Goodman Mfg RT6100004R13 Servicing, Checking Voltage Checking Wiring, 3A Thermostat and Wiring

Page 30

SERVICING

S-1 CHECKING VOLTAGE

S-2 CHECKING WIRING

1. Remove outer case, control panel cover, etc., from unit being tested.

With power ON:

WARNING

Line Voltage now present.

2.Using a voltmeter, measure the voltage across terminals L1 and L2 of the contactor for the condensing unit or at the field connections for the air handler or heaters.

3.No reading - indicates open wiring, open fuse(s) no power or etc., from unit to fused disconnect service. Repair as needed.

4.With ample voltage at line voltage connectors, energize the unit.

5.Measure the voltage with the unit starting and operating, and determine the unit Locked Rotor Voltage. NOTE: If checking heaters, be sure all heating elements are energized.

Locked Rotor Voltage is the actual voltage available at the compressor during starting, locked rotor, or a stalled condition. Measured voltage should be above minimum listed in chart below.

To measure Locked Rotor Voltage attach a voltmeter to the run "R" and common "C" terminals of the compressor, or to the T1 and T2 terminals of the contactor. Start the unit and allow the compressor to run for several seconds, then shut down the unit. Immediately attempt to restart the unit while measuring the Locked Rotor Voltage.

6.Lock rotor voltage should read within the voltage tabula- tion as shown. If the voltage falls below the minimum voltage, check the line wire size. Long runs of undersized wire can cause low voltage. If wire size is adequate, notify the local power company in regard to either low or high voltage.

REMOTE CONDENSING UNITS

BLOWER COILS

VOLTAGE

MIN.

MAX.

 

 

 

208/230

198

253

 

 

 

115

104

127

 

 

 

NOTE: When operating electric heaters on voltages other than 240 volts, refer to the System Operation section on electric heaters to calculate temperature rise and air flow. Low voltage may cause insufficient heating.

1.Check wiring visually for signs of overheating, damaged insulation and loose connections.

2.Use an ohmmeter to check continuity of any suspected open wires.

3.If any wires must be replaced, replace with comparable gauge and insulation thickness.

S-3 CHECKING THERMOSTAT, WIRING, AND ANTICIPATOR

THERMOSTAT WIRE SIZING CHART

LENGTH OF RUN

MIN. COPPER WIRE

GAUGE (AWG)

 

25 feet

18

50 feet

16

75 feet

14

100 feet

14

125 feet

12

150 feet

12

S-3A THERMOSTAT AND WIRING

WARNING

Line Voltage now present.

With power ON, thermostat calling for cooling

1.Use a voltmeter to check for 24 volts at thermostat wires C and Y in the condensing unit control panel.

2.No voltage indicates trouble in the thermostat, wiring or external transformer source.

3.Check the continuity of the thermostat and wiring. Repair or replace as necessary.

Indoor Blower Motor

With power ON:

WARNING

Line Voltage now present.

1.Set fan selector switch at thermostat to "ON" position.

2.With voltmeter, check for 24 volts at wires C and G.

3.No voltage indicates the trouble is in the thermostat or wiring.

30

Image 30
Contents Service Instructions Table of Contents Important InformationSafe Refrigerant Handling Product Identification Split System Air Conditioners R-22Split System Air Conditioners R-22 Split System Heat Pumps R-22 Product Identification Single Piece Air Handlers Single Piece Air Handlers MBR/MBE Air Handlers 036 036 120 3642 1824 Accessories ASC01CPKF24 CPKF36 CPKF42 CPKF48 CPKF60 CPKF61 Expansion Valve Kits FSK01A Coil Accessories Product Design Condensing UnitProduct Design System Operation HeatingCooling Cycle System Operation Indoor Coil Outdoor Thermostatic Expansion Valve AFE18-60A Control Board DescriptionTroubleshooting Chart COOLING/HP Analysis ChartServicing Table of Contents 3A Thermostat and Wiring Checking Voltage Checking WiringChecking THERMOSTAT, WIRING, and Anticipator Servicing3B Cooling Anticipator 3C Heating AnticipatorChecking Transformer Control Circuit Checking Time Delay RelayTesting Coil Circuit Checking Cycle ProtectorChecking Contactor AND/OR Relays Testing Compressor ContactorTesting FAN Relay Checking Contactor ContactsCopeland Comfort Alert Diagnostics Applies to ASC13 & ASH13Diagnostics Table Red TripChecking Loss of Charge Protector Hard Start KIT WiringTesting Capacitor Resistance Checking Capacitor16A Checking FAN and Blower Motor Windings PSC Motors Testing Capacitance15B Capacitance Check 16B Checking FAN and Blower Motor ECM Motors16D ECM CFM Adjustments 16C Checking ECM Motor WindingsChart on Next Chart from Previous Itc h 17A Resistance Test 16E Checking GE X13TM MotorsChecking Compressor GE X13TM Motor Connections17D Operation Test Testing Compressor Windings17B Ground Test Compressor Ground TestTesting Defrost Thermostat Testing Crankcase Heater Optional ItemTesting Defrost Control Checking Reversing Valve and SolenoidAR*F & MBR With Single Stage Condensers 40 AR*F & MBR Electronic Blowers Time Delay RelaySequence of Operation AR*F & MBR With Single Stage Heat PumpsAEP* & MBE Electronic Blower Time Delay Relay 41 AEP* & MBE with Single Stage CON Densers41A AEP* & MBE with Single Stage Heat Pumps Electric Heater Optional Item Temperature Rise F @ CFM 61A Checking Heater Limit ControlsChecking Heater Elements Leak Testing Nitrogen or NITROGEN-TRACED61B Checking Heater Fuse Link Optional Electric Heaters Refrigeration Repair PracticeEvacuation ChargingEvacuation Checking Compressor Efficiency An inaccurately charged system will cause future prob- lems105B Thermostatic Expansion Valve Superheat OverfeedingUnderfeeding Thermostatic Expansion ValvesChecking Subcooling Checking Expansion Valve OperationNON-CONDENSABLES Overcharge of RefrigerantChecking Restricted Liquid Line Compressor BurnoutSuction Line Drier Clean-Up Method Refrigerant PipingInstallation Requirements Reversing Valve Replacement System ChargingTotal External Static AIR Handler External StaticCoil Static Pressure Drop Static Pressure DropAccessories Wiring Diagrams ALL Fuel System AFE18-60A Control BoardALL Fuel System Control Board AFE18-60A 10kw and Below, One Stage Electric Heat OT/EHR18-60 #2 GRD PLM PLF XFMR-R XFMR-C After Installing Optional Heat KIT, Mark AN X Provided Above HKR Heat Kit GRD PLM PLF Accessories Wiring Diagrams