Parameter

Number

Description

 

 

 

SENSOR_TYPE

20

Type of sensor connected with the transducer block.

 

 

Valid sensor types are the following:

 

 

117 = Capacitance

 

 

124 = Strain Gauge

ST_REV

01

The revision level of the static data associated with the function block.

 

 

 

STRATEGY

03

The strategy field can be used to identify grouping of blocks.

TAG_DESC

02

The user description of the intended application of the block.

 

 

 

TB_DETAILED_STATUS

31

Indicates the state of the transmitter. The parameter contains specific codes relating to

 

 

the transducer block and the pressure sensor specifically.

TRANSDUCER_DIRECTORY

09

Directory that specifies the number and starting indices of the transducers in the

 

 

transducer block.

 

 

 

TRANSDUCER_TYPE

10

Identifies the transducer that follows.

 

 

100 = Standard pressure with calibration

UPDATE_EVT

07

This alert is generated by any change to the static data.

 

 

 

XD_ERROR

11

Provides additional error codes related to transducer blocks.

 

 

 

Block/Transducer Errors The following conditions are reported in the BLOCK_ERR and XD_ERROR parameters. Conditions in bold type are available. Conditions in italics are inactive for the Transducer block and are given here only for your reference.

Condition

 

Number

Condition Name and Description

0Other

1Block Configuration Error

2Link Configuration Error

3Simulate Active

4Local Override

5Device Fault State Set

6Device Needs Maintenance Soon

7Input failure/process variable has bad status

8Output Failure

9Memory Failure

10Lost Static Data

11Lost NV Data

12Readback Check Failed

13Device Needs Maintenance Now

14Power Up: The device was just powered-up.

15Out of Service: The actual mode is out of service.

17

General Error: A general error that cannot be specified below occurred

 

 

20

Electronics Failure: An electrical component failed.

 

 

22I/O Failure: An I/O failure occurred.

23Data Integrity Error: Data stored in the device is no longer valid due to a non-volatile memory checksum failure, a data verify after write failure, etc.

25Algorithm Error: The algorithm used in the transducer block produced an error due to overflow, data reasonableness failure, etc.

