Section 4 Operation and Maintenance

Reference Manual

00809-0200-4101, Rev AA July 2008

Rosemount 2051

Section 4 Operation and Maintenance

OVERVIEW

SAFETY MESSAGES

Warnings

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1 Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-2 Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-3

This section contains information on operation and maintenance procedures.

METHODS AND MANUAL OPERATION

Each FOUNDATION fieldbus host or configuration tool has different ways of displaying and performing operations. Some hosts will use Device Descriptions (DD) and DD Methods to complete device configuration and will display data consistently across platforms. The DD can found on Foundation’s website at www.fieldbus.org. There is no requirement that a host or configuration tool support these features.

For DeltaV users, the DD can be found at www.easydeltav.com. The information in this section will describe how to use methods in a general fashion. In addition, if your host or configuration tool does not support methods this section will cover manually configuring the parameters involved with each method operation. For more detailed information on the use of methods, see your host or configuration tool manual.

Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations. Information that raises potential safety issues is indicated by a warning symbol (Manual background). Refer to the following safety messages before performing an operation preceded by this symbol.

Explosions can result in death or serious injury.

Do not remove the transmitter covers in explosive environments when the circuit is live.

Transmitter covers must be fully engaged to meet explosion proof requirements.

Before connecting a communicator in an explosive atmosphere, make sure the instruments in the loop are installed in accordance with intrinsically safe or nonincendive field wiring practices.

