ANALOG INPUT (AI) FUNCTION BLOCK

Reference Manual

00809-0200-4101, Rev AA July 2008

Rosemount 2051

ANALOG INPUT (AI) FUNCTION BLOCK

Configure the AI block

Configure the AI block A minimum of four parameters are required to configure the AI Block. The parameters are described below with example configurations shown at the end of this section.

CHANNEL

Select the channel that corresponds to the desired sensor measurement. The 2051 measures both pressure (channel 1) and sensor temperature (channel 2).

Table 3-1. I/O Channel Definitions

Channel Number

Channel Description

 

 

1

differential pressure in AI.XD_SCALE units

 

 

2

sensor temperature in AI.XD_SCALE units

 

 

L_TYPE

The L_TYPE parameter defines the relationship of the sensor measurement (pressure or sensor temperature) to the desired output of the AI Block (e.g. pressure, level, flow, etc.). The relationship can be direct, indirect, or indirect square root.

Direct

Select direct when the desired output will be the same as the sensor measurement (pressure or sensor temperature).

Indirect

Select indirect when the desired output is a calculated measurement based on the sensor measurement (e.g. a pressure measurement is made to determine level in a tank). The relationship between the sensor measurement and the calculated measurement will be linear.

Indirect Square Root

Select indirect square root when the desired output is an inferred measurement based on the sensor measurement and the relationship between the sensor measurement and the inferred measurement is square root (e.g. flow).

XD_SCALE and OUT_SCALE

The XD_SCALE and OUT_SCALE each include three parameters: 0%, 100%, and, engineering units. Set these based on the L_TYPE:

L_TYPE is Direct

When the desired output is the measured variable, set the XD_SCALE to the “Primary_Value_Range”. This is found in the Sensor Transducer Block. Set OUT_SCALE to match XD_SCALE.

L_TYPE is Indirect

When an inferred measurement is made based on the sensor measurement, set the XD_SCALE to represent the operating range that the sensor will see in the process. Determine the inferred measurement values that correspond to the XD_SCALE 0 and 100% points and set these for the OUT_SCALE.

