ELECTRICAL

Reference Manual

00809-0200-4101, Rev AA July 2008

Rosemount 2051

ELECTRICAL

NOTE

CONSIDERATIONS

Make sure all electrical installation is in accordance with national and local code

 

requirements.

Conduit Installation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If all connections are not sealed, excess moisture accumulation can damage the transmitter. Make sure to mount the transmitter with the electrical housing positioned downward for drainage. To avoid moisture accumulation in the housing, install wiring with a drip loop, and ensure the bottom of the drip loop is mounted lower than the conduit connections or the transmitter housing.

Figure 2-12. Conduit Installation Diagrams.

Possible

Conduit Line

Positions

Sealing

Compound

CORRECT

Recommended conduit connections are shown in Figure 2-12.

Conduit

Lines

Sealing

Compound

Possible

Conduit Line

Positions

CORRECTINCORRECT

2-21

Image 31
Contents Reference Manual with FOUNDATION Fieldbus ProtocolRosemount 2051 Pressure Transmitter Page Reference Manual Rosemount 2051 PressureTransmitter with FOUNDATION Fieldbus RosemountPage Rosemount Table of ContentsSECTION 1 Introduction SECTION 2 Installation SECTION 3 ConfigurationRosemount SECTION Operation and MaintenanceSECTION 5 Troubleshooting APPENDIX A Reference DataReference Manual APPENDIX B Approval InformationAPPENDIX C Block Information RosemountReference Manual RosemountTOC-4 Rosemount USING THIS MANUAL SERVICE SUPPORTSection IntroductionRosemount MODELS COVEREDReference Manual Rosemount InstallationOVERVIEW SAFETY MESSAGES Warnings SectionENVIRONMENTAL GENERALCONSIDERATIONS MECHANICALRosemount INSTALLATION PROCEDURESDimensional Drawings 2051C Coplanar Flange Dimensional Drawing00809-0200-4101,Rev AA Coplanar Flange Mounting Configurations withRosemount Reference ManualRosemount 2051C Coplanar with Traditional FlangeReference Manual Reference Manual Traditional Flange Mounting Configurations withOptional Brackets for 2-in.Pipe or Panel Mounting RosemountReference Manual 2051T Dimensional Drawings2051T with Rosemount 306 Integral Manifold RosemountPanel Mounting RosemountReference Manual Pipe MountingRosemount 2051L Liquid LevelReference Manual Rosemount Mount the TransmitterReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July 00809-0200-4101,Rev AA July Figure 2-6.Traditional Flange Bolt ConfigurationsRosemount Reference ManualRosemount Impulse PipingReference Manual Reference Manual RosemountFlow Rosemount Process ConnectionsReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July Rosemount Housing RotationReference Manual Reference Manual LCD DisplayTagging RosemountReference Manual Conduit InstallationELECTRICAL RosemountRosemount WiringReference Manual Rosemount Transient Protection Terminal BlockReference Manual Rosemount JumpersSecurityReference Manual Rosemount GroundingReference Manual Reference Manual Figure 2-17.External Ground AssemblyExternal Ground Assembly RosemountReference Manual HAZARDOUS LOCATIONS CERTIFICATIONSROSEMOUNT 305, 306 AND 304 MANIFOLDS RosemountConventional Manifold Installation Procedure Rosemount 305 Integral Manifold InstallationProcedure Rosemount 306 Integral Manifold Installation Procedure RosemountRosemount Integral Manifold OperationReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual LIQUID LEVEL MEASUREMENTOpen Vessels Closed Vessels RosemountReference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual RosemountRosemount ConfigurationOVERVIEW SAFETY MESSAGES Warnings SectionRosemount DEVICE CAPABILITIES Link Active SchedulerCapabilities GENERAL BLOCK INFORMATION ModesReference Manual RESOURCE BLOCK FEATURES and FEATURES SELSimulation RosemountRosemount MAX_NOTIFYReference Manual Reference Manual Configure the AI blockANALOG INPUT AI FUNCTION BLOCK RosemountRosemount Configuration ExamplesReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual FilteringLow Cutoff RosemountReference Manual Process Alarms Alarm PriorityStatus Options RosemountRosemount Advanced Features LCD BLOCKReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Section 4 Operation and MaintenanceOVERVIEW SAFETY MESSAGES Warnings RosemountRosemount STATUS Master Reset Method SimulationReference Manual Reference Manual CALIBRATION Sensor CalibrationUpper and Lower Trim Methods RosemountReference Manual Sensor Calibration, Zero Trim MethodFactory Calibration Method RosemountReference Manual Section 5 TroubleshootingOVERVIEW SAFETY MESSAGES Warnings Rosemount00809-0200-4101,Rev AA July TROUBLESHOOTING GUIDESRosemount Reference