Grounding

Reference Manual

00809-0200-4101, Rev AA July 2008

Rosemount 2051

Figure 2-15. Transmitter Jumper Locations

Grounding

Simulate Jumper

Security Jumper

Manual background Use the following techniques to properly ground the transmitter case:

Transmitter Case

Always ground the transmitter case in accordance with national and local electrical codes. The most effective transmitter case grounding method is a direct connection to earth ground with minimal impedance. Methods for grounding the transmitter case include:

Internal Ground Connection: The Internal Ground Connection screw

is inside the FIELD TERMINALS side of the electronics housing. This screw is identified by a ground symbol ( Manual background ). The ground connection screw is standard on all Rosemount 2051 transmitters. Refer to Figure 2-16.

External Ground Assembly: This assembly is included with the optional transient protection terminal block (Option Code T1), and it is included with various hazardous location certifications. The External Ground Assembly can also be ordered with the transmitter (Option Code V5), or as a spare part. See “Spare Parts” on page A-25. Refer to Figure 2-17 for location of the External Ground Screw.

2-25

Image 35
Contents Rosemount 2051 Pressure Transmitter with FOUNDATION Fieldbus ProtocolReference Manual Page Reference Manual Rosemount 2051 PressureTransmitter with FOUNDATION Fieldbus RosemountPage Rosemount Table of ContentsSECTION 1 Introduction SECTION 2 Installation SECTION 3 ConfigurationRosemount SECTION Operation and MaintenanceSECTION 5 Troubleshooting APPENDIX A Reference DataReference Manual APPENDIX B Approval InformationAPPENDIX C Block Information RosemountTOC-4 RosemountReference Manual Rosemount USING THIS MANUAL SERVICE SUPPORTSection IntroductionReference Manual MODELS COVEREDRosemount Rosemount InstallationOVERVIEW SAFETY MESSAGES Warnings SectionENVIRONMENTAL GENERALCONSIDERATIONS MECHANICALRosemount INSTALLATION PROCEDURESDimensional Drawings 2051C Coplanar Flange Dimensional Drawing00809-0200-4101,Rev AA Coplanar Flange Mounting Configurations withRosemount Reference ManualReference Manual 2051C Coplanar with Traditional FlangeRosemount Reference Manual Traditional Flange Mounting Configurations withOptional Brackets for 2-in.Pipe or Panel Mounting RosemountReference Manual 2051T Dimensional Drawings2051T with Rosemount 306 Integral Manifold RosemountPanel Mounting RosemountReference Manual Pipe MountingReference Manual 2051L Liquid LevelRosemount Reference Manual Mount the TransmitterRosemount 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July Figure 2-6.Traditional Flange Bolt ConfigurationsRosemount Reference ManualReference Manual Impulse PipingRosemount Flow RosemountReference Manual Reference Manual Process ConnectionsRosemount 00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual Housing RotationRosemount Reference Manual LCD DisplayTagging RosemountReference Manual Conduit InstallationELECTRICAL RosemountReference Manual WiringRosemount Reference Manual Transient Protection Terminal BlockRosemount Reference Manual JumpersSecurityRosemount Reference Manual GroundingRosemount Reference Manual Figure 2-17.External Ground AssemblyExternal Ground Assembly RosemountReference Manual HAZARDOUS LOCATIONS CERTIFICATIONSROSEMOUNT 305, 306 AND 304 MANIFOLDS RosemountConventional Manifold Installation Procedure Rosemount 305 Integral Manifold InstallationProcedure Rosemount 306 Integral Manifold Installation Procedure RosemountReference Manual Integral Manifold OperationRosemount 00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual LIQUID LEVEL MEASUREMENTOpen Vessels Closed Vessels Rosemount00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual RosemountRosemount ConfigurationOVERVIEW SAFETY MESSAGES Warnings SectionRosemount DEVICE CAPABILITIES Link Active SchedulerCapabilities GENERAL BLOCK INFORMATION ModesReference Manual RESOURCE BLOCK FEATURES and FEATURES SELSimulation RosemountReference Manual MAX_NOTIFYRosemount Reference Manual Configure the AI blockANALOG INPUT AI FUNCTION BLOCK RosemountReference Manual Configuration ExamplesRosemount 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual FilteringLow Cutoff RosemountReference Manual Process Alarms Alarm PriorityStatus Options RosemountReference Manual Advanced Features LCD BLOCKRosemount 00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual Section 4 Operation and MaintenanceOVERVIEW SAFETY MESSAGES Warnings RosemountReference Manual STATUS Master Reset Method SimulationRosemount Reference Manual CALIBRATION Sensor CalibrationUpper and Lower Trim Methods RosemountReference Manual Sensor Calibration, Zero Trim MethodFactory Calibration