manual RosemountB-16 Reference Manual RosemountB-17 Reference Manual RosemountB-18 Reference Manual RosemountB-19 Reference Manual RosemountB-20 Rosemount Canadian Standards Association CSAReference Manual B-21Reference Manual RosemountB-22 Reference Manual RosemountB-23 Reference Manual RosemountB-24 Reference Manual RosemountB-25 Reference Manual RosemountB-26 Reference Manual RosemountB-27 Reference Manual RosemountB-28 Reference Manual RosemountB-29 Reference Manual RosemountB-30 Block Information Appendix CTRANSDUCER BLOCK Overview RosemountRosemount Parameters and DescriptionsReference Manual Reference Manual RosemountPRIMARY_VALUE_RANGE Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Overview TroubleshootingRosemount Reference ManualReference Manual RosemountParameters and Descriptions 00809-0200-4101,Rev AA JulyReference Manual RosemountFLANGE_MTL Reference Manual RosemountREM_SEAL_FILL Reference Manual RosemountSimulate_STATE Rosemount Block ErrorsReference Manual 00809-0200-4101,Rev AA JulyReference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual RosemountMode will not leave Reference Manual RosemountC-14 Rosemount IndexReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual RosemountIndex-4 Reference Manual Rosemount00809-0200-4101,Rev AA July NOTES Reference Manual RosemountPage ¢00809-0100-4801V¤ RosemountReference Manual