Manual00809-0200-4101,Rev AA July Figure 5-2.Problems with communications flowchartRosemount Reference Manual00809-0200-4101,Rev AA July Table 5-1.Troubleshooting guideRosemount Reference ManualRosemount RESOURCE BLOCKReference Manual Rosemount SENSOR TRANSDUCER BLOCKReference Manual ANALOG INPUT AI FUNCTION BLOCK LCD TRANSDUCER BLOCKRosemount Reference Manual00809-0200-4101,Rev AA July 1.Put Resource block into OOS Out of ServiceRosemount Reference ManualReference Manual DISASSEMBLY PROCEDURES Remove from ServiceRemove Terminal Block RosemountRosemount Remove the Electronics BoardReference Manual Rosemount REASSEMBLY PROCEDURES Attach theElectronics Board Install the Terminal Block Reassemble the 2051C Process FlangeRosemount Install the Drain/Vent ValveReference Manual Reference Data PERFORMANCE SPECIFICATIONSConformance To Specification ±3σ Sigma Appendix ARosemount Long Term StabilityDynamic Performance Line Pressure Effect per 1000 psi 6,9 MPaElectromagnetic Compatibility EMC Vibration Effect Power Supply EffectAmbient Temperature Effect per 50F 28C Mounting Position EffectsRosemount FUNCTIONAL SPECIFICATIONS Range and Sensor LimitsService ProtocolsReference Manual Rosemount00809-0200-4101,Rev AA July Rosemount Overpressure LimitsReference Manual Reference Manual Static Pressure Limit Burst Pressure LimitsTemperature Limits RosemountReference Manual Humidity Limits Volumetric Displacement DampingFailure Mode Alarm Rosemount2051L Process Wetted Parts PHYSICAL SPECIFICATIONS Electrical ConnectionsProcess Connections 2051C Process Wetted Parts 2051T Process Wetted PartsRosemount Non-WettedParts for 2051C/T/LReference Manual Table A-6.Transmitter Options Weights Shipping WeightsTable A-4.Transmitter Weights without Options Table A-5.2051L Weights without OptionsRosemount ORDERING INFORMATIONReference Manual Reference Manual RosemountAlternate Process Connection: Flange2 Reference Manual RosemountCSA FISCO Intrinsically Safe Reference Manual RosemountA-15 Reference Manual RosemountGGage AAbsolute Reference Manual RosemountFM Intrinsically Safe, Division Prior-usecertificate of FMEDA data RosemountReference Manual Special Certifications Q4 Calibration CertificateReference Manual Rosemount4 -300to 300 psi/3 psi -20,7to 20,7 bar/0,2 bar Reference Manual RosemountSyltherm XLT Rosemount ATEX Flameproof, Intrinsic Safety, Type n, DustReference Manual Rosemount OPTIONSReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July LCD Display, FOUNDATION fieldbus SPARE PARTSRosemount Reference ManualReference Manual RosemountNickel-platedcarbon steel Reference Manual RosemountGage Flange and Adapter Bolt Kit Set of Reference Manual RosemountA-28 Approved Manufacturing Locations OVERVIEW SAFETY MESSAGESAppendix B Approval Information WarningsRosemount European Directive InformationFIELDBUS PROTOCOL Hazardous Locations CertificationsReference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Rosemount APPROVAL DRAWINGS Factory Mutual FMReference Manual Reference Manual RosemountReference Manual RosemountB-10 Reference Manual RosemountB-11 Reference Manual RosemountB-12 Reference Manual RosemountB-13 Reference Manual RosemountB-14 Reference Manual RosemountB-15 Reference Manual RosemountB-16 Reference Manual RosemountB-17 Reference Manual RosemountB-18 Reference Manual RosemountB-19 Reference Manual RosemountB-20 B-21 Canadian Standards Association CSARosemount Reference ManualReference Manual RosemountB-22 Reference Manual RosemountB-23 Reference Manual RosemountB-24 Reference Manual RosemountB-25 Reference Manual RosemountB-26 Reference Manual RosemountB-27 Reference Manual RosemountB-28 Reference Manual RosemountB-29 Reference Manual RosemountB-30 Rosemount Appendix CBlock Information TRANSDUCER BLOCK OverviewRosemount Parameters and DescriptionsReference Manual Reference Manual RosemountPRIMARY_VALUE_RANGE Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual TroubleshootingOverview Rosemount00809-0200-4101,Rev AA July RosemountReference Manual Parameters and DescriptionsReference Manual RosemountFLANGE_MTL Reference Manual RosemountREM_SEAL_FILL Reference Manual RosemountSimulate_STATE 00809-0200-4101,Rev AA July Block ErrorsRosemount Reference ManualReference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual RosemountMode will not leave Reference Manual RosemountC-14 Rosemount IndexReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual RosemountIndex-4 Reference Manual Rosemount00809-0200-4101,Rev AA July NOTES Reference Manual RosemountPage ¢00809-0100-4801V¤ RosemountReference Manual