SERVICING

DIPSWITCH FUNCTIONS

The MBE air handler motor has an electronic control that contains an eight (8) position dip switch. The function of these dipswitches are shown in Table 1.

Dipswitch Number

Function

1

Electric Heat

2

 

3

N/A

4

Indoor Thermostat

5

Cooling & Heat Pump CFM

6

 

7

CFM Trim Adjust

8

 

 

Table 1

CFM DELIVERY

Tables 2, 2A and 3, 3A show the CFM output for dipswitch combinations 1-2, 5-6 and 7-8.

Electric Heat Operation

Model

Switch 1

Switch 2

CFM

 

OFF

OFF

1,200

MBE1200

ON

OFF

1,000

OFF

ON

800

 

 

ON

ON

600

 

OFF

OFF

1,600

MBE1600

ON

OFF

1,400

OFF

ON

1,200

 

 

ON

ON

1,000

 

OFF

OFF

2,000

MBE2000

ON

OFF

1,800

OFF

ON

1,600

 

 

ON

ON

1,200

 

Table 2

 

Cooling/Heat Pump Operation

 

Model

Switch 5

Switch 6

CFM

 

OFF

OFF

1,200

MBE1200

ON

OFF

1,000

OFF

ON

800

 

 

ON

ON

600

 

OFF

OFF

1,600

MBE1600

ON

OFF

1,400

OFF

ON

1,200

 

 

ON

ON

1,000

 

OFF

OFF

1,600

MBE2000

ON

OFF

1,400

OFF

ON

1,200

 

 

ON

ON

1,000

Table 2A

Dipswitch 1/2 & 7/8

 

 

 

 

 

 

 

 

 

 

 

 

AEPF 1830

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

 

Switch

Switch

 

Emergency

 

Heat Pump

Element

 

Position

Position

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Backup

 

With Backup

 

(kw)

 

1

 

 

2

7

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UP TO 10

 

OFF

 

OFF

OFF

 

 

OFF

 

 

1100

 

1210

UP TO 10

 

ON

 

OFF

OFF

 

 

OFF

 

 

890

 

935

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

OFF

 

ON

OFF

 

 

OFF

 

 

700

 

770

AEPF3036 / 3137 / 4260

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

 

Switch

Switch

 

Emergency

 

Heat Pump

Element

 

Position

Position

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Backup

 

With Backup

 

(kw)

 

1

 

 

2

7

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UP TO 20

 

OFF

 

OFF

OFF

 

 

OFF

 

 

2050

 

2150

UP TO 20

 

ON

 

OFF

OFF

 

 

OFF

 

 

1750

 

1835

UP TO 15

 

OFF

 

ON

OFF

 

 

OFF

 

 

1600

 

1680

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UP TO 10

 

ON

 

ON

OFF

 

 

OFF

 

 

1200

 

1260

UP TO 10

 

ON

 

ON

OFF

 

 

ON

 

 

1020

 

1070

 

 

 

 

 

 

 

 

Table 3

 

 

 

 

 

 

 

 

 

Dipswitch 5/6 & 7/8

 

 

 

 

 

 

 

 

 

 

 

 

AEPF 1830

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Switch

 

 

Switch

 

 

 

Indoor Airflow

 

 

Position

 

 

Position

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

6

 

 

7

8

 

 

Cooling

 

Heat Pump

 

 

OFF

 

OFF

 

 

OFF

OFF

 

 

1100

 

 

1100

 

 

ON

 

OFF

 

 

OFF

OFF

 

 

800

 

 

800

 

 

OFF

 

 

ON

 

 

OFF

OFF

 

 

600

 

 

600

 

 

AEPF3036 / 3137 / 4260

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Switch

 

 

Switch

 

 

 

Indoor Airflow

 

 

Position

 

 

Position

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

6

 

 

7

8

 

 

Cooling

 

Heat Pump

 

 

OFF

 

OFF

 

 

OFF

OFF

 

 

1800

 

 

1800

 

 

ON

 

OFF

 

 

OFF

OFF

 

 

1580

 

 

1580

 

 

OFF

 

 

ON

 

 

OFF

OFF

 

 

1480

 

 

1480

 

 

ON

 

 

ON

 

 

OFF

OFF

 

 

1200

 

 

1200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

ON

 

 

OFF

ON

 

 

1020

 

 

1020

 

Table 3A

THERMOSTAT “FAN ONLY” MODE

During Fan Only Operations, the CFM output is 30% of the cooling setting.