Method RosemountReference Manual Section 5 TroubleshootingOVERVIEW SAFETY MESSAGES Warnings Rosemount00809-0200-4101,Rev AA July TROUBLESHOOTING GUIDESRosemount Reference Manual00809-0200-4101,Rev AA July Figure 5-2.Problems with communications flowchartRosemount Reference Manual00809-0200-4101,Rev AA July Table 5-1.Troubleshooting guideRosemount Reference ManualReference Manual RESOURCE BLOCKRosemount Reference Manual SENSOR TRANSDUCER BLOCKRosemount ANALOG INPUT AI FUNCTION BLOCK LCD TRANSDUCER BLOCKRosemount Reference Manual00809-0200-4101,Rev AA July 1.Put Resource block into OOS Out of ServiceRosemount Reference ManualReference Manual DISASSEMBLY PROCEDURES Remove from ServiceRemove Terminal Block RosemountReference Manual Remove the Electronics BoardRosemount Rosemount REASSEMBLY PROCEDURES Attach theElectronics Board Install the Terminal Block Reassemble the 2051C Process FlangeReference Manual Install the Drain/Vent ValveRosemount Reference Data PERFORMANCE SPECIFICATIONSConformance To Specification ±3σ Sigma Appendix ARosemount Long Term StabilityDynamic Performance Line Pressure Effect per 1000 psi 6,9 MPaElectromagnetic Compatibility EMC Vibration Effect Power Supply EffectAmbient Temperature Effect per 50F 28C Mounting Position EffectsRosemount FUNCTIONAL SPECIFICATIONS Range and Sensor LimitsService Protocols00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual Overpressure LimitsRosemount Reference Manual Static Pressure Limit Burst Pressure LimitsTemperature Limits RosemountReference Manual Humidity Limits Volumetric Displacement DampingFailure Mode Alarm Rosemount2051L Process Wetted Parts PHYSICAL SPECIFICATIONS Electrical ConnectionsProcess Connections 2051C Process Wetted Parts 2051T Process Wetted PartsReference Manual Non-WettedParts for 2051C/T/LRosemount Table A-6.Transmitter Options Weights Shipping WeightsTable A-4.Transmitter Weights without Options Table A-5.2051L Weights without OptionsReference Manual ORDERING INFORMATIONRosemount Alternate Process Connection: Flange2 RosemountReference Manual CSA FISCO Intrinsically Safe RosemountReference Manual A-15 RosemountReference Manual GGage AAbsolute RosemountReference Manual FM Intrinsically Safe, Division RosemountReference Manual Prior-usecertificate of FMEDA data RosemountReference Manual Special Certifications Q4 Calibration Certificate4 -300to 300 psi/3 psi -20,7to 20,7 bar/0,2 bar RosemountReference Manual Syltherm XLT RosemountReference Manual Reference Manual ATEX Flameproof, Intrinsic Safety, Type n, DustRosemount Reference Manual OPTIONSRosemount 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual LCD Display, FOUNDATION fieldbus SPARE PARTSRosemount Reference ManualNickel-platedcarbon steel RosemountReference Manual Gage Flange and Adapter Bolt Kit Set of RosemountReference Manual A-28 RosemountReference Manual Approved Manufacturing Locations OVERVIEW SAFETY MESSAGESAppendix B Approval Information WarningsRosemount European Directive InformationFIELDBUS PROTOCOL Hazardous Locations Certifications00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual APPROVAL DRAWINGS Factory Mutual FMRosemount Reference Manual RosemountB-10 RosemountReference Manual B-11 RosemountReference Manual B-12 RosemountReference Manual B-13 RosemountReference Manual B-14 RosemountReference Manual B-15 RosemountReference Manual B-16 RosemountReference Manual B-17 RosemountReference Manual B-18 RosemountReference Manual B-19 RosemountReference Manual B-20 RosemountReference Manual B-21 Canadian Standards Association CSARosemount Reference ManualB-22 RosemountReference Manual B-23 RosemountReference Manual B-24 RosemountReference Manual B-25 RosemountReference Manual B-26 RosemountReference Manual B-27 RosemountReference Manual B-28 RosemountReference Manual B-29 RosemountReference Manual B-30 RosemountReference Manual Rosemount Appendix CBlock Information TRANSDUCER BLOCK OverviewReference Manual Parameters and DescriptionsRosemount PRIMARY_VALUE_RANGE RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual TroubleshootingOverview Rosemount00809-0200-4101,Rev AA July RosemountReference Manual Parameters and DescriptionsFLANGE_MTL RosemountReference Manual REM_SEAL_FILL RosemountReference Manual Simulate_STATE RosemountReference Manual 00809-0200-4101,Rev AA July Block ErrorsRosemount Reference Manual00809-0200-4101,Rev AA July RosemountReference Manual Mode will not leave RosemountReference Manual C-14 RosemountReference Manual Reference Manual IndexRosemount 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Index-4 RosemountReference Manual 00809-0200-4101,Rev AA July NOTES RosemountReference Manual Reference Manual RosemountPage Reference Manual Rosemount¢00809-0100-4801V¤