Page 140
Simulate_STATE

Rosemount 2051

Reference Manual

00809-0200-4101, Rev AA July 2008

 

Index

 

Parameter

Number

Description

 

 

 

Simulate_STATE

66

The state of the simulate jumper.

 

 

0 = Uninitialized

 

 

1 = Jumper/ switch off, simulation not allowed

 

 

2 = Jumper/ switch on, simulation not allowed (need to cycle jumper/ switch)

 

 

 

simulate_IO

64

Status of simulate jumper/switch.

RB_SFTWR_REV_ALL

51

The string will contain the following fields:

 

 

Major rev: 1-3 characters, decimal number 0-255

 

 

Minor rev: 1-3 characters, decimal number 0-255

 

 

Build rev: 1-5 characters, decimal number 0-255

 

 

Time of build: 8 characters, xx:xx:xx, military time

 

 

Day of week of build: 3 characters, Sun, Mon,...

 

 

Month of build: 3 characters, Jan, Feb...

 

 

Day of month of build: 1-2 characters, decimal number 1-31

 

 

Year of build: 4 characters, decimal

 

 

Builder: 7 characters, login name of builder

 

 

 

RB_SFTWR_REV_BUILD

50

Build of software that the resource block was created with.

RB_SFTWR_REV_MAJOR

48

Major revision of software that the resource block was created with.

 

 

 

RB_SFTWR_REV_MINIOR

49

Minor revision of software that the resource block was created with.

start_with_defaults

63

0 = Uninitialized

 

 

1 = do not power-up with NV defaults

 

 

2 = power-up with default node address

 

 

3 = power-up with default pd_tag and node address

 

 

4 = power-up with default data for the entire communications stack (no application data)

 

 

 

STRATEGY

03

The strategy field can be used to identify grouping of blocks.

ST_REV

01

The revision level of the static data associated with the function block.

 

 

 

summary_status

56

An enumerated value of repair analysis.

TAG_DESC

02

The user description of the intended application of the block.

 

 

 

TEST_RW

08

Read/write test parameter - used only for conformance testing.

UPDATE_EVT

35

This alert is generated by any change to the static data.

 

 

 

WRITE_ALM

40

This alert is generated if the write lock parameter is cleared.

WRITE_LOCK

34

If set, no writes from anywhere are allowed, except to clear WRITE_LOCK. Block inputs

 

 

will continue to be updated.

 

 

 

WRITE_PRI

39

Priority of the alarm generated by clearing the write lock.

 

 

 