C-4

Image 134
Contents Rosemount 2051 Pressure Transmitter with FOUNDATION Fieldbus ProtocolReference Manual Page Rosemount Rosemount 2051 PressureTransmitter with FOUNDATION Fieldbus Reference ManualPage SECTION 3 Configuration Table of ContentsSECTION 1 Introduction SECTION 2 Installation RosemountAPPENDIX A Reference Data SECTION Operation and MaintenanceSECTION 5 Troubleshooting RosemountRosemount APPENDIX B Approval InformationAPPENDIX C Block Information Reference ManualTOC-4 RosemountReference Manual Introduction USING THIS MANUAL SERVICE SUPPORTSection RosemountReference Manual MODELS COVEREDRosemount Section InstallationOVERVIEW SAFETY MESSAGES Warnings RosemountMECHANICAL GENERALCONSIDERATIONS ENVIRONMENTAL2051C Coplanar Flange Dimensional Drawing INSTALLATION PROCEDURESDimensional Drawings RosemountReference Manual Coplanar Flange Mounting Configurations withRosemount 00809-0200-4101,Rev AAReference Manual 2051C Coplanar with Traditional FlangeRosemount Rosemount Traditional Flange Mounting Configurations withOptional Brackets for 2-in.Pipe or Panel Mounting Reference ManualRosemount 2051T Dimensional Drawings2051T with Rosemount 306 Integral Manifold Reference ManualPipe Mounting RosemountReference Manual Panel MountingReference Manual 2051L Liquid LevelRosemount Reference Manual Mount the TransmitterRosemount 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual Figure 2-6.Traditional Flange Bolt ConfigurationsRosemount 00809-0200-4101,Rev AA JulyReference Manual Impulse PipingRosemount Flow RosemountReference Manual Reference Manual Process ConnectionsRosemount 00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual Housing RotationRosemount Rosemount LCD DisplayTagging Reference ManualRosemount Conduit InstallationELECTRICAL Reference ManualReference Manual WiringRosemount Reference Manual Transient Protection Terminal BlockRosemount Reference Manual JumpersSecurityRosemount Reference Manual GroundingRosemount Rosemount Figure 2-17.External Ground AssemblyExternal Ground Assembly Reference ManualRosemount HAZARDOUS LOCATIONS CERTIFICATIONSROSEMOUNT 305, 306 AND 304 MANIFOLDS Reference ManualManifold Installation Procedure Rosemount Rosemount 305 Integral Manifold InstallationProcedure Rosemount 306 Integral Conventional Manifold Installation ProcedureReference Manual Integral Manifold OperationRosemount 00809-0200-4101,Rev AA July RosemountReference Manual Rosemount LIQUID LEVEL MEASUREMENTOpen Vessels Closed Vessels Reference Manual00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Rosemount Reference ManualSection ConfigurationOVERVIEW SAFETY MESSAGES Warnings RosemountGENERAL BLOCK INFORMATION Modes DEVICE CAPABILITIES Link Active SchedulerCapabilities RosemountRosemount RESOURCE BLOCK FEATURES and FEATURES SELSimulation Reference ManualReference Manual MAX_NOTIFYRosemount Rosemount Configure the AI blockANALOG INPUT AI FUNCTION BLOCK Reference ManualReference Manual Configuration ExamplesRosemount 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Rosemount FilteringLow Cutoff Reference ManualRosemount Process Alarms Alarm PriorityStatus Options Reference ManualReference Manual Advanced Features LCD BLOCKRosemount 00809-0200-4101,Rev AA July RosemountReference Manual Rosemount Section 4 Operation and MaintenanceOVERVIEW SAFETY MESSAGES Warnings Reference ManualReference Manual STATUS Master Reset Method SimulationRosemount Rosemount CALIBRATION Sensor CalibrationUpper and Lower Trim Methods Reference ManualRosemount Sensor Calibration, Zero Trim MethodFactory Calibration Method Reference ManualRosemount Section 5 TroubleshootingOVERVIEW SAFETY MESSAGES Warnings Reference ManualReference Manual TROUBLESHOOTING GUIDESRosemount 00809-0200-4101,Rev AA JulyReference Manual Figure 5-2.Problems with communications flowchartRosemount 00809-0200-4101,Rev AA JulyReference Manual Table 5-1.Troubleshooting guideRosemount 00809-0200-4101,Rev AA JulyReference Manual RESOURCE BLOCKRosemount Reference Manual SENSOR TRANSDUCER BLOCKRosemount Reference Manual LCD TRANSDUCER BLOCKRosemount ANALOG INPUT AI FUNCTION BLOCKReference Manual 1.Put Resource block into OOS Out of ServiceRosemount 00809-0200-4101,Rev AA JulyRosemount DISASSEMBLY PROCEDURES Remove from ServiceRemove Terminal Block Reference ManualReference Manual Remove the Electronics BoardRosemount Reassemble the 2051C Process Flange REASSEMBLY PROCEDURES Attach theElectronics Board Install the Terminal Block RosemountReference Manual Install the Drain/Vent ValveRosemount Appendix A PERFORMANCE SPECIFICATIONSConformance To Specification ±3σ Sigma Reference DataLine Pressure Effect per 1000 psi 6,9 MPa Long Term StabilityDynamic Performance RosemountMounting Position Effects Vibration Effect Power Supply EffectAmbient Temperature Effect per 50F 28C Electromagnetic Compatibility EMCProtocols FUNCTIONAL SPECIFICATIONS Range and Sensor LimitsService Rosemount00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual Overpressure LimitsRosemount Rosemount Static Pressure Limit Burst Pressure LimitsTemperature Limits Reference ManualRosemount Humidity Limits Volumetric Displacement DampingFailure Mode Alarm Reference Manual2051T Process Wetted Parts PHYSICAL SPECIFICATIONS Electrical ConnectionsProcess Connections 2051C Process Wetted Parts 2051L Process Wetted PartsReference Manual Non-WettedParts for 2051C/T/LRosemount Table A-5.2051L Weights without Options Shipping WeightsTable A-4.Transmitter Weights without Options Table A-6.Transmitter Options WeightsReference Manual ORDERING INFORMATIONRosemount Alternate Process Connection: Flange2 RosemountReference Manual CSA FISCO Intrinsically Safe RosemountReference Manual A-15 RosemountReference Manual GGage AAbsolute RosemountReference Manual FM Intrinsically Safe, Division RosemountReference Manual Special Certifications Q4 Calibration Certificate RosemountReference Manual Prior-usecertificate of FMEDA data4 -300to 300 psi/3 psi -20,7to 20,7 bar/0,2 bar RosemountReference Manual Syltherm XLT RosemountReference Manual Reference Manual ATEX Flameproof, Intrinsic Safety, Type n, DustRosemount Reference Manual OPTIONSRosemount 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual SPARE PARTSRosemount LCD Display, FOUNDATION fieldbusNickel-platedcarbon steel RosemountReference Manual Gage Flange and Adapter Bolt Kit Set of RosemountReference Manual A-28 RosemountReference Manual Warnings OVERVIEW SAFETY MESSAGESAppendix B Approval Information Approved Manufacturing LocationsHazardous Locations Certifications European Directive InformationFIELDBUS PROTOCOL Rosemount00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Reference Manual APPROVAL DRAWINGS Factory Mutual FMRosemount Rosemount Reference ManualB-10 RosemountReference Manual B-11 RosemountReference Manual B-12 RosemountReference Manual B-13 RosemountReference Manual B-14 RosemountReference Manual B-15 RosemountReference Manual B-16 RosemountReference Manual B-17 RosemountReference Manual B-18 RosemountReference Manual B-19 RosemountReference Manual B-20 RosemountReference Manual Reference Manual Canadian Standards Association CSARosemount B-21B-22 RosemountReference Manual B-23 RosemountReference Manual B-24 RosemountReference Manual B-25 RosemountReference Manual B-26 RosemountReference Manual B-27 RosemountReference Manual B-28 RosemountReference Manual B-29 RosemountReference Manual B-30 RosemountReference Manual TRANSDUCER BLOCK Overview Appendix CBlock Information RosemountReference Manual Parameters and DescriptionsRosemount PRIMARY_VALUE_RANGE RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Rosemount TroubleshootingOverview Reference ManualParameters and Descriptions RosemountReference Manual 00809-0200-4101,Rev AA JulyFLANGE_MTL RosemountReference Manual REM_SEAL_FILL RosemountReference Manual Simulate_STATE RosemountReference Manual Reference Manual Block ErrorsRosemount 00809-0200-4101,Rev AA July00809-0200-4101,Rev AA July RosemountReference Manual Mode will not leave RosemountReference Manual C-14 RosemountReference Manual Reference Manual IndexRosemount 00809-0200-4101,Rev AA July RosemountReference Manual 00809-0200-4101,Rev AA July RosemountReference Manual Index-4 RosemountReference Manual 00809-0200-4101,Rev AA July NOTES RosemountReference Manual Rosemount Reference ManualPage Reference Manual Rosemount¢00809-0100-4801V¤