Emerson Process Management 2051 manual Troubleshooting, Overview, Rosemount, Reference Manual

Page 136
Troubleshooting

Rosemount 2051

Reference Manual

00809-0200-4101, Rev AA July 2008

Troubleshooting

In Auto mode, PRIMARY_VALUE reflects the value and status quality of the output channels.

Methods

Sensor Calibration

In order to calibrate the sensor, the following steps are performed by the user calibration method:

1.Set MODE_BLK.TARGET = OOS.

2.Apply desired pressure (low pressure); allow to stabilize. Pressure applied must be between range limits defined in

PRIMARY_VALUE_RANGE.

3.Set CAL_POINT_LO to applied pressure.

4.Apply desired pressure (high pressure); allow to stabilize. Pressure applied must be between range limits defined in PRIMARY_VALUE_RANGE and greater than CAL_POINT_LO + CAL_MIN_SPAN.

5.Set CAL_POINT_HI to applied pressure.

6.Set SENSOR_CAL_DATE to current date.

7.Set SENSOR_CAL_WHO to person responsible for calibration.

8.Set SENSOR_CAL_LOC to calibration location.

9.Set MODE_BLK.TARGET = AUTO.

Refer to the table below to troubleshoot any problems encountered.

Symptom

Possible Causes

Corrective Action

 

 

 

Mode will not leave

Target mode not set.

Set target mode to something other

OOS

 

than OOS.

 

 

 

 

Detailed status error

See “Diagnostics” on page C-5

 

Resource block

The actual mode of the Resource block

 

 

is OOS. See Resource Block

 

 

Diagnostics for corrective action.

 

 

 

Pressure or Sensor

Measurement or

See “Diagnostics” on page C-5

Temperature Status

Device Error

 

is BAD

 

 

 

 

 

RESOURCE BLOCK

Overview

This section contains information on the Rosemount 2051 Resource Block.

 

Descriptions of all Resource Block Parameters, errors, and diagnostics are

 

included. Also the modes, alarm detection, status handling, and

 

troubleshooting are discussed.

 

Definition

 

The resource block defines the physical resources of the device. The

 

resource block also handles functionality that is common across multiple

 

blocks. The block has no linkable inputs or outputs and it performs memory

 

diagnostics.