C-10

Image 140
Contents Rosemount 2051 Pressure Transmitter with FOUNDATION Fieldbus ProtocolReference Manual Page Rosemount 2051 Pressure Transmitter with FOUNDATION FieldbusRosemount Reference ManualPage Table of Contents SECTION 1 Introduction SECTION 2 InstallationSECTION 3 Configuration RosemountSECTION Operation and Maintenance SECTION 5 TroubleshootingAPPENDIX A Reference Data RosemountAPPENDIX B Approval Information APPENDIX C Block InformationRosemount Reference ManualTOC-4 RosemountReference Manual USING THIS MANUAL SERVICE SUPPORT SectionIntroduction RosemountReference Manual MODELS COVEREDRosemount Installation OVERVIEW SAFETY MESSAGES WarningsSection RosemountGENERAL CONSIDERATIONSMECHANICAL ENVIRONMENTALINSTALLATION PROCEDURES Dimensional Drawings2051C Coplanar Flange Dimensional Drawing RosemountCoplanar Flange Mounting Configurations with RosemountReference Manual 00809-0200-4101,Rev AAReference Manual 2051C Coplanar with Traditional FlangeRosemount Traditional Flange Mounting Configurations with Optional Brackets for 2-in.Pipe or Panel MountingRosemount Reference Manual2051T Dimensional Drawings 2051T with Rosemount 306 Integral ManifoldRosemount Reference ManualRosemount Reference ManualPipe Mounting Panel MountingReference Manual 2051L Liquid LevelRosemount Reference Manual Mount the TransmitterRosemount 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Figure 2-6.Traditional Flange Bolt Configurations RosemountReference Manual 00809-0200-4101,Rev AA JulyReference Manual Impulse PipingRosemount Flow RosemountReference Manual Reference Manual Process ConnectionsRosemount 00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual Housing RotationRosemount LCD Display TaggingRosemount Reference ManualConduit Installation ELECTRICALRosemount Reference ManualReference Manual WiringRosemount Reference Manual Transient Protection Terminal BlockRosemount Reference Manual JumpersSecurityRosemount Reference Manual GroundingRosemount Figure 2-17.External Ground Assembly External Ground AssemblyRosemount Reference ManualHAZARDOUS LOCATIONS CERTIFICATIONS ROSEMOUNT 305, 306 AND 304 MANIFOLDSRosemount Reference ManualRosemount 305 Integral Manifold Installation Procedure Rosemount 306 IntegralManifold Installation Procedure Rosemount Conventional Manifold Installation ProcedureReference Manual Integral Manifold OperationRosemount 00809-0200-4101,Rev AA July RosemountReference Manual LIQUID LEVEL MEASUREMENT Open Vessels Closed VesselsRosemount Reference Manual00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Rosemount Reference ManualConfiguration OVERVIEW SAFETY MESSAGES WarningsSection RosemountDEVICE CAPABILITIES Link Active Scheduler CapabilitiesGENERAL BLOCK INFORMATION Modes RosemountRESOURCE BLOCK FEATURES and FEATURES SEL SimulationRosemount Reference ManualReference Manual MAX_NOTIFYRosemount Configure the AI block ANALOG INPUT AI FUNCTION BLOCKRosemount Reference ManualReference Manual Configuration ExamplesRosemount 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Filtering Low CutoffRosemount Reference ManualProcess Alarms Alarm Priority Status OptionsRosemount Reference ManualReference Manual Advanced Features LCD BLOCKRosemount 00809-0200-4101,Rev AA July RosemountReference Manual Section 4 Operation and Maintenance OVERVIEW SAFETY MESSAGES WarningsRosemount Reference ManualReference Manual STATUS Master Reset Method SimulationRosemount CALIBRATION Sensor Calibration Upper and Lower Trim MethodsRosemount Reference ManualSensor Calibration, Zero Trim Method Factory Calibration MethodRosemount Reference ManualSection 5 Troubleshooting OVERVIEW SAFETY MESSAGES WarningsRosemount Reference ManualTROUBLESHOOTING GUIDES RosemountReference Manual 00809-0200-4101,Rev AA JulyFigure 5-2.Problems with communications flowchart RosemountReference Manual 00809-0200-4101,Rev AA JulyTable 5-1.Troubleshooting guide RosemountReference Manual 00809-0200-4101,Rev AA JulyReference Manual RESOURCE BLOCKRosemount Reference Manual SENSOR TRANSDUCER BLOCKRosemount LCD TRANSDUCER BLOCK RosemountReference Manual ANALOG INPUT AI FUNCTION BLOCK1.Put Resource block into OOS Out of Service RosemountReference Manual 00809-0200-4101,Rev AA JulyDISASSEMBLY PROCEDURES Remove from Service Remove Terminal BlockRosemount Reference ManualReference Manual Remove the Electronics BoardRosemount REASSEMBLY PROCEDURES Attach the Electronics Board Install the Terminal BlockReassemble the 2051C Process Flange RosemountReference Manual Install the Drain/Vent ValveRosemount PERFORMANCE SPECIFICATIONS Conformance To Specification ±3σ SigmaAppendix A Reference DataLong Term Stability Dynamic PerformanceLine Pressure Effect per 1000 psi 6,9 MPa RosemountVibration Effect Power Supply Effect Ambient Temperature Effect per 50F 28CMounting Position Effects Electromagnetic Compatibility EMCFUNCTIONAL SPECIFICATIONS Range and Sensor Limits ServiceProtocols Rosemount00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual Overpressure LimitsRosemount Static Pressure Limit Burst Pressure Limits Temperature LimitsRosemount Reference ManualHumidity Limits Volumetric Displacement Damping Failure Mode AlarmRosemount Reference ManualPHYSICAL SPECIFICATIONS Electrical Connections Process Connections 2051C Process Wetted Parts2051T Process Wetted Parts 2051L Process Wetted PartsReference Manual Non-WettedParts for 2051C/T/LRosemount Shipping Weights Table A-4.Transmitter Weights without OptionsTable A-5.2051L Weights without Options Table A-6.Transmitter Options WeightsReference Manual ORDERING INFORMATIONRosemount Alternate Process Connection: Flange2 RosemountReference Manual CSA FISCO Intrinsically Safe RosemountReference Manual A-15 RosemountReference Manual GGage AAbsolute RosemountReference Manual FM Intrinsically Safe, Division RosemountReference Manual Rosemount Reference ManualSpecial Certifications Q4 Calibration Certificate Prior-usecertificate of FMEDA data4 -300to 300 psi/3 psi -20,7to 20,7 bar/0,2 bar RosemountReference Manual Syltherm XLT RosemountReference Manual Reference Manual ATEX Flameproof, Intrinsic Safety, Type n, DustRosemount Reference Manual OPTIONSRosemount 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual SPARE PARTS RosemountReference Manual LCD Display, FOUNDATION fieldbusNickel-platedcarbon steel RosemountReference Manual Gage Flange and Adapter Bolt Kit Set of RosemountReference Manual A-28 RosemountReference Manual OVERVIEW SAFETY MESSAGES Appendix B Approval InformationWarnings Approved Manufacturing LocationsEuropean Directive Information FIELDBUS PROTOCOLHazardous Locations Certifications Rosemount00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual APPROVAL DRAWINGS Factory Mutual FMRosemount Rosemount Reference ManualB-10 RosemountReference Manual B-11 RosemountReference Manual B-12 RosemountReference Manual B-13 RosemountReference Manual B-14 RosemountReference Manual B-15 RosemountReference Manual B-16 RosemountReference Manual B-17 RosemountReference Manual B-18 RosemountReference Manual B-19 RosemountReference Manual B-20 RosemountReference Manual Canadian Standards Association CSA RosemountReference Manual B-21B-22 RosemountReference Manual B-23 RosemountReference Manual B-24 RosemountReference Manual B-25 RosemountReference Manual B-26 RosemountReference Manual B-27 RosemountReference Manual B-28 RosemountReference Manual B-29 RosemountReference Manual B-30 RosemountReference Manual Appendix C Block InformationTRANSDUCER BLOCK Overview RosemountReference Manual Parameters and DescriptionsRosemount PRIMARY_VALUE_RANGE RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Troubleshooting OverviewRosemount Reference ManualRosemount Reference ManualParameters and Descriptions 00809-0200-4101,Rev AA JulyFLANGE_MTL RosemountReference Manual REM_SEAL_FILL RosemountReference Manual Simulate_STATE RosemountReference Manual Block Errors RosemountReference Manual 00809-0200-4101,Rev AA July00809-0200-4101,Rev AA July RosemountReference Manual Mode will not leave RosemountReference Manual C-14 RosemountReference Manual Reference Manual IndexRosemount 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Index-4 RosemountReference Manual 00809-0200-4101,Rev AA July NOTES RosemountReference Manual Rosemount Reference ManualPage Reference Manual Rosemount¢00809-0100-4801V¤