LIQUID LEVEL MEASUREMENT

Reference Manual

00809-0200-4101, Rev AA July 2008

Rosemount 2051

LIQUID LEVEL MEASUREMENT

Differential pressure transmitters used for liquid level applications measure hydrostatic pressure head. Liquid level and specific gravity of a liquid are factors in determining pressure head. This pressure is equal to the liquid height above the tap multiplied by the specific gravity of the liquid. Pressure head is independent of volume or vessel shape.

Open Vessels

Closed Vessels

A pressure transmitter mounted near a tank bottom measures the pressure of the liquid above.

Make a connection to the high pressure side of the transmitter, and vent the low pressure side to the atmosphere. Pressure head equals the liquid’s specific gravity multiplied by the liquid height above the tap.

Zero range suppression is required if the transmitter lies below the zero point of the desired level range. Figure 2-19 shows a liquid level measurement example.

Pressure above a liquid affects the pressure measured at the bottom of a closed vessel. The liquid specific gravity multiplied by the liquid height plus the vessel pressure equals the pressure at the bottom of the vessel.

To measure true level, the vessel pressure must be subtracted from the vessel bottom pressure. To do this, make a pressure tap at the top of the vessel and connect this to the low side of the transmitter. Vessel pressure is then equally applied to both the high and low sides of the transmitter. The resulting differential pressure is proportional to liquid height multiplied by the liquid specific gravity.

Dry Leg Condition

Low-side transmitter piping will remain empty if gas above the liquid does not condense. This is a dry leg condition. Range determination calculations are the same as those described for bottom-mounted transmitters in open vessels, as shown in Figure 2-19.

Figure 2-19. Liquid Level

Measurement Example.

Let X equal the vertical distance between the minimum and maximum measurable levels (500 in.).

Let Y equal the vertical distance between the transmitter datum line and the minimum measurable level (100 in.).

Let SG equal the specific gravity of the fluid (0.9).

Let h equal the maximum head pressure to be measured in inches of water. Let e equal head pressure produced by Y expressed in inches of water. Let Range equal e to e + h.

Then h = (X)(SG)

=500 x 0.9

=450 inH2O

e = (Y)(SG)

=100 x 0.9

=90 inH2O

Range = 90 to 540 inH2O

X

Y

T

20

ZERO SUPRESSION

mA dc

4

0

90

540

 

 