3-5

Image 49
Contents Reference Manual with FOUNDATION Fieldbus ProtocolRosemount 2051 Pressure Transmitter Page Transmitter with FOUNDATION Fieldbus Rosemount 2051 PressureRosemount Reference ManualPage SECTION 1 Introduction SECTION 2 Installation Table of ContentsSECTION 3 Configuration RosemountSECTION 5 Troubleshooting SECTION Operation and MaintenanceAPPENDIX A Reference Data RosemountAPPENDIX C Block Information APPENDIX B Approval InformationRosemount Reference ManualReference Manual RosemountTOC-4 Section USING THIS MANUAL SERVICE SUPPORTIntroduction RosemountRosemount MODELS COVEREDReference Manual OVERVIEW SAFETY MESSAGES Warnings InstallationSection RosemountCONSIDERATIONS GENERALMECHANICAL ENVIRONMENTALDimensional Drawings INSTALLATION PROCEDURES2051C Coplanar Flange Dimensional Drawing RosemountRosemount Coplanar Flange Mounting Configurations withReference Manual 00809-0200-4101,Rev AARosemount 2051C Coplanar with Traditional FlangeReference Manual Optional Brackets for 2-in.Pipe or Panel Mounting Traditional Flange Mounting Configurations withRosemount Reference Manual2051T with Rosemount 306 Integral Manifold 2051T Dimensional DrawingsRosemount Reference ManualReference Manual RosemountPipe Mounting Panel MountingRosemount 2051L Liquid LevelReference Manual Rosemount Mount the TransmitterReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Rosemount Figure 2-6.Traditional Flange Bolt ConfigurationsReference Manual 00809-0200-4101,Rev AA JulyRosemount Impulse PipingReference Manual Reference Manual RosemountFlow Rosemount Process ConnectionsReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July Rosemount Housing RotationReference Manual Tagging LCD DisplayRosemount Reference ManualELECTRICAL Conduit InstallationRosemount Reference ManualRosemount WiringReference Manual Rosemount Transient Protection Terminal BlockReference Manual Rosemount JumpersSecurityReference Manual Rosemount GroundingReference Manual External Ground Assembly Figure 2-17.External Ground AssemblyRosemount Reference ManualROSEMOUNT 305, 306 AND 304 MANIFOLDS HAZARDOUS LOCATIONS CERTIFICATIONSRosemount Reference ManualProcedure Rosemount 306 Integral Rosemount 305 Integral Manifold InstallationManifold Installation Procedure Rosemount Conventional Manifold Installation ProcedureRosemount Integral Manifold OperationReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July Open Vessels Closed Vessels LIQUID LEVEL MEASUREMENTRosemount Reference ManualReference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual RosemountOVERVIEW SAFETY MESSAGES Warnings ConfigurationSection RosemountCapabilities DEVICE CAPABILITIES Link Active SchedulerGENERAL BLOCK INFORMATION Modes RosemountSimulation RESOURCE BLOCK FEATURES and FEATURES SELRosemount Reference ManualRosemount MAX_NOTIFYReference Manual ANALOG INPUT AI FUNCTION BLOCK Configure the AI blockRosemount Reference ManualRosemount Configuration ExamplesReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Low Cutoff FilteringRosemount Reference ManualStatus Options Process Alarms Alarm PriorityRosemount Reference ManualRosemount Advanced Features LCD BLOCKReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July OVERVIEW SAFETY MESSAGES Warnings Section 4 Operation and MaintenanceRosemount Reference ManualRosemount STATUS Master Reset Method SimulationReference Manual Upper and Lower Trim Methods CALIBRATION Sensor CalibrationRosemount Reference ManualFactory Calibration Method Sensor Calibration, Zero Trim MethodRosemount Reference ManualOVERVIEW SAFETY MESSAGES Warnings Section 5 TroubleshootingRosemount Reference ManualRosemount TROUBLESHOOTING GUIDESReference Manual 00809-0200-4101,Rev AA JulyRosemount Figure 5-2.Problems with communications flowchartReference Manual 00809-0200-4101,Rev AA JulyRosemount Table 5-1.Troubleshooting guideReference Manual 00809-0200-4101,Rev AA JulyRosemount RESOURCE BLOCKReference Manual Rosemount SENSOR TRANSDUCER BLOCKReference Manual Rosemount LCD TRANSDUCER BLOCKReference Manual ANALOG INPUT AI FUNCTION BLOCKRosemount 1.Put Resource block into OOS Out of ServiceReference Manual 00809-0200-4101,Rev AA JulyRemove Terminal Block DISASSEMBLY PROCEDURES Remove from ServiceRosemount Reference ManualRosemount Remove the Electronics BoardReference Manual Electronics Board Install the Terminal Block REASSEMBLY PROCEDURES Attach theReassemble the 2051C Process Flange RosemountRosemount Install the Drain/Vent ValveReference Manual Conformance To Specification ±3σ Sigma PERFORMANCE SPECIFICATIONSAppendix A Reference DataDynamic Performance Long Term StabilityLine Pressure Effect per 1000 psi 6,9 MPa RosemountAmbient Temperature Effect per 50F 28C Vibration Effect Power Supply EffectMounting Position Effects Electromagnetic Compatibility EMCService FUNCTIONAL SPECIFICATIONS Range and Sensor LimitsProtocols RosemountReference Manual Rosemount00809-0200-4101,Rev AA July Rosemount Overpressure LimitsReference Manual Temperature Limits Static Pressure Limit Burst Pressure LimitsRosemount Reference ManualFailure Mode Alarm Humidity Limits Volumetric Displacement DampingRosemount Reference ManualProcess Connections 2051C Process Wetted Parts PHYSICAL SPECIFICATIONS Electrical Connections2051T Process Wetted Parts 2051L Process Wetted PartsRosemount Non-WettedParts for 2051C/T/LReference Manual Table A-4.Transmitter Weights without Options Shipping WeightsTable A-5.2051L Weights without Options Table A-6.Transmitter Options WeightsRosemount ORDERING INFORMATIONReference Manual Reference Manual RosemountAlternate Process Connection: Flange2 Reference Manual RosemountCSA FISCO Intrinsically Safe Reference Manual RosemountA-15 Reference Manual RosemountGGage AAbsolute Reference Manual RosemountFM Intrinsically Safe, Division Reference Manual RosemountSpecial Certifications Q4 Calibration Certificate Prior-usecertificate of FMEDA dataReference Manual Rosemount4 -300to 300 psi/3 psi -20,7to 20,7 bar/0,2 bar Reference Manual RosemountSyltherm XLT Rosemount ATEX Flameproof, Intrinsic Safety, Type n, DustReference Manual Rosemount OPTIONSReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Rosemount SPARE PARTSReference Manual LCD Display, FOUNDATION fieldbusReference Manual RosemountNickel-platedcarbon steel Reference Manual RosemountGage Flange and Adapter Bolt Kit Set of Reference Manual RosemountA-28 Appendix B Approval Information OVERVIEW SAFETY MESSAGESWarnings Approved Manufacturing LocationsFIELDBUS PROTOCOL European Directive InformationHazardous Locations Certifications RosemountReference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Rosemount APPROVAL DRAWINGS Factory Mutual FMReference Manual Reference Manual RosemountReference Manual RosemountB-10 Reference Manual RosemountB-11 Reference Manual RosemountB-12 Reference Manual RosemountB-13 Reference Manual RosemountB-14 Reference Manual RosemountB-15 Reference Manual RosemountB-16 Reference Manual RosemountB-17 Reference Manual RosemountB-18 Reference Manual RosemountB-19 Reference Manual RosemountB-20 Rosemount Canadian Standards Association CSAReference Manual B-21Reference Manual RosemountB-22 Reference Manual RosemountB-23 Reference Manual RosemountB-24 Reference Manual RosemountB-25 Reference Manual RosemountB-26 Reference Manual RosemountB-27 Reference Manual RosemountB-28 Reference Manual RosemountB-29 Reference Manual RosemountB-30 Block Information Appendix CTRANSDUCER BLOCK Overview RosemountRosemount Parameters and DescriptionsReference Manual Reference Manual RosemountPRIMARY_VALUE_RANGE Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Overview TroubleshootingRosemount Reference ManualReference Manual RosemountParameters and Descriptions 00809-0200-4101,Rev AA JulyReference Manual RosemountFLANGE_MTL Reference Manual RosemountREM_SEAL_FILL Reference Manual RosemountSimulate_STATE Rosemount Block ErrorsReference Manual 00809-0200-4101,Rev AA JulyReference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual RosemountMode will not leave Reference Manual RosemountC-14 Rosemount IndexReference Manual Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual Rosemount00809-0200-4101,Rev AA July Reference Manual RosemountIndex-4 Reference Manual Rosemount00809-0200-4101,Rev AA July NOTES Reference Manual RosemountPage ¢00809-0100-4801V¤ RosemountReference Manual