CFM TRIM ADJUST

Minor adjustments can be made through the dip switch combination of 7-8. Table 4 shows the switch position for this feature.

NOTE: The airflow will not make the decreasing adjustment in Electric Heat mode.

C FM

S w itc h 7

S w itc h 8

+ 1 0 %

O N

O F F

-1 5 %

O F F

O N

Table 4

41

Image 41
Contents Service Instructions Important Information Table of ContentsSafe Refrigerant Handling Split System Air Conditioners R-22 Product IdentificationSplit System Air Conditioners R-22 Split System Heat Pumps R-22 Product Identification Single Piece Air Handlers Single Piece Air Handlers MBR/MBE Air Handlers 036 036 120 3642 1824 ASC01 AccessoriesCPKF24 CPKF36 CPKF42 CPKF48 CPKF60 CPKF61 Expansion Valve Kits FSK01A Coil Accessories Condensing Unit Product DesignProduct Design Heating System OperationCooling Cycle System Operation Indoor Coil Outdoor Thermostatic Expansion Valve Description AFE18-60A Control BoardCOOLING/HP Analysis Chart Troubleshooting ChartServicing Table of Contents Checking THERMOSTAT, WIRING, and Anticipator Checking Voltage Checking Wiring3A Thermostat and Wiring Servicing3C Heating Anticipator 3B Cooling AnticipatorTesting Coil Circuit Checking Time Delay RelayChecking Transformer Control Circuit Checking Cycle ProtectorTesting FAN Relay Testing Compressor ContactorChecking Contactor AND/OR Relays Checking Contactor ContactsApplies to ASC13 & ASH13 Copeland Comfort Alert DiagnosticsRed Trip Diagnostics TableTesting Capacitor Resistance Hard Start KIT WiringChecking Loss of Charge Protector Checking Capacitor15B Capacitance Check Testing Capacitance16A Checking FAN and Blower Motor Windings PSC Motors 16B Checking FAN and Blower Motor ECM Motors16C Checking ECM Motor Windings 16D ECM CFM AdjustmentsChart on Next Chart from Previous Itc h Checking Compressor 16E Checking GE X13TM Motors17A Resistance Test GE X13TM Motor Connections17B Ground Test Testing Compressor Windings17D Operation Test Compressor Ground TestTesting Defrost Control Testing Crankcase Heater Optional ItemTesting Defrost Thermostat Checking Reversing Valve and SolenoidSequence of Operation 40 AR*F & MBR Electronic Blowers Time Delay RelayAR*F & MBR With Single Stage Condensers AR*F & MBR With Single Stage Heat Pumps41 AEP* & MBE with Single Stage CON Densers AEP* & MBE Electronic Blower Time Delay Relay41A AEP* & MBE with Single Stage Heat Pumps Electric Heater Optional Item 61A Checking Heater Limit Controls Temperature Rise F @ CFM61B Checking Heater Fuse Link Optional Electric Heaters Leak Testing Nitrogen or NITROGEN-TRACEDChecking Heater Elements Refrigeration Repair PracticeEvacuation EvacuationCharging An inaccurately charged system will cause future prob- lems Checking Compressor Efficiency105B Thermostatic Expansion Valve Underfeeding OverfeedingSuperheat Thermostatic Expansion ValvesChecking Expansion Valve Operation Checking SubcoolingChecking Restricted Liquid Line Overcharge of RefrigerantNON-CONDENSABLES Compressor BurnoutRefrigerant Piping Suction Line Drier Clean-Up MethodInstallation Requirements System Charging Reversing Valve ReplacementCoil Static Pressure Drop AIR Handler External StaticTotal External Static Static Pressure DropALL Fuel System Control Board AFE18-60A Accessories Wiring DiagramsALL Fuel System AFE18-60A Control Board 10kw and Below, One Stage Electric Heat OT/EHR18-60 #2 GRD PLM PLF XFMR-R XFMR-C After Installing Optional Heat KIT, Mark AN X Provided Above HKR Heat Kit GRD PLM PLF Accessories Wiring Diagrams