inH2O

2-31

Image 41
Contents Rosemount 2051 Pressure Transmitter with FOUNDATION Fieldbus ProtocolReference Manual Page Transmitter with FOUNDATION Fieldbus Rosemount 2051 PressureRosemount Reference ManualPage SECTION 1 Introduction SECTION 2 Installation Table of ContentsSECTION 3 Configuration RosemountSECTION 5 Troubleshooting SECTION Operation and MaintenanceAPPENDIX A Reference Data RosemountAPPENDIX C Block Information APPENDIX B Approval InformationRosemount Reference ManualTOC-4 RosemountReference Manual Section USING THIS MANUAL SERVICE SUPPORTIntroduction RosemountReference Manual MODELS COVEREDRosemount OVERVIEW SAFETY MESSAGES Warnings InstallationSection RosemountCONSIDERATIONS GENERALMECHANICAL ENVIRONMENTALDimensional Drawings INSTALLATION PROCEDURES2051C Coplanar Flange Dimensional Drawing RosemountRosemount Coplanar Flange Mounting Configurations withReference Manual 00809-0200-4101,Rev AAReference Manual 2051C Coplanar with Traditional FlangeRosemount Optional Brackets for 2-in.Pipe or Panel Mounting Traditional Flange Mounting Configurations withRosemount Reference Manual2051T with Rosemount 306 Integral Manifold 2051T Dimensional DrawingsRosemount Reference ManualReference Manual RosemountPipe Mounting Panel MountingReference Manual 2051L Liquid LevelRosemount Reference Manual Mount the TransmitterRosemount 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Rosemount Figure 2-6.Traditional Flange Bolt ConfigurationsReference Manual 00809-0200-4101,Rev AA JulyReference Manual Impulse PipingRosemount Flow RosemountReference Manual Reference Manual Process ConnectionsRosemount 00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual Housing RotationRosemount Tagging LCD DisplayRosemount Reference ManualELECTRICAL Conduit InstallationRosemount Reference ManualReference Manual WiringRosemount Reference Manual Transient Protection Terminal BlockRosemount Reference Manual JumpersSecurityRosemount Reference Manual GroundingRosemount External Ground Assembly Figure 2-17.External Ground AssemblyRosemount Reference ManualROSEMOUNT 305, 306 AND 304 MANIFOLDS HAZARDOUS LOCATIONS CERTIFICATIONSRosemount Reference ManualProcedure Rosemount 306 Integral Rosemount 305 Integral Manifold InstallationManifold Installation Procedure Rosemount Conventional Manifold Installation ProcedureReference Manual Integral Manifold OperationRosemount 00809-0200-4101,Rev AA July RosemountReference Manual Open Vessels Closed Vessels LIQUID LEVEL MEASUREMENTRosemount Reference Manual00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual RosemountOVERVIEW SAFETY MESSAGES Warnings ConfigurationSection RosemountCapabilities DEVICE CAPABILITIES Link Active SchedulerGENERAL BLOCK INFORMATION Modes RosemountSimulation RESOURCE BLOCK FEATURES and FEATURES SELRosemount Reference ManualReference Manual MAX_NOTIFYRosemount ANALOG INPUT AI FUNCTION BLOCK Configure the AI blockRosemount Reference ManualReference Manual Configuration ExamplesRosemount 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Low Cutoff FilteringRosemount Reference ManualStatus Options Process Alarms Alarm PriorityRosemount Reference ManualReference Manual Advanced Features LCD BLOCKRosemount 00809-0200-4101,Rev AA July RosemountReference Manual OVERVIEW SAFETY MESSAGES Warnings Section 4 Operation and MaintenanceRosemount Reference ManualReference Manual STATUS Master Reset Method SimulationRosemount Upper and Lower Trim Methods CALIBRATION Sensor CalibrationRosemount Reference ManualFactory Calibration Method Sensor Calibration, Zero Trim MethodRosemount Reference ManualOVERVIEW SAFETY MESSAGES Warnings Section 5 TroubleshootingRosemount Reference ManualRosemount TROUBLESHOOTING GUIDESReference Manual 00809-0200-4101,Rev AA JulyRosemount Figure 5-2.Problems with communications flowchartReference Manual 00809-0200-4101,Rev AA JulyRosemount Table 5-1.Troubleshooting guideReference Manual 00809-0200-4101,Rev AA JulyReference Manual RESOURCE BLOCKRosemount Reference Manual SENSOR TRANSDUCER BLOCKRosemount Rosemount LCD TRANSDUCER BLOCKReference Manual ANALOG INPUT AI FUNCTION BLOCKRosemount 1.Put Resource block into OOS Out of ServiceReference Manual 00809-0200-4101,Rev AA JulyRemove Terminal Block DISASSEMBLY PROCEDURES Remove from ServiceRosemount Reference ManualReference Manual Remove the Electronics BoardRosemount Electronics Board Install the Terminal Block REASSEMBLY PROCEDURES Attach theReassemble the 2051C Process Flange RosemountReference Manual Install the Drain/Vent ValveRosemount Conformance To Specification ±3σ Sigma PERFORMANCE SPECIFICATIONSAppendix A Reference DataDynamic Performance Long Term StabilityLine Pressure Effect per 1000 psi 6,9 MPa RosemountAmbient Temperature Effect per 50F 28C Vibration Effect Power Supply EffectMounting Position Effects Electromagnetic Compatibility EMCService FUNCTIONAL SPECIFICATIONS Range and Sensor LimitsProtocols Rosemount00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual Overpressure LimitsRosemount Temperature Limits Static Pressure Limit Burst Pressure LimitsRosemount Reference ManualFailure Mode Alarm Humidity Limits Volumetric Displacement DampingRosemount Reference ManualProcess Connections 2051C Process Wetted Parts PHYSICAL SPECIFICATIONS Electrical Connections2051T Process Wetted Parts 2051L Process Wetted PartsReference Manual Non-WettedParts for 2051C/T/LRosemount Table A-4.Transmitter Weights without Options Shipping WeightsTable A-5.2051L Weights without Options Table A-6.Transmitter Options WeightsReference Manual ORDERING INFORMATIONRosemount Alternate Process Connection: Flange2 RosemountReference Manual CSA FISCO Intrinsically Safe RosemountReference Manual A-15 RosemountReference Manual GGage AAbsolute RosemountReference Manual FM Intrinsically Safe, Division RosemountReference Manual Reference Manual RosemountSpecial Certifications Q4 Calibration Certificate Prior-usecertificate of FMEDA data4 -300to 300 psi/3 psi -20,7to 20,7 bar/0,2 bar RosemountReference Manual Syltherm XLT RosemountReference Manual Reference Manual ATEX Flameproof, Intrinsic Safety, Type n, DustRosemount Reference Manual OPTIONSRosemount 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Rosemount SPARE PARTSReference Manual LCD Display, FOUNDATION fieldbusNickel-platedcarbon steel RosemountReference Manual Gage Flange and Adapter Bolt Kit Set of RosemountReference Manual A-28 RosemountReference Manual Appendix B Approval Information OVERVIEW SAFETY MESSAGESWarnings Approved Manufacturing LocationsFIELDBUS PROTOCOL European Directive InformationHazardous Locations Certifications Rosemount00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual APPROVAL DRAWINGS Factory Mutual FMRosemount Reference Manual RosemountB-10 RosemountReference Manual B-11 RosemountReference Manual B-12 RosemountReference Manual B-13 RosemountReference Manual B-14 RosemountReference Manual B-15 RosemountReference Manual B-16 RosemountReference Manual B-17 RosemountReference Manual B-18 RosemountReference Manual B-19 RosemountReference Manual B-20 RosemountReference Manual Rosemount Canadian Standards Association CSAReference Manual B-21B-22 RosemountReference Manual B-23 RosemountReference Manual B-24 RosemountReference Manual B-25 RosemountReference Manual B-26 RosemountReference Manual B-27 RosemountReference Manual B-28 RosemountReference Manual B-29 RosemountReference Manual B-30 RosemountReference Manual Block Information Appendix CTRANSDUCER BLOCK Overview RosemountReference Manual Parameters and DescriptionsRosemount PRIMARY_VALUE_RANGE RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Overview TroubleshootingRosemount Reference ManualReference Manual RosemountParameters and Descriptions 00809-0200-4101,Rev AA JulyFLANGE_MTL RosemountReference Manual REM_SEAL_FILL RosemountReference Manual Simulate_STATE RosemountReference Manual Rosemount Block ErrorsReference Manual 00809-0200-4101,Rev AA July00809-0200-4101,Rev AA July RosemountReference Manual Mode will not leave RosemountReference Manual C-14 RosemountReference Manual Reference Manual IndexRosemount 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Index-4 RosemountReference Manual 00809-0200-4101,Rev AA July NOTES RosemountReference Manual Reference Manual RosemountPage Reference Manual Rosemount¢00809-0100-4801V¤