C-6

Image 136
Contents Reference Manual with FOUNDATION Fieldbus ProtocolRosemount 2051 Pressure Transmitter Page Rosemount 2051 Pressure Transmitter with FOUNDATION FieldbusRosemount Reference ManualPage Table of Contents SECTION 1 Introduction SECTION 2 InstallationSECTION 3 Configuration RosemountSECTION Operation and Maintenance SECTION 5 TroubleshootingAPPENDIX A Reference Data RosemountAPPENDIX B Approval Information APPENDIX C Block InformationRosemount Reference ManualReference Manual RosemountTOC-4 USING THIS MANUAL SERVICE SUPPORT SectionIntroduction RosemountRosemount MODELS COVEREDReference Manual Installation OVERVIEW SAFETY MESSAGES WarningsSection RosemountGENERAL CONSIDERATIONSMECHANICAL ENVIRONMENTALINSTALLATION PROCEDURES Dimensional Drawings2051C Coplanar Flange Dimensional Drawing RosemountCoplanar Flange Mounting Configurations with RosemountReference Manual 00809-0200-4101,Rev AARosemount 2051C Coplanar with Traditional FlangeReference Manual Traditional Flange Mounting Configurations with Optional Brackets for 2-in.Pipe or Panel MountingRosemount Reference Manual2051T Dimensional Drawings 2051T with Rosemount 306 Integral ManifoldRosemount Reference ManualRosemount Reference ManualPipe Mounting Panel MountingRosemount 2051L Liquid LevelReference Manual Rosemount Mount the TransmitterReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Figure 2-6.Traditional Flange Bolt Configurations RosemountReference Manual 00809-0200-4101,Rev AA JulyRosemount Impulse PipingReference Manual Reference Manual RosemountFlow Rosemount Process ConnectionsReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July Rosemount Housing RotationReference Manual LCD Display TaggingRosemount Reference ManualConduit Installation ELECTRICALRosemount Reference ManualRosemount WiringReference Manual Rosemount Transient Protection Terminal BlockReference Manual Rosemount JumpersSecurityReference Manual Rosemount GroundingReference Manual Figure 2-17.External Ground Assembly External Ground AssemblyRosemount Reference ManualHAZARDOUS LOCATIONS CERTIFICATIONS ROSEMOUNT 305, 306 AND 304 MANIFOLDSRosemount Reference ManualRosemount 305 Integral Manifold Installation Procedure Rosemount 306 IntegralManifold Installation Procedure Rosemount Conventional Manifold Installation ProcedureRosemount Integral Manifold OperationReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July LIQUID LEVEL MEASUREMENT Open Vessels Closed VesselsRosemount Reference ManualReference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Rosemount Reference ManualConfiguration OVERVIEW SAFETY MESSAGES WarningsSection RosemountDEVICE CAPABILITIES Link Active Scheduler CapabilitiesGENERAL BLOCK INFORMATION Modes RosemountRESOURCE BLOCK FEATURES and FEATURES SEL SimulationRosemount Reference ManualRosemount MAX_NOTIFYReference Manual Configure the AI block ANALOG INPUT AI FUNCTION BLOCKRosemount Reference ManualRosemount Configuration ExamplesReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Filtering Low CutoffRosemount Reference ManualProcess Alarms Alarm Priority Status OptionsRosemount Reference ManualRosemount Advanced Features LCD BLOCKReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July Section 4 Operation and Maintenance OVERVIEW SAFETY MESSAGES WarningsRosemount Reference ManualRosemount STATUS Master Reset Method SimulationReference Manual CALIBRATION Sensor Calibration Upper and Lower Trim MethodsRosemount Reference ManualSensor Calibration, Zero Trim Method Factory Calibration MethodRosemount Reference ManualSection 5 Troubleshooting OVERVIEW SAFETY MESSAGES WarningsRosemount Reference ManualTROUBLESHOOTING GUIDES RosemountReference Manual 00809-0200-4101,Rev AA JulyFigure 5-2.Problems with communications flowchart RosemountReference Manual 00809-0200-4101,Rev AA JulyTable 5-1.Troubleshooting guide RosemountReference Manual 00809-0200-4101,Rev AA JulyRosemount RESOURCE BLOCKReference Manual Rosemount SENSOR TRANSDUCER BLOCKReference Manual LCD TRANSDUCER BLOCK RosemountReference Manual ANALOG INPUT AI FUNCTION BLOCK1.Put Resource block into OOS Out of Service RosemountReference Manual 00809-0200-4101,Rev AA JulyDISASSEMBLY PROCEDURES Remove from Service Remove Terminal BlockRosemount Reference ManualRosemount Remove the Electronics BoardReference Manual REASSEMBLY PROCEDURES Attach the Electronics Board Install the Terminal BlockReassemble the 2051C Process Flange RosemountRosemount Install the Drain/Vent ValveReference Manual PERFORMANCE SPECIFICATIONS Conformance To Specification ±3σ SigmaAppendix A Reference DataLong Term Stability Dynamic PerformanceLine Pressure Effect per 1000 psi 6,9 MPa RosemountVibration Effect Power Supply Effect Ambient Temperature Effect per 50F 28CMounting Position Effects Electromagnetic Compatibility EMCFUNCTIONAL SPECIFICATIONS Range and Sensor Limits ServiceProtocols RosemountReference Manual Rosemount00809-0200-4101,Rev AA July Rosemount Overpressure LimitsReference Manual Static Pressure Limit Burst Pressure Limits Temperature LimitsRosemount Reference ManualHumidity Limits Volumetric Displacement Damping Failure Mode AlarmRosemount Reference ManualPHYSICAL SPECIFICATIONS Electrical Connections Process Connections 2051C Process Wetted Parts2051T Process Wetted Parts 2051L Process Wetted PartsRosemount Non-WettedParts for 2051C/T/LReference Manual Shipping Weights Table A-4.Transmitter Weights without OptionsTable A-5.2051L Weights without Options Table A-6.Transmitter Options WeightsRosemount ORDERING INFORMATIONReference Manual Reference Manual RosemountAlternate Process Connection: Flange2 Reference Manual RosemountCSA FISCO Intrinsically Safe Reference Manual RosemountA-15 Reference Manual RosemountGGage AAbsolute Reference Manual RosemountFM Intrinsically Safe, Division Rosemount Reference ManualSpecial Certifications Q4 Calibration Certificate Prior-usecertificate of FMEDA dataReference Manual Rosemount4 -300to 300 psi/3 psi -20,7to 20,7 bar/0,2 bar Reference Manual RosemountSyltherm XLT Rosemount ATEX Flameproof, Intrinsic Safety, Type n, DustReference Manual Rosemount OPTIONSReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July SPARE PARTS RosemountReference Manual LCD Display, FOUNDATION fieldbusReference Manual RosemountNickel-platedcarbon steel Reference Manual RosemountGage Flange and Adapter Bolt Kit Set of Reference Manual RosemountA-28 OVERVIEW SAFETY MESSAGES Appendix B Approval InformationWarnings Approved Manufacturing LocationsEuropean Directive Information FIELDBUS PROTOCOLHazardous Locations Certifications RosemountReference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Rosemount APPROVAL DRAWINGS Factory Mutual FMReference Manual Rosemount Reference ManualReference Manual RosemountB-10 Reference Manual RosemountB-11 Reference Manual RosemountB-12 Reference Manual RosemountB-13 Reference Manual RosemountB-14 Reference Manual RosemountB-15 Reference Manual RosemountB-16 Reference Manual RosemountB-17 Reference Manual RosemountB-18 Reference Manual RosemountB-19 Reference Manual RosemountB-20 Canadian Standards Association CSA RosemountReference Manual B-21Reference Manual RosemountB-22 Reference Manual RosemountB-23 Reference Manual RosemountB-24 Reference Manual RosemountB-25 Reference Manual RosemountB-26 Reference Manual RosemountB-27 Reference Manual RosemountB-28 Reference Manual RosemountB-29 Reference Manual RosemountB-30 Appendix C Block InformationTRANSDUCER BLOCK Overview RosemountRosemount Parameters and DescriptionsReference Manual Reference Manual RosemountPRIMARY_VALUE_RANGE Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Troubleshooting OverviewRosemount Reference ManualRosemount Reference ManualParameters and Descriptions 00809-0200-4101,Rev AA JulyReference Manual RosemountFLANGE_MTL Reference Manual RosemountREM_SEAL_FILL Reference Manual RosemountSimulate_STATE Block Errors RosemountReference Manual 00809-0200-4101,Rev AA JulyReference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual RosemountMode will not leave Reference Manual RosemountC-14 Rosemount IndexReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual RosemountIndex-4 Reference Manual Rosemount00809-0200-4101,Rev AA July NOTES Rosemount Reference ManualPage ¢00809-0100-4801V¤ RosemountReference Manual