www.rosemount.com

Image 57
Contents with FOUNDATION Fieldbus Protocol Reference ManualRosemount 2051 Pressure Transmitter Page Transmitter with FOUNDATION Fieldbus Rosemount 2051 PressureRosemount Reference ManualPage SECTION 1 Introduction SECTION 2 Installation Table of ContentsSECTION 3 Configuration RosemountSECTION 5 Troubleshooting SECTION Operation and MaintenanceAPPENDIX A Reference Data RosemountAPPENDIX C Block Information APPENDIX B Approval InformationRosemount Reference ManualRosemount Reference ManualTOC-4 Section USING THIS MANUAL SERVICE SUPPORTIntroduction RosemountMODELS COVERED RosemountReference Manual OVERVIEW SAFETY MESSAGES Warnings InstallationSection RosemountCONSIDERATIONS GENERALMECHANICAL ENVIRONMENTALDimensional Drawings INSTALLATION PROCEDURES2051C Coplanar Flange Dimensional Drawing RosemountRosemount Coplanar Flange Mounting Configurations withReference Manual 00809-0200-4101,Rev AA2051C Coplanar with Traditional Flange RosemountReference Manual Optional Brackets for 2-in.Pipe or Panel Mounting Traditional Flange Mounting Configurations withRosemount Reference Manual2051T with Rosemount 306 Integral Manifold 2051T Dimensional DrawingsRosemount Reference ManualReference Manual RosemountPipe Mounting Panel Mounting2051L Liquid Level RosemountReference Manual Mount the Transmitter RosemountReference Manual Rosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Figure 2-6.Traditional Flange Bolt ConfigurationsReference Manual 00809-0200-4101,Rev AA JulyImpulse Piping RosemountReference Manual Rosemount Reference ManualFlow Process Connections RosemountReference Manual Rosemount Reference Manual00809-0200-4101,Rev AA July Housing Rotation RosemountReference Manual Tagging LCD DisplayRosemount Reference ManualELECTRICAL Conduit InstallationRosemount Reference ManualWiring RosemountReference Manual Transient Protection Terminal Block RosemountReference Manual JumpersSecurity RosemountReference Manual Grounding RosemountReference Manual External Ground Assembly Figure 2-17.External Ground AssemblyRosemount Reference ManualROSEMOUNT 305, 306 AND 304 MANIFOLDS HAZARDOUS LOCATIONS CERTIFICATIONSRosemount Reference ManualProcedure Rosemount 306 Integral Rosemount 305 Integral Manifold InstallationManifold Installation Procedure Rosemount Conventional Manifold Installation ProcedureIntegral Manifold Operation RosemountReference Manual Rosemount Reference Manual00809-0200-4101,Rev AA July Open Vessels Closed Vessels LIQUID LEVEL MEASUREMENTRosemount Reference ManualRosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference Manual00809-0200-4101,Rev AA July Reference Manual RosemountOVERVIEW SAFETY MESSAGES Warnings ConfigurationSection RosemountCapabilities DEVICE CAPABILITIES Link Active SchedulerGENERAL BLOCK INFORMATION Modes RosemountSimulation RESOURCE BLOCK FEATURES and FEATURES SELRosemount Reference ManualMAX_NOTIFY RosemountReference Manual ANALOG INPUT AI FUNCTION BLOCK Configure the AI blockRosemount Reference ManualConfiguration Examples RosemountReference Manual Rosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference Manual00809-0200-4101,Rev AA July Low Cutoff FilteringRosemount Reference ManualStatus Options Process Alarms Alarm PriorityRosemount Reference ManualAdvanced Features LCD BLOCK RosemountReference Manual Rosemount Reference Manual00809-0200-4101,Rev AA July OVERVIEW SAFETY MESSAGES Warnings Section 4 Operation and MaintenanceRosemount Reference ManualSTATUS Master Reset Method Simulation RosemountReference Manual Upper and Lower Trim Methods CALIBRATION Sensor CalibrationRosemount Reference ManualFactory Calibration Method Sensor Calibration, Zero Trim MethodRosemount Reference ManualOVERVIEW SAFETY MESSAGES Warnings Section 5 TroubleshootingRosemount Reference ManualRosemount TROUBLESHOOTING GUIDESReference Manual 00809-0200-4101,Rev AA JulyRosemount Figure 5-2.Problems with communications flowchartReference Manual 00809-0200-4101,Rev AA JulyRosemount Table 5-1.Troubleshooting guideReference Manual 00809-0200-4101,Rev AA JulyRESOURCE BLOCK RosemountReference Manual SENSOR TRANSDUCER BLOCK RosemountReference Manual Rosemount LCD TRANSDUCER BLOCKReference Manual ANALOG INPUT AI FUNCTION BLOCKRosemount 1.Put Resource block into OOS Out of ServiceReference Manual 00809-0200-4101,Rev AA JulyRemove Terminal Block DISASSEMBLY PROCEDURES Remove from ServiceRosemount Reference ManualRemove the Electronics Board RosemountReference Manual Electronics Board Install the Terminal Block REASSEMBLY PROCEDURES Attach theReassemble the 2051C Process Flange RosemountInstall the Drain/Vent Valve RosemountReference Manual Conformance To Specification ±3σ Sigma PERFORMANCE SPECIFICATIONSAppendix A Reference DataDynamic Performance Long Term StabilityLine Pressure Effect per 1000 psi 6,9 MPa RosemountAmbient Temperature Effect per 50F 28C Vibration Effect Power Supply EffectMounting Position Effects Electromagnetic Compatibility EMCService FUNCTIONAL SPECIFICATIONS Range and Sensor LimitsProtocols RosemountRosemount Reference Manual00809-0200-4101,Rev AA July Overpressure Limits RosemountReference Manual Temperature Limits Static Pressure Limit Burst Pressure LimitsRosemount Reference ManualFailure Mode Alarm Humidity Limits Volumetric Displacement DampingRosemount Reference ManualProcess Connections 2051C Process Wetted Parts PHYSICAL SPECIFICATIONS Electrical Connections2051T Process Wetted Parts 2051L Process Wetted PartsNon-WettedParts for 2051C/T/L RosemountReference Manual Table A-4.Transmitter Weights without Options Shipping WeightsTable A-5.2051L Weights without Options Table A-6.Transmitter Options WeightsORDERING INFORMATION RosemountReference Manual Rosemount Reference ManualAlternate Process Connection: Flange2 Rosemount Reference ManualCSA FISCO Intrinsically Safe Rosemount Reference ManualA-15 Rosemount Reference ManualGGage AAbsolute Rosemount Reference ManualFM Intrinsically Safe, Division Reference Manual RosemountSpecial Certifications Q4 Calibration Certificate Prior-usecertificate of FMEDA dataRosemount Reference Manual4 -300to 300 psi/3 psi -20,7to 20,7 bar/0,2 bar Rosemount Reference ManualSyltherm XLT ATEX Flameproof, Intrinsic Safety, Type n, Dust RosemountReference Manual OPTIONS RosemountReference Manual Rosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference Manual00809-0200-4101,Rev AA July Rosemount SPARE PARTSReference Manual LCD Display, FOUNDATION fieldbusRosemount Reference ManualNickel-platedcarbon steel Rosemount Reference ManualGage Flange and Adapter Bolt Kit Set of Rosemount Reference ManualA-28 Appendix B Approval Information OVERVIEW SAFETY MESSAGESWarnings Approved Manufacturing LocationsFIELDBUS PROTOCOL European Directive InformationHazardous Locations Certifications RosemountRosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference Manual00809-0200-4101,Rev AA July APPROVAL DRAWINGS Factory Mutual FM RosemountReference Manual Reference Manual RosemountRosemount Reference ManualB-10 Rosemount Reference ManualB-11 Rosemount Reference ManualB-12 Rosemount Reference ManualB-13 Rosemount Reference ManualB-14 Rosemount Reference ManualB-15 Rosemount Reference ManualB-16 Rosemount Reference ManualB-17 Rosemount Reference ManualB-18 Rosemount Reference ManualB-19 Rosemount Reference ManualB-20 Rosemount Canadian Standards Association CSAReference Manual B-21Rosemount Reference ManualB-22 Rosemount Reference ManualB-23 Rosemount Reference ManualB-24 Rosemount Reference ManualB-25 Rosemount Reference ManualB-26 Rosemount Reference ManualB-27 Rosemount Reference ManualB-28 Rosemount Reference ManualB-29 Rosemount Reference ManualB-30 Block Information Appendix CTRANSDUCER BLOCK Overview RosemountParameters and Descriptions RosemountReference Manual Rosemount Reference ManualPRIMARY_VALUE_RANGE Rosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference Manual00809-0200-4101,Rev AA July Overview TroubleshootingRosemount Reference ManualReference Manual RosemountParameters and Descriptions 00809-0200-4101,Rev AA JulyRosemount Reference ManualFLANGE_MTL Rosemount Reference ManualREM_SEAL_FILL Rosemount Reference ManualSimulate_STATE Rosemount Block ErrorsReference Manual 00809-0200-4101,Rev AA JulyRosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference ManualMode will not leave Rosemount Reference ManualC-14 Index RosemountReference Manual Rosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference Manual00809-0200-4101,Rev AA July Rosemount Reference ManualIndex-4 Rosemount Reference Manual00809-0200-4101,Rev AA July NOTES Reference Manual RosemountPage Rosemount ¢00809-0100-4801V¤Reference Manual